Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 14

CHAPTER 8

LOCATION AND
SIZING SUBSTATION

1
CONTENT

• SUBSTATION LOCATION
• THE RATING OF A SUBSTATION
◦ Square Shape
◦ Hexagonally Shape
• SUBSTATION SERVICE AREA WITH N
PRIMARY FEEDRS
• VOLTAGE DROP CALCULATION

2
SUBSTATION LOCATION
 SELECTING LOCATION FOR SUBSTATION
• As much as feasible close to the load center of its service
area, proper voltage regulation can be obtainable without
taking extensive measures.
• Provides proper access for incoming subs-transmission lines
and outgoing primary feeder.
• Provide enough space for the future substation expansion.
• The selected substation should not be opposed by land use
regulations, local ordinances, and neighbors.
• The selected substation location should help to minimize
the number of customers affected by any service
discontinuity.
• Other considerations, such as adaptability, emergency.

3
SUBSTATION LOCATION
 Steps of the rule to a service area map
1. Draw a straight line between a proposed
substation site and each of its neighbors
2. Perpendicularly bisect each of those line
3. The set of all the perpendicular bisectors a
round a substation defines its service
territory.
4. The target load for this substation will be
the sum of all loads in its service territory.
4
SUBSTATION LOCATION

The perpendicular bisector rule for planning expansion

5
THE RATING OF A
SUBSTATION
The additional capacity requirements of
a system with increasing load density
can be met by:
◦ Either holding the service area of a given
substation constant and increasing its
capacity
◦ Developing new substations and thereby
holding the rating of the given substations
constant.

6
THE RATING OF A SUBSTATION

Square Shaped Distribution Substation Service Area

7
THE RATING OF A
SUBSTATION
 Square Shaped
 Serves total load of each feeder is, S4 = A4 x D kVA
 Where,
◦ S4 is kVA load served by one of four feeder emanating
from a feed point.
◦ A4 is area served by one of four feeders emanating from
a feed point, mi2
◦ D : load density, kVA/mi2
 S4 = l42 x D kVA
◦ Since, A4 = l42
 TSn = n x D x An = total kVA supplied from feed point
(size)
◦ N is no of feeder

8
THE RATING OF A SUBSTATION

2 2
6 6

Hexagonally shaped service area supplied

9
THE RATING OF A
SUBSTATION
 Hexagonally shaped
l6
A6  xl6  0.578 xl 62
3
◦ A6 = area served by one of six feeders
emanating from a feed point, mi2
◦ l6 2 = linear dimensions of a primary feeder
service area, mi
 Each feeder serves a total load, S 6 =
A6 x D kVA or S6 = 0.578 x D x l62

10
THE RATING OF A SUBSTATION
Substation Service Area served by n primary feeder

The total kVA load served by one of n feeders


In
Sn    n x tan 
2
dS Dxl
x 0
11
VOLTAGE DROP CALCULATION
(2 / 3xl n ) K (nxDxAn )
%VDn 
n
or

%VDn  (2 / 3 xl n xK ) S n

 Where
◦ % VDn = percent voltage drop in primary feeder circuit
◦ 2/3 x ln = effective length of primary feeder
◦ K = % VD/(A.mi) of the feeder (the value of K is obtained
from Figure)
◦ An = Area served by one feeder
◦ n = number of primary feeders
◦ D = Load density.

12
VOLTAGE DROP CALCULATION
The K constant for conductors

13
Example
To illustrate distribution substation sizing and spacing,
assume a squared-shaped distribution substation service
area assume that the substation is served by three phase
four wire 2.4/4.16 kV grounded wye primary feeders. The
feeders mains are made of 2 AWG cooper conductors with
maximum current capacity is 230 A. Assume a lagging
load power factor of 0.9 and a 1000 kVA/km uniformly
distributed load density. Calculate the following :-

1. Maximum load per feeder


2. Substation size
3. Substation spacing
4. Total percentage voltage drop from the feed point the end
of the main
5. If the distribution substation service is hexagon shaped,
calculate 2-4

14

You might also like