Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 22

PER UNIT SYSTEM

Per unit system


 A key problem in analyzing power systems is the large number of
transformers.
– It would be very difficult to continually have to refer impedances to the different
sides of the transformers
This problem is avoided by a normalization of all variables.

This normalization is known as per unit analysis

In power system analysis, it is common practice to use per-unit quantities


for analyzing and communicating voltages, current, power, and impedance
values.
Per unit system
 These per-unit quantities are normalized or scaled on a selected
base, allowing engineers to simplify power system calculations with
multiple voltage transformations

Therefore;
actual quantity
quantity in per unit =
base value of quantity
Per Unit Conversion Procedure
Pick a 1f VA base for the entire system, SB

Pick a voltage base for each different voltage level, VB. Voltage bases are
related by transformer turns ratios. Voltages are line to neutral.

Calculate the impedance base, ZB= (VB)2/SB

Calculate the current base, IB = VB/ZB

Convert actual values to per unit


Per unit system
Note:
 Per unit conversion affects magnitudes,

Angles are not affected

If the nominal value is chosen as the base voltage, a “normal” voltage
value will be close to 1.0 p.u

 Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u.
volts) except under certain conditions
Advantages of per unit system
ordinary parameters vary considerably with variation of physical size,
terminal voltage and power rating etc. while per unit parameters are
independent of these quantities over a wide range of the same type of
apparatus. In other words, the per unit impedance values for the
apparatus of like ratings lie within a narrow range

It provide more meaningful information.

The chance of confusion between line and phase values in a three-phase


balanced system is reduced. A per unit phase quantity has the same
numerical value as the corresponding per unit line quantity regardless of
the three-phase connection whether star or delta.
Advantages of per unit system cont’d
Impedances of machines are specified by the manufacturer in terms of
per unit values.
The per unit impedance referred to either side of a single-phase
transformer is the same.
 The per unit impedance referred to either side of a three -phase
transformer is the same regardless of the connection whether they are
∆-∆, Y-Y or ∆-Y.
The computation effort in power system is very much reduced with the
use of per unit quantities.
 Usually, the per unit quantities being of the order of unity or less can
easily be handled with a digital computer. Manual calculation are also
simplified. Per unit quantities simply theoretical deduction and give
them more generalizes forms.
example
•Example: nominal voltage at bus bar A is 132 kV and actual voltage at
A is 127 kV. The per unit voltage at A is:
Rules for Choosing Base Values

 Choose ONE base power for the entire system


Arbitrary choice
Commensurate with the system

e.g. 400V use 100kVA or 1MVA, 11kV use 10MVA,


 132KV use 100MVA, 400kV use 1000MVA
 Choice also depends on rating of generators/transformers

 e.g. commercial/industrial building = mainly 400V use 100kVA


 distribution utility = mainly 11kV use 10MVA
Rules for Choosing Base Values cont’d
Choose ONE base voltage for voltage level “of most interest”
Choose the nominal voltage,
Each voltage level must have one base voltage, between two base voltages the
connecting transformer turns ratio must be maintained

Other base values chosen to get the same relations between per unit
quantities as between actual quantities – electrical laws (ohms law,….) will
not be broken under per unit system

With the base power and base Voltage determined, the base current and
base impedance can be calculated
Rules for Choosing Base Values cont’d
• That is;
• For a three phase system,
Per unit example

• Solve for the current, load voltage and load power in the circuit
shown below using per unit analysis with an SB of 100 MVA, and
voltage bases of 8 kV, 80 kV and 16 kV, respectively.
Per unit example cont’d
82 (kV) 2
Z BLeft = = 0.64W
100MVA
802 (kV) 2
Z BMiddle = = 64W
100MVA
162 (kV) 2
Z BRight = = 2.56W
100MVA

Same circuit, with


values expressed
in per unit
Per unit example cont’d

1.0а 0
I = = 0.22�- 30.8�p.u. (not amps)
3.91 + j 2.327
VL =а-�-0��0.22
1.0 2.327�30.8
90�
= 0.859�- 30.8�p.u.
2
VL
SL = VL I L*
= = 0.189 p.u.
Z
SG =а�а
1.0 =0.22 а
0 0.22 30.8 30.8 p.u.
Per unit example cont’d
To convert back to actual values just multiply the
per unit values by their per unit base

V LActual = 0.859�- 30.8�


�16 kV = 13.7�- 30.8�kV
S LActual =а� =а 0
0.189 100 MVA 18.9 0 MVA
SGActual =а�
0.22=а30.8 100 MVA 22.0 30.8 MVA
100 MVA
I BMiddle = = 1250 Amps
80 kV
Actual
I Middle = 0.22�- 30.8�
�1250 = 275�- 30.8�A
Calculation in 3 phase “Homework”
Solve for the current, load voltage and load power in the
previous circuit, assuming:
–a 3f power base of 300 MVA, 
–and line to line voltage bases of 13.8 kV, 138 kV  and 27.6 kV 
–the generator is Y­connected so its line to line voltage is 13.8 kV.    
Change of MVA Base in per unit
Parameters for equipment are often given using power rating of
equipment as the MVA base
To analyze a system all per unit data must be on a common power base

OriginalBase NewBase
Z pu � Z actual � Z pu
2 2
OriginalBase Vbase Vbase NewBase
Hence Z pu � OriginalBase / NewBase = Z pu
S Base S Base
NewBase
S Base
ZOriginalBase
pu � OriginalBase
= Z NewBase
pu
S Base
example
 Example: A 350 MVA, 230/20 kV transformer has leakage reactance
of 10%. What is p.u. value on 100 MVA base? What is value in
ohms (230 kV)?
100
X e = 0.10 � = 0.0286 p.u.
350
230 2
0.0286 � = 15.1 W
100
• In general for change of MVA base,

• In cases where the new base Voltage equates to the old base voltage,
then;
Calculation example questions

• A 3phase two winding transformer is rated at 75MVA,


11.8/145kV, 50Hz and the equivalent leakage impedance
referred to the 11.8kV
• Using the transformer ratings as base values, determine the
per-unit leakage impedances referred to the 11.8kV winding and
the 145kV winding.
• winding is Zeq = 0.22Ω
Example question 2
For the power network shown below calculate using per-unit
quantities the voltage in kV, the current in kA and the power in kW
received by the load

• G1 = synchronous generator = 75MVA, 11.8kV, sync reactance Xd = j1.83 p.u.


• T1 = generator transformer = 75MVA, 11.8kV/145kV X = j0.125 p.u.
• L1 = 132kV transmission line: Z = 0.18 + j0.40 Ω/km, length = 20km.
• T2 = step-down transformer = 45MVA, 132kV/11kV, X = j0.125 p.u.
• ZL = 11kV load = 10MVA, cosɸ = 0.8 (lagging).

You might also like