Nominal Data Generator: Apparent Power MVA 778 1 p.u. Nominal Voltage kV 20 1 p.u. Nominal Current kA 22.458 1 p.u.
Ratio Current and Voltage Transformers:
Current transformer 30000 A / 1A Voltage transformer 20000 V / 100V
Calculation of Reference value:
1A 1 Re fcurrent 22458 A 0.748 30000 A 1A 100V 1 Re fvoltage 20000V 1.000 20000V 100V SYSTEM - SengSysA.set 01-06-2003 07:59 List AD Channels
Ch. 1 Protection CT 3ph - R 0.683 CT1
Used by : 1 Diff-Gen CurrentInp GEN DIFF PROT 87G Ch. 2 Protection CT 3ph - S 0.683 CT1 Ch. 3 Protection CT 3ph - T 0.683 CT1 Ch. 4 Protection CT 3ph - R 0.683 CT7 Used by : 6 Diff-Transf CurrentInp2 GEN TRF DIFF PROT 87T Used by : 8 Current-DT CurrentInp GEN CB FAILURE BF Ch. 5 Protection CT 3ph - S 0.683 CT7 Ch. 6 Protection CT 3ph - T 0.683 CT7 Power Chart Diagramm Hydro Sudden short circuit Test S=120MVA