The document summarizes the excitation system for a synchronous generator. It describes that the excitation system consists of an excitation power unit and excitation regulator. The excitation power unit supplies DC exciting current to the rotor winding, while the excitation regulator controls the output of the power unit based on control signals. The main functions of the excitation system are to maintain generator terminal voltage and control reactive power distribution. It then discusses the specific SPPA-E3000-SES530 static excitation system used for a 622MW unit, including its components, operation modes, and startup/shutdown procedures.
The document summarizes the excitation system for a synchronous generator. It describes that the excitation system consists of an excitation power unit and excitation regulator. The excitation power unit supplies DC exciting current to the rotor winding, while the excitation regulator controls the output of the power unit based on control signals. The main functions of the excitation system are to maintain generator terminal voltage and control reactive power distribution. It then discusses the specific SPPA-E3000-SES530 static excitation system used for a 622MW unit, including its components, operation modes, and startup/shutdown procedures.
The document summarizes the excitation system for a synchronous generator. It describes that the excitation system consists of an excitation power unit and excitation regulator. The excitation power unit supplies DC exciting current to the rotor winding, while the excitation regulator controls the output of the power unit based on control signals. The main functions of the excitation system are to maintain generator terminal voltage and control reactive power distribution. It then discusses the specific SPPA-E3000-SES530 static excitation system used for a 622MW unit, including its components, operation modes, and startup/shutdown procedures.
Part one The introduction of excitation system The excitation system of synchronous generator is mainly composed of two parts : 1) Excitation power unit Excitation power unit is the excitation power supply to provide DC exciting current to rotor winding of synchronous generator. 2) excitation regulator (device) Excitation regulator is the device that control output of excitation power unit which according to the input signal of control requirements and the adjustment criterion. • The entire system is composed of excitation regulator, excitation power unit and generator itself, which is called excitation control system. The main functions of excitation system 1)According to the change of generator load to correspondingly adjust the exciting current in order to maintain the voltage of generator terminal as a given value. 2) Control reactive power distribution of each generator which runs in parallel. 3)Improve the static stability of the generators running in parallel. 4)Improve the transient stability of the generator running in parallel. 5)When the internal generator has malfunction, make field discharged to minimize breakdown losses. 6)Make maximum excitation limits and minimum excitation limit for the generators according to the operation requirements. The performance requirements of excitation system for 600MW units • The basic requirements are as follow 1) Excitation energy should satisfy the demands under the various working conditions when generator is normal or fault. 2) Ensure the reliability and stability of generators operation. 3) It should be able to maintain a constant terminal voltage of the generators and guarantee a certain precision. The parallel units could stably share the reactive power. 4) With a certain strong excitation capacity. When the strong excitation is 2 times, response ratio is 3.5 times. 5) In lock of excitation area to guarantee generators operate normally. 6) Protection for over-voltage and over magnetic flux. 7) Provide positive damping for the unit oscillation, improve the dynamic stability. Part two SPPA-E3000-SES530 type self-shunt excitation of static excitation system The 622 MW unit excitation system of this project mainly adopts the Siemens SIMOREG 6RA70 series products excitation regulator, The Set of excitation system produced by China Zhang Yu Electric Company, static excitation systems for synchronous generator model SPPA-E3000- SES530;, SPPA-E3000-SES 530 excitation system introduction
• Siemens self shunt excitation system group mainly use
the all-digital control device for which SIMOREG 6RA70 series rectifying device is of the power supply of the three-phase AC current, the structure is compactness, and the system can be expanded through parallel connection with the SIMOREG rectifying device
• The main components of it are: excitation transformer,
excitation regulator, silicon controlled rectifier, the magnetizing excitation and de-excitation unit. The operation and adjustment of excitation system. The main control methods of SPPA-E3000-SES530 excitation system are as follow: 1) Conduct the remote control with the screen monitor control command in the control room. 2)Conduct the local control with local control unit (local control screen) integrated in the excitation system. The main control mode of SPPA-E3000- SES530 excitation system 1)Local / Manual Operation Mode - Regulation Mode of the Excitation Current The set value of excitation current is regarded as the regulation foundation of the regulator under this mode. The set value of excitation current is directly input in the OP panel. This mode is only used in the commissioning installation or emergency. 2) Local / Automatic Operation Mode - Voltage Regulation Mode at the Engine End The set value of the voltage of generator terminal is regarded as the regulation foundation of the regulator under this mode. This mode is only used in the commissioning installation or emergency. The main control mode of SPPA-E3000- SES530 excitation system 1)Local / Manual Operation Mode - Regulation Mode of the Excitation Current The set value of excitation current is regarded as the regulation foundation of the regulator under this mode. The set value of excitation current is directly input in the OP panel. This mode is only used in the commissioning installation or emergency. 2) Local / Automatic Operation Mode - Voltage Regulation Mode at the Engine End The set value of the voltage of generator terminal is regarded as the regulation foundation of the regulator under this mode. This mode is only used in the commissioning installation or emergency. The main control mode of SPPA-E3000- SES530 excitation system 3) Remote / Manual Running Mode - Regulation Mode of the Excitation Current The set value of excitation current is regarded as the regulation foundation of the regulator under this mode. The set value of excitation current is input in the control room, and when the transmission mode is the communication way, the analog value can be directly input in control room, or the set value of excitation current can be given in the mode of excitation increase and decrease. If the transmission mode is only provided with hard-wired method, the set value is generally given with the mode of excitation increase and decrease The main control mode of SPPA-E3000- SES530 excitation system 4) Remote / Automatic Operation Mode – Voltage Regulation Mode at the Engine End Such operation mode is a half of operation mode of the excitation regulator, i.e. fully automatic operation mode. The monitoring room only records its feedback value. The set value of the generator terminal voltage is regarded as the regulation foundation of the regulator under this mode. In other words, only the generator end voltage is adjusted. Some effects will bring on the reactive power and power factor, when the generator is grid-connected, the generator end voltage will be adjusted The main control mode of SPPA-E3000- SES530 excitation system 4) Remote / Automatic Operation Mode – Voltage Regulation Mode at the Engine End Such operation mode is a half of operation mode of the excitation regulator, i.e. fully automatic operation mode. The monitoring room only records its feedback value. The set value of the generator terminal voltage is regarded as the regulation foundation of the regulator under this mode. In other words, only the generator end voltage is adjusted. Some effects will bring on the reactive power and power factor, when the generator is grid-connected, the generator end voltage will be adjusted The control principle of excitation system The redundancy design of siemens excitation system means that the system contains two sets of completely identical control systems (main set and subordinate set). Each set of the control system contains exactly the same. Under the state of normal operation of the system, only a set of control system is operated to send out the triggering pulse to rectifier bridge. Another set in the reheating wait state monitors the controller in working condition, so that the control work is successfully and smoothly taken over under the fault state. The subordinate set does not output, but the set value of the subordinate set always trails the actual value of the main set,so that two sets of systems are always in the synchronization state during the waiting process. Check before the start of the excitation system
1) The maintenance of the system has been completed.
2) Control cabinet and power cabinet are read for running and being locked properly. 3) The generator in the standby state, the temporary ground wire has been removed. 4) The control power of field discharge switch and the regulator power have been powered on. 5) No alarm signal and fault information. 6) The excitation system has been switched to remote control mode. 7) The excitation system has been switched to automatic operation mode. 8) The generator has reached the rated speed (Check the displayed revolving speed in the display meter.) The Start-up of excitation system • Note Start-up Conditions 1. GCB of the generator is off 2. n>90% 3. No shutdown command and trip signals 4. Auxiliary power of Build excitation is supply The shutdown of excitation system • Note: when the generator outlet switch is in the switch-off state, the shutdown command can be executed. • When require emergency shutdown excitation system, you can use the emergency stop button on the control panel in the control room