Análisis de Exergía de La Utilización de PCMs en Refrigeración
Análisis de Exergía de La Utilización de PCMs en Refrigeración
Análisis de Exergía de La Utilización de PCMs en Refrigeración
Antofagasta Meeting 1
PCMSOL Project
8-9, November 2018
Introduction
24/08/2018
Universidad de
Almeria
24/08/2018
Conservation
temperature= 5°C
3
Operation of the System
24/08/2018
4
Views of the System:
Cold Rooms PV panels
24/08/2018
5
PCM cold storage tank
Exergy use in a cold room
Solar gain
Ti < To
Ventilation loss
Internal gain
Conduction gain
Ti
𝑄ሖ
Work
To; Po
𝑇ℎ − 𝑇𝑐 25𝐾
𝑊𝑟𝑒𝑣. = 𝑄ሶ = 𝑄ሶ = 0.051𝑄ሶ
𝑇𝑐 293𝐾
24/08/2018
Exergy Supply/Demand
Exergy saved
Direct cooling
0h 12 h 24 h 7
daytime
Operation mode of the cooling System
24/08/2018
8
Preliminary Results of Energy Consumption
24/08/2018
Exergy
Operation Mode consumption
[kWh]
24/08/2018
Heat from breathing
of products
10
Heat income from
Convective heat ventilation
infiltration
Cooling and exergy demand without cold
storage
24/08/2018
10% 14%
27%
49%
24/08/2018
5%
19%
16%
Cooling demand 492,35 [MJ]
9%
48%
Carga de producto
Carga por infiltración de calor
Carga por renovación de aire
Carga por iluminación 12
Carga del tanque
Cooling and exergy demand with sensible
cold storage
6%
24/08/2018
14%
13%
Cooling demand 459,48[MJ]
7%
4%
Exergy needed 8,29 [MJ]
56%
Carga de producto
Carga por infiltración de calor
Carga por renovación de aire
Carga por iluminación 13
Carga del tanque
Grassman diagram for a cold room without
cold storage
24/08/2018
Exergy efficiency = 6,56%
14
Grassmann diagram for a cold room with
sensible heat cold storage
24/08/2018
Exergy efficiency = 3,13%
15
Grassmann diagram for a cold room with
latent heat cold storage (PCM)
24/08/2018
Exergy efficiency = 2,54%
16
Our proposal for increasing efficiency
24/08/2018
9 h daily operation
15 h of exergy supply
PCM (wáter)
17
Grassmann diagram for a cold room with
sensible heat cold storage (PCM): our
proposal
24/08/2018
Exergy efficiency = 15,77%
18
Conclusions:
18%
15,77%
16%
24/08/2018
14%
Eficiencia exergética
12%
10%
8%
6,56%
6%
4% 3,13%
2,54%
2%
0%
Sin tanques Con tanques latente Con tanques Propuesta 19
sensible
24/08/2018
Thank you¡
20