Análisis de Exergía de La Utilización de PCMs en Refrigeración

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 20

UNIVERSIDAD CATÓLICA BOLIVIANA “SAN PABLO”

UNIDAD ACADEMICA REGIONAL COCHABAMBA


Departamento de Ciencias Exactas e Ingeniería

Exergy Analysis of a Solar Cold


Room for Fruits and Vegetables
Using PCMs
Andrés Gonzales & Marcos Luján

Antofagasta Meeting 1
PCMSOL Project
8-9, November 2018
Introduction

24/08/2018
Universidad de
Almeria

"Multipurpose pilot module for evaluation, optimization and


improvement of agro-food refrigeration systems with
renewable energies" 2
Characteristics of cold rooms at
CIESOL:

24/08/2018
Conservation
temperature= 5°C

3
Operation of the System

24/08/2018
4
Views of the System:
Cold Rooms PV panels

24/08/2018
5
PCM cold storage tank
Exergy use in a cold room
Solar gain
Ti < To

Ventilation loss

Internal gain
Conduction gain
Ti

𝑄ሖ

Work

To; Po
𝑇ℎ − 𝑇𝑐 25𝐾
𝑊𝑟𝑒𝑣. = 𝑄ሶ = 𝑄ሶ = 0.051𝑄ሶ
𝑇𝑐 293𝐾

Low exergy energy flux


Solar exergy supply versus exergy
demand for a cold room

24/08/2018
Exergy Supply/Demand

Exergy saved

Direct cooling

0h 12 h 24 h 7
daytime
Operation mode of the cooling System

24/08/2018
8
Preliminary Results of Energy Consumption

24/08/2018
Exergy
Operation Mode consumption
[kWh]

With latent cold storage 36,9

With sensible cold storage (PCM) 30,2

Without cold storage 16,8 9


Cooling demand of a cold room
Sensible heat of
Heat from lighting products

24/08/2018
Heat from breathing
of products

Heat from humans

10
Heat income from
Convective heat ventilation
infiltration
Cooling and exergy demand without cold
storage

24/08/2018
10% 14%

Cooling demand 155,63 [MJ]

27%

Exergy needed 11,92 [MJ]

49%

Carga de producto [kJ]


Carga por infiltración [kJ]
Carga por renovación [kJ] 11
Carga por ilumación [kJ]
Cooling and exergy demand with latent cold
storage

24/08/2018
5%
19%
16%
Cooling demand 492,35 [MJ]
9%

Exergy needed 12,49 [MJ]


3%

48%

Carga de producto
Carga por infiltración de calor
Carga por renovación de aire
Carga por iluminación 12
Carga del tanque
Cooling and exergy demand with sensible
cold storage

6%

24/08/2018
14%
13%
Cooling demand 459,48[MJ]
7%

4%
Exergy needed 8,29 [MJ]
56%

Carga de producto
Carga por infiltración de calor
Carga por renovación de aire
Carga por iluminación 13
Carga del tanque
Grassman diagram for a cold room without
cold storage

24/08/2018
Exergy efficiency = 6,56%

14
Grassmann diagram for a cold room with
sensible heat cold storage

24/08/2018
Exergy efficiency = 3,13%

15
Grassmann diagram for a cold room with
latent heat cold storage (PCM)

24/08/2018
Exergy efficiency = 2,54%

16
Our proposal for increasing efficiency

24/08/2018
9 h daily operation

15 h of exergy supply

PCM (wáter)

17
Grassmann diagram for a cold room with
sensible heat cold storage (PCM): our
proposal

24/08/2018
Exergy efficiency = 15,77%

18
Conclusions:

18%

15,77%
16%

24/08/2018
14%
Eficiencia exergética

12%

10%

8%
6,56%
6%

4% 3,13%
2,54%
2%

0%
Sin tanques Con tanques latente Con tanques Propuesta 19
sensible
24/08/2018
Thank you¡

20