Professional Documents
Culture Documents
Tydal Power Generation & Electricity Distribution
Tydal Power Generation & Electricity Distribution
Tydal Power Generation & Electricity Distribution
&
ELECTRICITY DISTRIBUTION
1
Structure:
• Tidal Energy
• Electricity Distribution
2
TIDAL ENERGY
3
INTRODUCTION
• Tidal energy is a sustainable and renewable source
of energy from the tides.
4
TIDES
5
• Moon exerts a larger gravitational pull on
water bodies as it is very closer to earth.
6
7
The tides contain energy that can be
harnessed to produce electricity
8
WORLD-WIDE DISTRIBUTION OF
TIDAL ENERGY
10
TIDAL BARRAGES
11
Consists of three main parts:
13
When the tide drops, this collected water is
released and is then used like in a regular
hydropower project.
14
• The tidal difference should be at least 4m
(around 13 ft).
15
TIDAL TURBINES
16
• Tidal turbines are placed under-water and
they rotate using the kinetic energy of tides.
17
18
ASSEMBLY OF TIDAL TURBINES
19
HELICAL TURBINES
20
Efficiency of HELICAL TURBINES
is 68%
21
22
POWER FLOW GRAPH
means of a belt.
Power (watts)
1500
flow doubles. 0
0 1 2 3 4 5 6 7 8 9 10
• Hence, helical turbines are Free Flow (Ft/sec)
23
TUBULAR TURBINES
24
SHROUDED TIDAL TURBINES
14000
13000
12000
11000
10000
9000
8000
7000
6000
5000
4000
3000
2000
1000
0
R D O A
R A
L IL A
S
A
L
LA IN D
R
LE O O G D
SO W
H
Y C C TI
U
N
28
TIDAL ENERGY : AN ECONOMICAL
OPTION
29
• The operating costs of a tidal-energy station
are less than 60% of those of the comparable
diesel option.
30
TIDAL POWER POTENTIAL
31
Tidal power generation of various countries:
1. France :: 260MW
2. Canada :: 34MW
3. China :: 8MW
4. Russia :: 2MW
32
TIDAL POWER PLANTS
WORLD-OVER
1. LA-RANCE TIDAL PLANT (FRANCE)
35
LENGTH of BARRAGE = 750m HEIGHT of BARRAGE =
13m
36
With 24 turbines and total power capacity of
240MW, La-Rance tidal power plant accounts
for 90% of total ocean energy exploited
worldwide.
37
SEVERN TIDAL BARRAGE
• Situated on river Severn in Bristol (UK).
• Produces 8500-14,000GW/hr.
38
39
KISLAYA TIDAL PLANT
40
TIDAL ENERGY : INDIAN SCENARIO
42
OVERVIEW OF DISTRIBUTION OF
ELECTRICITY IN INDIA
44
Electricity distribution is the final stage in the
delivery (before retail) of electricity to end
users.
45
A TYPICAL DISTRIBUTION
SYSTEM CONSISTS OF:
46
• Medium-voltage (less than 50 kV) power
lines
47
SUBSTATIONS
48
• A substation is a high-voltage electric system
facility. It is used to switch generators,
equipment, and circuits or lines in and out of a
system. It also is used to change AC voltages
from one level to another, and/or change
alternating current to direct current or direct
current to alternating current.
49
ASPECTS OF SUBSTATION
• Types
• Functions
• Equipment
50
1. TYPES OF SUBSTATIONS
• Distribution substation
51
DISTRIBUTION SUBSTATION
52
• Distribution substations are located near to
the end-users. Distribution substation
transformers change the transmission or
subtransmission voltage to lower levels for
use by end-users.
• From here the power is distributed to
industrial, commercial, and residential
customers.
53
UNDERGROUND DISTRIBUTION SUBSTATION SYSTEM
54
2. SUBSTATION FUNCTIONS
55
• Change voltage from one level to another
56
• Regulate voltage to compensate for system
voltage changes
57
• Switch transmission and distribution circuits
into and out of the grid system
58
• Measure electric power qualities flowing in
the circuits
59
• Connect communication signals to the circuits
60
• Eliminate lightning and other electrical surges
from the system
61
• Connect electric generation plants to the
system
62
• Make interconnections between the electric
systems of more than one utility
63
• Control reactive kilovolt-amperes supplied to
and the flow of reactive kilovolt-amperes in
the circuits
64
3. SUBSTATION EQUIPMENTS
65
Air circuit breakers
66
• Air circuit breakers are used to interrupt
circuits while current flows through them.
Compressed air is used to quench the arc
when the connection is broken.
67
Lightning arresters
68
• Lightning arresters are protective devices for
limiting surge voltages due to lightning strikes or
equipment faults or other events, to prevent
damage to equipment and disruption of
service. Also called surge arresters.
Lightning arresters are installed on many different
pieces of equipment such as power poles and
towers, power transformers, circuit breakers, bus
structures, and steel superstructures in
substations.
69
Distribution Bus
70
Metal-clad Switchgear
71
• Metal-clad Switchgear can be either for
outdoor use or indoor use. Outdoor -is a
weatherproof housing for circuit breakers,
protective relays, meters, current
transformers, potential transformers, bus
conductors, and other equipment. An indoor
switchgear must be protected from the
environment and contains the same types of
equipment as the outdoor type.
72
Control House
73
• The substation control house contains
switchboard panels, batteries, battery
chargers, supervisory control, power-line
carrier, meters, and relays. The control house
provides all weather protection and security
for the control equipment. It is also called a
doghouse.
74
Oil Circuit Breakers
75
• Oil circuit breakers are used to switch circuits
and equipment in and out of a system in a
substation. They are oil filled to provide
cooling and to prevent arcing when the switch
is activated.
76
Potheads and Riser
77
• Pothead is a type of insulator with a bell or pot-like shape
used to connect underground electrical cables to overhead
lines. It serves to separate the bunched-up conductors from
one another in the cable to the much wider separation in the
overhead line. It also seals the cable end from the weather.
Potheads are mounted on a distribution pole and the
assembly is called a riser pole.
• A riser is a set of devices that connects an overhead line to an
underground line. A riser has a conduit from the ground up
the pole where potheads are used to connect to the overhead
lines.
78
79
Manholes and Conduit
80
• A manhole is the opening in the underground duct system
which houses cables splices and which cablemen enter to pull
in cable and to make splices and tests. Also called a splicing
chamber or cable vault.
• Conduits Conduits are hollow tubes running from manhole to
manhole in an underground transmission or distribution
system. They can contain one or more ducts (See Duct Runs).
They can be made of plastic (PVC), fiberglass, fiber, tile,
concrete, or steel. PVC and fiberglass are most commonly
used.
81
High Voltage Underground
Cables
82
• High-Voltage underground cables are usually shielded
cables. They are made with a conductor, conductor-
strand shielding, insulation, semi-conducting insulation
shielding, metallic insulation shielding, and a sheath.
The sheath can be metallic and may then serve as the
metallic insulation shielding and be covered with a
nonmetallic jacket to protect the sheath. This sheath
helps to reduce or eliminate inductive reactance. Such
cables are commonly used in circuits operating at 2400
volts or higher.
83
Transformer Vault
84
• A transformer vault is a structure or room in
which power transformers, network
protectors, voltage regulators, circuit
breakers, meters, etc. are housed.
85
Underground Transformer
86
• An underground transformer is essentially the
same as an aboveground transformer, but is
constructed for the particular needs of
underground installation. Vault type, pad-
mounted, submersible, and direct-buried
transformers are used in underground
systems. Pad-mounted transformers are
installed on a concrete pad on the surface
near the end-user.
87
Circuit Diagram of the 66kV Substation in
Sector 15, Panchkula
88
89
TERMS RELATED TO
CALCULATION OF LOAD IN OUR
HOMES
90
Connected Load
91
Maximum Demand
92
If all the devices and outlets were used
simultaneously to the full extent, the
maximum demand of the consumer would
equal his connected load
93
Demand Factor
Maximum Demand
Demand factor =
____________________
Connected load
94
LOAD CURVE
95
TWO PART TARIFF
a kW + b kWh
where:
a= cost of power provided (`/kW)
kW= power provided
b= cost of one unit i.e. 1 kWh (`/kWh)
kWh= energy consumed
96
• We use TWO PART TARIFF because
• If tariff is based on the power provided(max
demand), consumers will be tempted to utilise
all the power provided causing overloading.
• If tariff is based on energy consumption, the
board will still have to provide max demand
and will have to plan accordingly. They might
have to suffer loss because of this.
97
• The load on an installation is 800kW, 0.8pf,
3000hr p.a. Tariff is: `100/kVA, 20 paise/kWh
• If pf is improved to 0.9 lagging by means of
capacitor costing 60/Kvar, calculate the
annual saving at 10% p.a. as the interest
charged on capacitor.
98
Thank You
99