Proposal of 1 MWP PV Rooftop Project: Trieu Van Binh - Employee of O&M Department, Gec

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 19

The weekly presentation

Proposal of
1 MWp PV Rooftop Project
Trieu Van Binh - Employee of O&M Department, GEC
Content Preliminary Calculation
1 MWp PV Rooftop Project
Modules Installation

Layout design

Conclusion
How I do

Input Data Simulating scenarios Optimal Proposal Installation design

Gathering necessary Using Pvsyst to Choosing optimal Design modules pillar


data for design simulate different propose by comparing structure, modules
scenarios by changing indicators arrangement.
some parameters.
Premilinary Calculation
Input data


Customer: I have $XXX and I need a
PV system with a DC capacity of 1
MWp

Site PV modules Inverter


information parameters parameters
Site area, Location, Nominal I, V, P; Size, Nominal DC I, V, P,
Topographic, Climate Pac, Nb of MPPT,
Efficiency.
Preliminary Calculation
General information
Address: Group 4, Nam Ben Soi Hamlet, Thanh Long
Commune, Chau Thanh District, Tay Ninh province.

Location: Latitude 11.286


Longtitude 105.997

Capacity: 1 MWp

Area: 100 x 100 m

Topography: The ground mount system elevating 2 meters


in height.
Preliminary Calculation
PV module’s parameters

PV Parameters
Parameter Unit Value
Number of Cells 72
PV size (LxWxH) (mxmxm) 1.956x0.992x0.04
Nominal Power 345
Voc V 46.08
Isc A 9.52
Impp A 9.02
Vmpp V 38.3
Pmpp Wp 345.466
Efficiency % 17.78
Preliminary Calculation
Inverter’s parameters Preliminary Calculation:

+ Number modules / 1string:

VMPP min 200


N min    4.3
VocPV 46.08
VMPPmax 1000
N max    21.7
VocPV 46.08
 5  N  21
+ Number Inverter:

Choose Pnom Ratio = 1.25

Pac Pdc 1000


N inverter    8
Pno inv Pnoinv  Pno m Ratio 100 1.25

Choose Pnom Ratio = 1.1

Pac Pdc 1000


N inverter    9
Pno inv Pnoinv  Pno m Ratio 100 1.1
Preliminary Calculation
Choose Module’s Tilt

Lc (Collection Ls (System
Loss) Loss) Useful Energy
Energy Output (kWh/kWp/day (kWh/kWp/day (kWh/kWp/day Global incident PV loss due to
PR (Annual) ) ) ) in coll. Plane temperature
Scenario 1
Tilt = 10
83.30% 1648 0.86 0.05 4.5 2.50% -11%
Scenario 2
Tilt = 18
83.20% 1650 0.86 0.05 4.51 2.70% -11.10%
Scenario 3
Tilt = 23
82.00% 1616 0.82 0.15 4.41 2.10% -11.10%
Preliminary Calculation
Choose Inverter

Lc (Collection Ls (System Useful Inverter Loss


Energy Loss) Loss) Energy Module array during
Output (kWh/kWp/d (kWh/kWp/d (kWh/kWp/d mismatch operation Inverter Loss
PR (Annual) ay) ay) ay) loss (efficiency) over nominal
Scenario 2
Sungrow
Inverter
83.20% 1650 0.86 0.05 4.51 -1.00% -1.00% -1.00%
Scenario 3
ABB
Inverter
82.40% 1635 0.86 0.09 4.47 -1.00% -1.90% -1.00%
Preliminary Calculation
Choose Inverter
Preliminary Calculation
Choosing Number of Modules in Parallel
Lc (Collection Ls (System Inverter Loss
Energy Loss) Loss) Useful Energy during
Output (kWh/kWp/da (kWh/kWp/da (kWh/kWp/da Module array operation Inverter Loss
PR (Annual) y) y) y) mismatch loss (efficiency) over nominal
Scenario 2,
19
modules/St
ring
82.60% 1640 0.82 0.12 4.48 -1.00% -2.60% 0.00%
Scenario 5,
15
modules/St
ring
83.20% 1650 0.86 0.05 4.51 -1.00% -1.00% -1.00%
Scenario 6,
21
modules/St
ring
84.20% 1664 0.82 0.04 4.56 -1.00% -0.80% 0.00%
Preliminary Calculation
Choosing Pnom Ratio

Lc (Collection Ls (System Inverter Loss


Energy Loss) Loss) Useful Energy during
Output (kWh/kWp/da (kWh/kWp/da (kWh/kWp/da Module array operation Inverter Loss
PR (Annual) y) y) y) mismatch loss (efficiency) over nominal
Scenario 7,
Pnom Ratio
= 1.1
84.20% 1664 0.82 0.04 4.56 -1.00% -0.80% 0.00%
Scenario 6,
Pnom
Ratio= 1.25
84.20% 1664 0.82 0.04 4.56 -1.00% -0.80% 0.00%
Results of Simulation for Optimal Proposal
Results of Simulation for Optimal Proposal
Single Line

DC side

3 strings = 1 Inverter input

AC side
9 IGBT modules convert DC power to AC power
1 transformer to step down the voltage from 400V to 220V

Control System

Power Control includes 9 MPPTs, adjust power to the max point


Gate I/F tracks the DC Voltage to control Inverter.
Module’s Pillar Construction

+ Tilt: 18 degree (According to the


simulation)
+ Height: 2 meters
+ Pitch: 5.2 m ( As long as possible to
avoiding shade)
+ Concrete Pillar: 2 meters in depth
underground
Layout Design

Modules Arrangement
21 modules in parallel = 1 string
4 columns, 18 rows
Pitch = 5.2 m

Inverter Arrangement

8 Inverters are in the centre


+ Avoiding shading
+ Convenient commuting, inspecting and checking
Conclusion
Gained knowledge

Premilinary design a PV rooftop Choose main facilities for PV Design installation for PV system’s
project with available parameters system using PVsyst components using AutoCAD
THANK YOU
FOR YOUR ATTENTION

For further information, please contact:


Trieu Van Binh
Department of O&M, GEC
Email: binhtv@geccom.vn
Mobile: +84 34 262 2172

You might also like