Professional Documents
Culture Documents
Furnace Safeguard Supervisory System
Furnace Safeguard Supervisory System
Mr.Anjan Dastidar
Mr.Amit Pandey
FSSS ?
F : Furnace
S : Safeguard
S : Supervision
S : System
FSSS : Furnace Safeguard Supervision
System
Why FSSS ?
FSSS can prevent the mix of explosive fuel and air from accumulating
anywhere inside a boiler, thus avoiding accidents such as boiler explosion
and ensuring the operational safety of boiler.
FSSS system will offer furnace purging judgment logic and ignition mode in
conformity to the safety regulations to operators for the start and
operation of boiler.
The operators may be informed on the work conditions for the operational
safety of boiler directly in engineer station. FSSS system will warn the
operators in case of abnormity to such information. It may also send MFT
tripping instruction, if necessary conditions are true, to cut off fuel, serving
as a reliable technological guarantee to boiler operational safety.
List of Boiler Main Equipment
Two forced draft fans (FDF)
Three primary air fans (PAF)
Three induced draft fans (IDF)
Two sealing air fans
Two air preheaters
Two electrostatic precipitators
Five Coal Mills
Two Scanner Air Fan
Burner System
System Functions
FD FAN Supplies heated air (Secondary Air) to the Boiler Furnace
in the amount and at the temperature required for optimum
combustion of coal.
PA FAN Supplies heated air (Primary Air) to the Pulverizing Mill for
drying coal during the pulverizing process and conveying pulverized
coal into separators.
Seal Air Fan Provides seal air for the coal feeders, the pulverizers
and the dampers
ID fan removes the furnace combustion gases, through flue gas
duct, electrostatic precipitator,chimney to the atmosphere.
Electrostatic Precipitators collects & removes the Ash (Dust)
mixed inside the flue gas.
Coal Mill are system where coal is grinded & dried. Coal with
required fineness is produced.
Scanner Air Fan are used for providing cooling air to Oil & Coal
Flame scanners.
Burner System
There are totally 20 sets of oil gun equipped in each boiler.
The oil gun has to be put into operation to support the ignition and
stable combustion during the startup and shutdown of the pulverizer, as
well as during lower load condition
The function of burner is to setup a stable ignition at the appropriate
range beyond the burner nozzle, and achieve the complete combustion.
Each Burner has two SA zones from where Secondary air from FD fan
is introduced inside the zone.SA zone is equipped with adjustable
vanes located in each zone which can enhance the ignition.
Each burner will be equipped with a set of High-Energy Spark Ignition
system(2.5kv) to ignite the fuel automatically. This igniter consists of HE
transformer, ignition rod, ignition cable, spark, oil gun and retractable
cylinder.
Burner also has Oil valve & purge valve. Oil valves are used to provide
ignition oil i.e LDO & Purge valve are used for purging of the oil lines
with help of compressed air.
FSSS - Furnace Safeguard
Supervision System
Boiler MFT (Master Fuel Trip)
Boiler OFT (Oil Fuel trip)
Furnace Purge Conditions
Boiler RB(Runback)
Oil Level Permission
Coal Level Permission
Oil Gun Control
Purge Conditions
Purge time : 300 seconds
All PA fan stopped
No MFT
No Leak test
After the leak test turns ON, the oil supply and return valve shall open .
Then closed oil return valve and check leak test oil- pressure (2.8 Mpa)
satisfies appropriately. If the pressure does not develop upto 2.8 Mpa
then send the oil leak test fail signal. The leak test is fail and the
program is stop.
Close the supply valve and wait for 180 seconds If the oil pressure
satisfies acceptable limit of 2.55 Mpa then move to next step and if it
does not remain within acceptable limit of 2.55Mpa for 3 minutes .
Then it is considered as leak test fail.
If the leak test oil pressure acceptable signal is maintained for 3
minutes, open the return valve and the control valve. After 30
seconds, judge the differential pressure (0.5 Mpa) oil supply force
and after is recovery. If the different pressure is recovered, the leak
test is fail. If the different pressure is not recovered, next step.
Close return oil valve and control valve. After 3 minutes, judge the
different pressure (1.5 Mpa) oil supply force and after if recovery. If
the different pressure is recovered, the leak test is fail. If the
different pressure is not recovered the leak test completes.
Causes of Master Fuel Trip (MFT)
Both FD Fans trips:-
After two FD.F stop, sends this signal. On arriving of stop feedback of both
FD fan with time delay of 1 sec generates MFT.
After 3 ID.F stop completely, sends this signal. On arriving of stop feedback of
all three ID fan with time delay of 1 sec generates MFT.
System sends this signal after judgment boiler in non-oil layer input when
any mill
When two out of three furnace pressure switch is sensed more than set value it
acts and in logic at DCS with a time delay of 2 sec generates MFT.
Furnace pressure very low(-2500 pa) 2out of 3 logic.
When two out of three furnace pressure switch is acted with a time delay of 2
sec this signal is send for MFT.
Drum level very high (250mmwc) 2out of 3 logic(delay 5
sec)
Drum water level is measured from level transmitters and if two out of three
level transmitter value crosses the high level then in logic at DCS after 5
second time delay it generates MFT
Drum level very low (-250mmwc) 2out of 3 logic(delay 5 sec)
Drum water level is measured from level transmitter and if two out of three
level transmitter value crosses the low level then in logic at DCS after 5 second
time delay it generates MFT
Total air flow less than 30% (300 TPH)
Total air flow i.e sum of total primary air flow and secondary air flow is less than
30 % (300 TPH) of total air flow with time delay of 10 sec signal is send to MFT.
Manual MFT
When operator presses two push buttons at a time given on desk, The system
receives the MFT button trip signal through hard wiring
Flame Loss :
Arming of Logic: If any mill & Feeder is running for 60 sec logic gets armed.
a. 2/4 coal Flame scanner proven & All Four oil flame scanners of any
elevation not proven generates MFT.
If nine or more coal flame scanners sensing NO FLAME within time span of 5
seconds this actuates to MFT.
Fuel loss :
Arming of Logic: After all 4 oil Gun in any is elevation proven.
Main oil supply valve (Trip valve) close or All oil corner valve closed and all Mill
and Feeder stopped .Generates signal to MFT.
FURNACE
FLAME LOSS
FUEL LOSS LOGIC
Scanner cooling air lost :
Scanner cooling air pressure very low (<3.2 Kpa) two out of three pressure
switches senses cooling air pressure less than set value it acts or both SA
fans are stopped than with time delay of 10 sec sends signal to MFT.
Reheater protection:
Arming :Boiler load > 30 % means MS flow more than 300 TPH OR any Mill &
Federer proven
a. Turbine trips and if HP Bypass valve is not open more than 30 % within
10 sec generates command signal to MFT.
b. When GCB is in OPEN condition and HP Bypass valve has once crossed 30
% open feedback and thereafter closes and attains a feedback of less than
5% open actuates MFT
REHEATER
PROTECTION
All APH lost:
If Both APH Main and spare motor are stopped for more than 60 seconds the
signal is send to MFT.
When fuel oil pressure low low switch two out of three is acted the signal is send
for OFT.
In Normal unit running condition if supply oil valve is closed OFT signal
generated.But the same phenomenon will not generate MFT.
All corner valve closed:
In Normal unit running condition if all elevation corner oil valve is closed OFT
signal generated.That means during operation of oil gun when the last oil valve
is closed OFT is generated.
In Normal unit running condition if return oil valve is closed OFT signal
generated.
If Main & Auxiliary power supply both are failed OFT signal generated.
OFT LOGIC
Run back to trip Mill
According to CCS the RB action situation is following.
No OFT
Purge End
Coal Fire Permission
Secondary air temperature suitable(>177 .C)
No MFT
PA fan Running
No fast/urgent trip
Lube oil system normal (Pump Running & pressure 0.13 Mpa)
1) Step-1:- Mill inlet Hot Air & Cold Air valves & dampers close command is
executed and Mill outlet damper and all seal air valve open command is
executed. On receiving the desired feedback of each valves Step-2 is
executed .
2) Step-2:- Start command for lubrication oil pump and hydraulic loading oil is
generated & the fire fighting steam valve is opened for 300 seconds.
3) Step-3:- Mill fire fighting valve close and Coal feeder inlet valve open
command is executed . On receiving the feedback next step is executed
4) Step-4:- Cold air MOV & hot air gate pneumatic cylinder open command is
executed and both valve gets open.
5. Step-5:- Check all below mentioned condition
Adjust primary air flow more than 45 TPH & outlet temperature within 60-90 ‘C by operating cold
air damper & hot air damper.
Mill Lube oil condition should be satisfied i.e pressure should be more than 0.1 Mpa.
Mill hydraulic system should be in variable load condition i.e hydraulic pressure varies with respect
to coal feeding.
6. Step-6:- Lift roller command is executed and on receiving the lift roller
feedback after 20 seconds next step is executed.
8. Step-8:- Opens the coal feeder outlet gate and set the coal feeder speed
min value.(12 TPH) Start the coal feeder by giving start command from DCS
after verifying all coal feeder permissive are meet and no trip condition
exists.Fall the roller after the coal feeder running.
Coal Mill stop sequence
On pressing the sequence stop button in operator screen
following steps will be executed in sequence auto mode.
1) Step-1:- Set the coal feeder min 12 TPH and close coal feeder inlet gate
commands are generated. On receiving the feedback next step
2) Step-2:- Coal feeder stop & Feeder outlet damper close command are
executed. After 60 seconds time delay next step is executed
3) Step-3:- Coal Mill Roller Lift command is generated.After Roller gets lifted
next step is executed
4) Step-4:- Coal Mill Stop command is generated. After time delay of 80
seconds next step is executed.
5) Step-5:- Roller fall command is generated and roller gets fall.
6) Step-6:- Close mill cold air gate & damper.
7) Step-7 :-Opens the fire fighting MOV.
8) Step-8:-Closes the fire fighting MOV after 8 minutes.
9) Step-9:-Close the mill outlet gate. When the mill normally stop, may only
close n-1 outlet gate; When the mill trip, must close completely all outlet
gate.
10) Step-10:-Stop Mill hydraulic oil pump, and close mill seal air valve and
outlet seal valve.
Mill Fast Trip Conditions
Mill PA flow<38TPH:
If coal Mill in running condition & Inlet PA flow transmitter value falls
below 35 TPH then with time delay of 5 sec Mill urgent stop signal is
generated.
Coal Mill in running condition and seal air to primary air differential
pressure falls below 0.1 Kpa then with time delay of 5 sec Mill urgent
stop signal is generated.
MFT:
Master fuel trip condition generated will cause all running coal mill to
urgent trip without any time delay.
Coal Mill running condition and if any two mill outlet damper are
closed then Mill urgent stop signal is generated
Coal level no flame (2out of 4):
Coal Mill in running condition and if two out of four coal flame
scanner does not sense flame then with time delay of 5 sec Mill
urgent stop signal is generated
If coal feeder belt is swayed on either side of feeder will act belt
tracking switch then with time delay of two seconds coal feeder
urgent trip is generated.
Coal feeder temperature value increased more than 80’C then coal
feeder urgent trip is generated.
Coal feeder running and outlet damper is closed then with time delay
of 2 seconds coal feeder urgent trip is generated.
Coal feeder belt motor fail to start then coal feeder urgent trip is
generated