Sales Presentation
May , 2013
V1.0
By: Jose Mendez & JC Theron – Product Managers
Content
• C90Plus: Bay Monitoring/control, SSOD, F/V, dF/dt and Fast Load Shed. . . easy to
design, expand
• Powerful automation flexlogic & math engine . . .Improved substation automation capability in
terms of performance, cost & redundancy
• Color HMI & annunciator . . . very intuitive and easy-to-use visual tool to monitor & control the
bay/bus
. . . Soft labels, descriptive messages - eliminate LEDs and annunciator in
panels – 288 Alarms
• Powerful DFR capability . . . Eliminate the need for standalone DFRs and meet NERC requirement
• Enhanced metering functionality . . . Enhanced data logger and Synchrophasors as per IEEE
C37.118
What is it?
UR FW version 7.10 release introduces specific new Value Proposition of UR FW version 7.10
communication and P&C capabilities to The UR Family
of devices. • Increases network availability by enabling
independent failure mode and reducing failover
New Communication functionality time to zero through implementation of IEC62439-3
- New network redundancy method as per the IEC “PRP”
62439-3 PRP standard.
- Updated KEMA certification on the IEC61850 protocol • In-zone transformer capability in the L90 enables
decreasing the number of required CT banks by 1/3
New P&C Functionalities and dedicated transformer relay for line differential
- In-zone transformer capabilities added to the L90 Line schemes with a power transformer in between
Protection System
- CyberSentryTM UR Lvl 1 new settings for password • New settings fields for bypassing user
bypass authentication may speed up relays commissioning
and testing by 10% while keeping NERC/CIP
compliance
MDS WiYZTM
Product Summary URPlus
What is it?
URPlus FW version 1.90 release introduces specific new Value Proposition of URPlus FW version
communication and enhanced P&C capabilities to The
URPlus platform, excluding the B95Plus.
1.90
• Increases network availability by enabling
New Communication functionality independent failure mode and reducing failover time
- New network redundancy method as per the IEC
to zero through implementation of IEC62439-3 “PRP”
62439-3 PRP standard.
- Updated KEMA certification on the IEC61850 protocol • The SSOD (Small Signal Oscillation Detection)
range is expanded and refined to ensure a larger
Enhanced P&C Functionalities (C90Plus)
area of system oscillations can be detected
- Small Signal Oscillation Detection range is expanded
to cover a wider range of 0.08 to 1Hz with step
increments of 0.02Hz.
Application Examples
Applications 1 – PRP (UR & URPlus)
MDS WiYZTM
• Bumpless recovery of
communications
• UR / URPlus
• 2 networks
• 2 ports
• 1 MAC address/IP
address
• UR receives frames from
both networks
• Discards 2nd frame
• Transparent to switches
LAN A – LAN B –
Ring mode Tree mode
UR v6.xx or older
SAN: Single SAN
access node UR v7.10 or
higher
DANP: Double DANP
access node PRP
Eth Port 1
Eth Port 2
Eth Port 3
Applications 2 – L90 With In-zone Transformer
MDS WiYZTM
(UR)
In-zone Power Transformer Functionality
• Compensates remote terminal side phase shift
• Suitable for two and three line terminals
• Several Inrush Inhibit modes
Reduces the number of required CT banks by 1/3 and dedicated transformer relay for
line differential schemes with a power transformer in between
Applications 3 – CyberSentryTM (UR)
MDS WiYZTM
Standard
CyberSentryTM UR Level 1
• Exceeds NERC CIP Password requirements (6
• Exceeds NERC CIP Password requirements (6
digits, alpha-numeric and special characters;
digits, alpha-numeric and special characters;
UR – 20 Digits, Alpha-numeric, special, capital
UR – 20 Digits, Alpha-numeric, special, capital
and small case characters)
and small case characters)
• Access Level for Settings
• RBAC with Five Roles
• Access Level for Commands
•Administrator
•Supervisor
• Dual Access control
•Engineer
• Remote Password, Local Password
•Operator
•Observer
• Security Audit Trial (6.0x)
• Enterprise authentication - Radius
Local Password
User Activities FP User Activities Comms
Bypass See and write independent Read and write settings files
settings Read record files
See independent records Write independent settings
Front Panel, RS232 No access to CyberSentry FW upgrade
& RS485 settings CybersSentry settings
Master/client Comm
Detection (URPlus)
SSOD Settings Range Expanded in C90Plus
• Measure up to 6 analog inputs either local or remote signals at a fixed
measurement rate of 100 ms, and monitor for small power system oscillations
(Power or Frequency) Alarm and Trip stage
• Settings range expanded: 0.08 to 1 Hz with 0.02 Hz frequency step
Increases large power system stability by monitoring 6 inputs and allow system
separations upon detected instability
Multilin UR &10 Key Feature Descriptions
C0 PRP $ 500.00
C90P- * * - * * ** * * * - * * * * * * * * ** *
Interface | | | | | | | | | | | | | | | | | | Description
| | | | | | | | | | | | | | | | | |
Front Panel A | | | | | | | | | | | | | | | | | Annunciator (standard)
H | | | | | | | | | | | | | | | | | + HMI
| | | | | | | | | | | | | | | | |
Language E | | | | | | | | | | | | | | | | English (Standard)
| | | | | | | | | | | | | | | |
Features | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | |
Protection X | | | | | | | | | | | | | | | None (standard)
(AC module must for this option) P | | | | | | | | | | | | | | | Basic Protection + Protection Flexlogic
O | | | | | | | | | | | | | | | + Small Signal Oscillation
| | | | | | | | | | | | | | |
Automation S | | | | | | | | | | | | | | Breaker Control + Synccheck
(protection or/ and automation) E | | | | | | | | | | | | | | Breaker Control + Synccheck + Automation Controller (standard)
L | | | | | | | | | | | | | | + Basic Load Shedding elements
C | | | | | | | | | | | | | | Fast Load Shedding Element (Controller) - Does not support AC, I/ O card optional, needs IEC61850
A | | | | | | | | | | | | | | Fast Load Shedding Element (Aggregator) - Does not require AC or I/ O card, needs IEC61850