The height of service line conductors erected along a street must not be less than:-
• For low and medium voltage line=5.490 m
• For high voltage line=5.795 m
For extra high voltage line, the clearance ground shall not be less than 5.185 m plus
0.305 m for every 33 KV or part thereof by which the line voltage exceeds 33 KV.
2. Rule no 79
Where a low or medium voltage overhead line passes
above or adjacent to the building; the following minimum
clearances must be as follow:-
When the line passes above the building, a vertical
distance of 2.44 m from the highest point of the building
When the line passes adjacent to the building, a horizontal
clearance of 1.22 m from the nearest point.
Estimate For Service Connection For
Overhead Line
Q. A newly constructed single storeyed house
is to be provided with single phase 230 volts, 50
Hz having a load of 5 KW. The supply is to be
given from overhead line 20 m away from the
building. Prepare a list of material for giving the
service connection and also estimate the cost
of the service connection.
Ans;- Assume:-
1. Height of the ground floor=3.5 m
2. Service connection received at A height of 6 M from the floor.
Diagram for overhead service connection and for the overhead estimate also
Selection of rating of weatherproof, twin core,
aluminum conductor cable and line conductor:-
1 8 SWG G.I wire to serve as a bare conductor from supply pole upto 63 m 50/- m 3150/-
house service connection including wastage
2 Weatherproof cable of size 1/3.35 or 10mm2 twin core PVC insulated 7 m 60/-m 420/-
rated to carry a load of 34 A
3 G.I pipe of 50 mm dia 7.5 m 50/-m 375/-
4 Earth wire 8 SWG G.I running along G.I pipe upto meter board 6m 80/-m 480/-
9 Iron clad meter board along with 4 No bolts and nut of size 1 No 1000/- 1000/-
25cm*30cm
10 Conduit bushings 50 mm dia for G.I pipe 2 No 150/- 300/-
11 Stay wire 7/10 SWG G.I 7m 50/-m 350/-
12 Stay bow 1 no 500/- 500/-
Specifications Qty. Rate Amount
13 Star rod with bolts and stay buckle and stay plate of size 1 set 300/- 300/-
30cm*30cm
17 Aluminum clips 75 mm long to hold earth wire pipe 1 box 300/- 300/-
Ans:- Assume :
a) Height of main board from floor : 1.5 m
b) Service connection received above the ground: 5 m
Diagram for underground service connection and for the underground estimate also
Selection and rating of weatherproof cable from pole to meter board :
total load connected to the building is 200 A
Diversity factor = 60%
Max load being used = 132 A
3 Pole clamp of mild steel with nuts and bolts to hold earth wire 1 no 200/- 200/-
with pole
4 G.I pipe 35mm dia to carry cable for main board along wall 6m 50/-m 300/-
upto floor
5 G.I pipe 50 mm dia from outer wall upto underground 4m 100/-m 400/-
concrete cable enclosure running below floor
6 G.I pipe 35mm dia from concrete cable enclosure upto space 2m 50/-m 100/-
for main board through wall vertically
7 Conduit saddles of Galvanized steel to hold G.I pipe with wall 10 No 20/- 200/-
8 Hooked ray bolt 200mm long and 15 mm diameter to hold 4 no 25/- 100/-
earth wire with wall
9 Iron clad board for installation of main board of size 1 no 1500/- 1500/-
100cm*75cm
Sr no Specifications Qty Rate Amount
11 Rag bolts with nuts 10 mm dia and 100 mm long to fix 20 No 25/- 500/-
conduit saddles with wall
12 Link clips of aluminum 75mm long to hold cable with 3m 100/- 300/-
support wire OR binding wire of 12 SWG
13 Earthing thimbles 45 A rating with nuts and bolts to 2 no. 250 500/-
connect earth wire with energymeter main switch
Total 12000/-
Labor charge 1500/-
Contingency 1500/-
Grand total 15000/-