+NBC and Fire Code Standards
+NBC and Fire Code Standards
RA 9514
DESIGN STANDARDS
LIGHT AND VENTILATION PD1096 RA9514
MIN.
DIMENSION OF 2.00 MTS. N/A
COURT
PASSAGEWAY
FROM INNER N/A
AT LEAST 1.20 MTS.
COURT
MIN. HT.
CLEARANCE 1.00 M. ABOVE THE N/A
FROM ROOF
FIREWALL
HEADROOM 2.00 M. 2.00 M.
CLEARANCE
MIN. CEILING
HT. FOR 2.40 M. – ART. VENT
HABITABLE 2.70 M. – NAT. VENT 2.30M.
ROOMS
LIGHT AND VENTILATION PD1096 RA9514
MIN. CEILING 2.70 M – 1ST STOREY; 2.30 M.
HT. FOR 2.40 M. – 2ND STOREY;
BUILDINGS 2.10 – SUCCEEDING 2.13 M. FOR
STOREYS MEZ. FLR.
1.80 – MEZ. FLR.
SUM OF AREAS LESS THAN 50% OF
OF OPENINGS TOTAL AREA OF THE N/A
IN ANY AREAS
WALL ON THAT STOREY
WINDOW
OPENINGS AT LEAST 10% OF N/A
EAVES OVER
REQUIRED AT LEAST 750 MM N/A
WINDOWS
SIZE/DIMENSION OF RMS PD1096 RA9514
ROOMS FOR 6.00 SQ.M. WITH N/A
HUMAN
HABITATION
MINIMUM
DIMENSION OF 2.00
M.
KITCHENS 3.00 SQ.M. WITH
MIN. DIMENSION OF N/A
1.50 M.
TOILET AND
BATH 1.20 SQ.M. WITH N/A
MIN. DIMENSION OF
0.90 M.
PD1096 RA9514
OCCUPANT AT LEAST 1 AT LEAST 2
LOAD OF LESS
THAN 10
EXIT EXITS
OCCUPANT
LOAD OF 10- AT LEAST 2 EXITS N/A
EXITS
499
OCCUPANT
LOAD OF 500- AT LEAST 3 EXITS N/A
999
OCCUPANT
LOAD OF 1000 AT LEAST 4 EXITS N/A
AND ABOVE
DISTANCE TO
EXITS WITHOUT MAX. OF 45 M. MAX. OF 46 M.
SPRINKLE
SYSTEM
PD1096 RA9514
DISTANCE TO
EXITS WITH MAX. OF MAX. OF
SPRINKLE 60 M. 61 M.
SYSTEM
MIN. EXIT
DOOR WIDTH 700 MM 710 MM
EXITS
MIN. OF EXIT
DOOR HEIGHT 2.00 M. 2.00 M.
MIN. OF
CORRIDOR 1.10 M. 550 MM
WIDTH
MIN. STAIR
WIDTH:
OCCUPANT
900 MM NA
LOAD OF 10-50
MIN. STAIR
WIDTH:
OCCUPANT
1.10 M NA
LOAD OF 50 -
ABOVE
DISTANCE
BET. 2.75 M CLASS A
3.60 M
LANDINGS 3.70 M CLASS B
DIMENSION
OF LANDINGS EQUAL TO THE 1.12 M
IN THE WIDTH OF THE
DIRECTION
OF TRAVEL
STAIRWAY
1/6 OF
NA
ARCADES
WIDTH OF
SIDEWALK R.R.O.W
800 MM FOR
SIDEWALKS
PLANT
EXCEEDING 2.00 M IN
NA
STRIP
WIDTH
DRIVEWAYS, ENTRANCE
SLOPE OF NA
ENTRYWAY
1:3 OR 1:4
& EXITS