Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 105

MM300

Motor Management System

Low Voltage
Motor Protection & Control

ggMultilin
Multilin
MM300 Motor Management System
Agenda
• Introduction
• MM300 Key Benefits
• Hardware Overview
• Electrical Overview
• Protection Overview
• Monitoring & Metering
• Communications
• Graphic Display Panel
• EnerVista™ MM300 Setup Software
• Order Codes

2/
GE /
October 21, 2019
MM300 Advanced Automation
• Eliminate Stand-alone dedicated PLC,

Advanced Motor Management Package controllers


• Pre-canned starter logic: FVNR, FVR, Two
speed, wye-delta, inverter/soft-start
• Process interlocks for starter supervision
Comprehensive Motor Protection • FlexLogic™ for sequencing applications,
• Thermal Overload, Mechanical Jam Custom starter/interlock logic
• Unbalance • Multiple I/O options
• Thermistor
• Ground Fault (CBCT)
• UV, Underpower RTD (Optional)

Powerful Comms for Easy


Integration
• Modbus RTU (RS485) standard
• Ethernet with Modbus TCP
+ Fieldbus Optinal
 Profibus DP
 DeviceNet

Powerful Metering Motor Diagnostic Information


• RMS currents, %UB, Thermistor • Sequence of Events Data
• AUX voltage, frequency, power • Motor Learned Data
• 3 Phase voltage, metering • Small Footprint • Waveform Capture
(Optional) • Conformal Coating Standard • RMS Data Logger
• Eliminate stand-alone metering • -20°C to +70°C Continuous
Operation

3/
GE /
October 21, 2019
MM300 Motor Management System
The MM300 is a modular based Motor Protection and Control system
designed specifically for Low Voltage Motor Applications

Key Applications
• Designed to meet the requirements
of IEC and NEMA Class MCC Buckets
• Panel Mount option for Stand alone
motor applications
• Powerful and Flexible protection to
meet the specific requirements of
Low Voltage AC Motor Applications
• Conveyor Belts
• Fans
• Pumps
• etc.

4/
GE /
October 21, 2019
MM300 Key Benefits

g imagination at work
5/
GE /
October 21, 2019
MM300 . . . Key Benefits
Functionality

Reliable protection for secondary & backup purposes


6/
GE /
October 21, 2019
Major Features
Certifications & Form Factor
• Fully Certified and Tested
• CSA, UL, CE, IEC, ISO
• IEC 60068-2-38 Temperature / Humidity Cycle
• IEC Vibration Tested: 57 – 150 Hz for DIN Rail
installations, Sinusoidal (high-vibration
installation mode)
Small Form Factor
• Compact and Modular Design
• Designed for IEC or NEMA MCCs
• Remote Mounted Control Panel (Door + DIN
Rail Mounting) 8/
GE /
October 21, 2019
Flexibility for Standardization

Flexibility & Customization


• Direct connect up to 690V (No requirement for
additional CT’s & VT’s)
• 1A & 5A Internal CT’s
• Programmable and Expandable I/O eliminates PLCs or
other discrete relay devices
• Mounting Options (Door + DIN Rail, Panel Mount, Screw
Mount)
• Scalable Protection & Control Logic Functionality
• Removable terminal blocks

9/
GE /
October 21, 2019
MM300 . . . Key Benefits
Size
Compact

Base Unit
• 120 mm (W) x 90 mm (H) x 123 mm (D)
• 4.74” (W) x 3.54” (H) x 4.84” (D)
Color HMI Display
• 154 mm (W) x 103 mm (H) x 15 mm (D)
• 6.06” (W) x 4.05” (H) x 0.60” (D)
Control Panel
• 75 mm (W) x 75 mm (H) x 31 mm (D)
• 2.95” (W) x 2.95” (H) x 1.22” (D)

10 /
GE /
October 21, 2019
Hardware Overview

g imagination at work
11 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
The MM300 Motor Protection system consists of 4 main components

Base Unit Color HMI Display

Control Panel
Expansion Module
12 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
User Interface
Graphical Display Front Panel Controls
• Multi-language Support • Integrated Device Control
Ease of Use • Large Metering Values • Simple to Use
• Graphical Interface • Wide viewing angle • Dedicated control keys
LED Indication
• Motor status
• Alarm Indication
Mounting Options • System Status
• DIN Rail • Communication Status
• Through Door • Additional user LEDs
• IP54 Rated Display

Security
• Role Based Access

Integrated Functionality
• Protection, Metering, Control
Entry Level Control Panel
• Event Recorder Front Port Access
Soft key Navigation • Control keys
• Data Logger • USB for Laptop Connection
• Graphical Module Control • LED Indication
• Waveform capture

13 /
GE /
October 21, 2019
MM300 . . . Electrical Overview
Terminal Connections
Expansion module
RS485 Communications
attaches to base unit
and Thermistor Input with a single connector

Optional Profibus 3 Phase and 1 Optional 3


DP or DeviceNet Residual GND phase Voltage
Fieldbus protocols CT Inputs Module

Optional Expansion Module


Allows additional Digital I/O,
RTD, or Voltage inputs

I/O card includes:


Optional RTD
• 2 Contactor Outputs (Form A)
Module with
Switched Power Supply Optional TCP / IP • 6 Programmable inputs
three RTD inputs
allows AC or DC control Ethernet • Single Phase VT input (60-300Vac)
voltage

Core Balance
Ground CT Input 14 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
Dimensions – Base Unit

•Small foot print


•Modular Design
•2 expansion modules can be added.
•Expansion modules are 56mm (2.2”)

15 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
Mounting options

• Provides a flexible footprint for smaller buckets


• Display can be mounted up to 6 feet away

16 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
Mounting options

17 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
Mounting options – Din rail

•Easy insertion and removal of unit


•MM300 slides straight in and the din
clips are closed

18 /
GE /
October 21, 2019
MM300 . . . Hardware Overview
Modules – Removal and Inserting

•A slot track is provided


•Align the new card with the
track and slowly slide the card in
place.
•Use the captive screws to anchor
the card in place.

19 /
GE /
October 21, 2019
MM300 . . . Module Arrangement

20 /
GE /
October 21, 2019
Electrical Overview

g imagination at work
21 /
GE /
October 21, 2019
Built-In Starter Logic

• Full-voltage non-reversing (FVNR)


• Full-voltage reversing (FVR)
• Two-speed (TS)
• Wye-delta open transition (WDOT)
• Inverter (I)
• Soft start (SS)

By selecting a pre-defined starter, inputs and


outputs are automatically assigned
22 /
GE /
October 21, 2019
Full Voltage Non-Reversing (FVNR)

23 /
GE /
October 21, 2019
FVNR Starter Timing

24 /
GE /
October 21, 2019
Full Voltage Reversing (FVR)

25 /
GE /
October 21, 2019
Full Voltage Reversing (FVR) Starter
Timing

26 /
GE /
October 21, 2019
Two Speed Starter

27 /
GE /
October 21, 2019
Two Speed Starter Timing

28 /
GE /
October 21, 2019
Wye-Delta open Transition

29 /
GE /
October 21, 2019
Wye-Delta open Transition Starter
Timing

30 /
GE /
October 21, 2019
Inverter

31 /
GE /
October 21, 2019
Soft Start (RVSS)

32 /
GE /
October 21, 2019
Soft Start and Inverter Timing

33 /
GE /
October 21, 2019
Process Interlocking

• Before Motor Start


– Ensure all support, safety and process
permissives are ready
– At start, ride-through for normal process
conditions may be applied
• Post Motor Start
– Ensure that process flow, pressure, temperature
or other limits are not in violation
– Provide ride-through for intermittent violations

34 /
GE /
October 21, 2019
Process Interlocking Examples
ON START
Centrifugal blower/fan no airflow alarm delayed on
start up until static and friction head pressure is
established against ductwork by using “start override”
delay
DURING RUN
Cryogenic fluid flashes at intervals in a positive
displacement pump causing cavitation and
momentary drop in differential pressure across pump.
Differential pressure alarm delayed using”running
override.”

35 /
GE /
October 21, 2019
Process Interlocking

36 /
GE /
October 21, 2019
Process Interlocking

37 /
GE /
October 21, 2019
Autorestart on Voltage Interruption

38 /
GE /
October 21, 2019
Protection Overview

g imagination at work
39 /
GE /
October 21, 2019
Protection Features

Goals: Detect ground fault, abnormal electrical conditions,


abnormal process conditions and thermal issues

40 /
GE /
October 21, 2019
MM300 – Single Line

41 /
GE /
October 21, 2019
MM300 . . . Protection Features
Thermal Model
Thermal Overload protection for both the
Stator and Rotor
RTD and Unbalanced Biasing of the Thermal
Model provides enhanced protection

Nameplate data used to


program thermal model
• Full Load Amps
• Safe Stall Ratio

Standard Overload Curves


• 15 Standard Multilin Curves with
multipliers available
• Based on motor thermal damage
curves provided by the manufacturer
• Automatically adjusted for Hot and
Cold motor conditions

42 /
GE /
October 21, 2019
Protection: Thermal Unbalance
Current Derating

Use #8 for NEMA

43 /
GE /
October 21, 2019
Protection: Thermal RTD Biasing

• Provides temperature-based protection against thermal damage


• Minimum is Ambient
• Midpoint is Rated Rise over Ambient, plus Calculation of Hot/Cold Stall
Ratio
• Maximum is Insulation Class Maximum
Protection: Thermal Cooling Time
Constant

• Uses Running and Stopped Cooling Time Constants


• Time Constant defined as time it takes to get 63%
to Ambient after 100% temperature is obtained
45 /
GE /
October 21, 2019
MM300 . . . Protection Features
Motor Starting
Start Inhibit
• Ensures motor has cooled sufficiently
to allow a successful motor start
command
• Compares learned starting
temperature and actual motor
temperature

Additional Motor Starting Protection


• Acceleration Trip
• Starts per Hour
• Time Between Starts
• Start Inhibits
• Backspin Timer
• Restart Blocks

46 /
GE /
October 21, 2019
MM300 . . . Protection Features
Current
• Residual Ground Fault
• Sensitive Ground Fault
• Unbalance
• Single phase
• Mechanical jam/rapid trip

Voltage & Power


• Under / Over Voltage
• Phase reversal
• 3 Phase Underpower

47 /
GE /
October 21, 2019
MM300 . . . Protection Features
Advanced Process Control
Reduced Voltage Starting
• Controls transition of reduced voltage starters
• Based on current level and timers

Under Voltage Auto-Restart


• Automatically issues a start command for system
or process related faults
• Based on timers and optional system voltage

Remote Start / Stop Commands


• Serial or hardwired Start and Stop commands
operate Contactor Outputs for remote operation
of the motor

48 /
GE /
October 21, 2019
Monitoring & Metering

g imagination at work
49 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Current and voltage

• Phase Current (RMS / Phasor)


• Residual Ground Fault Current
• Sensitive Ground Fault
Current
• Unbalance current
• 3 Phase Voltage (RMS / Phasor)
• Frequency
• Motor Load

50 /
GE /
October 21, 2019
Metering – Graphic Display Panel

These are shots of the graphic panel.


All info available through PC/SCADA connection
51 /
GE /
October 21, 2019
Diagnostics – Graphic Display Panel

These are shots of the graphic panel.


All info available through PC/SCADA connection
52 /
GE /
October 21, 2019
Relay Status Indication – Graphic
Display Panel

These are shots of the graphic panel.


All info available through PC.
53 /
GE /
October 21, 2019
Trending and Oscillography

54 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Power
• Measured Power Quantities
• Power Factor
• Real Power (kW)
• Reactive Power
• Apparent Power (kVA)
• Watthours (MWh)
• Varhours (Mvarh)

55 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Inputs & Outputs
Multiple combinations of Contact outputs
and Digital Inputs available

Contact Inputs
• Up to 30 User definable inputs
• Assignable to Trip, Alarm, Control

Contact Outputs
• 2 Form A Contactor outputs standard
• Up to 16 additional outputs available in
combinations of form A and Form C

56 /
GE /
October 21, 2019
Connection of 3 Phase CT’s

57 /
GE /
October 21, 2019
Connection of 2 Phase CT’s
Power Flow

58 /
GE /
October 21, 2019
Connection of Core Balance CT

59 /
GE /
October 21, 2019
Connection of Thermistor

60 /
GE /
October 21, 2019
Connection of 3 Phase Voltage

Wye Delta

61 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
RTD’s
Up to 6 Three Wire RTD Inputs Available
• RTD Temperature
 Stator
 Bearing
 Ambient
 Other
• RTD Types
 100 Ohm Nickel
 120 Ohm Nickel
 100 Ohm Platinum

62 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Learned motor operating information

Monitoring the motor’s operating characteristics assists in


determining the motor start protection parameters, and is
also a powerful tool for determining the operating
condition of the system, motor, and connected loads.

• Acceleration time of last motor start • Thermal Capacity used during last
• Maximum current during last motor start motor start
• Average thermal capacity used during • Average Motor Loading
motor start • Maximum local RTD temperatures

63 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Statistical Information
Motor Statistical information provides information critical
for planning preventative maintenance for the motor and
associate system equipment
Motor operating statistics Protection operation statistics
• Number of Lockout Resets Performed • Total number of trips issued by the
• Total Motor Running Hours relay
• Time Remaining to Motor Restart • Breakdown of total trips issued for each
protection element

64 /
GE /
October 21, 2019
MM300 . . . Monitoring & Metering
Event Recorder
• Accessible through front panel
or EnerVista MM300 Setup
• Captures up to 255 events
• Trips
• Alarms
• Loss of Control Power
• Emergency Restarts
• Service Alarms
• General Events (Motor
Start / Stop)

65 /
GE /
October 21, 2019
Communications

g imagination at work
66 /
GE /
October 21, 2019
MM300 . . . Communications

• Configuration, troubleshooting,
monitoring and control
• Powerful and Flexible communication
options
• Multiple ports allow simultaneous
communication with different masters
• Open protocols and hardware for
interfacing with many different
monitoring and control systems

67 /
GE /
October 21, 2019
MM300 . . . Communications
Hardware Interfaces

RS485 Port Front USB Port Ethernet RJ45 Profibus Port


• Monitoring • Configuration • Networking • Monitoring
• Control • Diagnostics • Monitoring • Control
• Configuration • Fault Analysis • Control DeviceNet Port
• Diagnostics • Maintenance • Configuration • Monitoring
• Fault Analysis • Fault Analysis • Control

Flexible and Open communication protocols allow information


to be retrieved by third party monitoring and control system
Modbus RTU
Profibus DP
DeviceNet
Modbus TCP / IP

68 /
GE /
October 21, 2019
Communication

Concurrent Communications Capable 69 /


GE /
October 21, 2019
RS-485 Connection

70 /
GE /
October 21, 2019
Graphic Display Panel

71 /
GE /
October 21, 2019
MM300
Graphic Display Panel
Function Keys
Graphical Display
• Programming and all
relevant information on
Graphical
LED indicators
motor status.
display
Soft Keys
Control Keys
• Used to perform page
Soft keys
specific functions
USB port USB Port
• Used to connect PC to
front mini USB.

72 /
GE /
October 21, 2019
MM300
Introduction to the Graphic Control Panel
Function Keys Function Keys
• Perform labeled functions
• Home recalls Home Page
LED indicators
Graphical
display • Up/Down Keys scroll
though page, selection field,
Control Keys
etc.

Soft keys • ESC , escape from current


screen or edit
USB port • ENTER selection of field or
confirming entry
• HELP displays context help

73 /
GE /
October 21, 2019
MM300
Introduction to the Graphic Control Panel
Function Keys

Control Keys
• Start / Stop Function Keys
Graphical LED indicators
display • 10 LED indicators

Control Keys

Soft keys

USB port

74 /
GE /
October 21, 2019
MM300
Graphical Display Overview
Header Bar
• Path Indication
• Access Level
• Date and Time
Soft-Key Labels
• Soft-keys change for
current screen
Soft Key Color
Convention
• Identifies current
screen and type of
information
75 /
GE /
October 21, 2019
MM300
Display Page Hierarchy
Figure 40: MM300 display page hierarchy

Hierarchy is three levels


deep
Hierarchy is navigated
through the soft keys at
the bottom of the MM300

76 /
GE /
October 21, 2019
MM300
Display Page Hierarchy

Trips

Control

Virtual

77 /
GE /
October 21, 2019
Software

78 /
GE /
October 21, 2019
MM300 . . . EnerVista™ Software
Device Setup & Document Management Toolset
• Easily configure IEDs from a single Application
• Create and Edit setting files Offline, or in Real Time
• Manage your Support Documents & Software Tools
• Receive Automatic Notification of new updates

Easy to Use Monitoring and Data Recording


for Small Systems
• Pre-configured screens for Instant Monitoring
• Single-Line monitoring
• Annunciator Alarms
• Trending Reports
• Automatic Fault Data Collection

Troubleshooting and Reporting Tools


• Single click retrieval of Fault Data
• Security Audit Report shows details of setting changes
• Health Report showing status of Protective Devices
• Track Firmware Configuration changes to GE devices

79 /
GE /
October 21, 2019
MM300 . . . EnerVista™ Software
MM300 Setup

A Powerful and Simple way to Configure, Monitor, and Troubleshoot your relays
80 /
GE /
October 21, 2019
MM300 . . . EnerVista™ Software
MM300 Setup
• Online and Offline configuration of settings
• Simple Drop-Down menu for selecting parameters
• Save complete configuration files to and from the relay

Online Device Window

Active Settings Window

Offline File Window

81 /
GE /
October 21, 2019
Programming using MM300 Set Up
• No Charge PC Software
• Graphical Interface, Intuitive Navigation
• Local or Remote Access
• Allows:
– Programming
– Elements, Communications and Logic
– Viewing of Metering
– Viewing of Logs
– Viewing of Diagnostics
– Viewing of Oscillography
– Firmware Upgrades
82 /
GE /
October 21, 2019
EnerVista Launchpad

83 /
GE /
October 21, 2019
EnerVista Launchpad

84 /
GE /
October 21, 2019
MM300 Set Up: Getting Started

ON LINE WINDOW

SETTING AREA

OFF LINE WINDOW

85 /
GE /
October 21, 2019
Make a New MM300 File
Offline Configuration

For Offline
configuration of the
MM300 the order
code must be entered

86 /
GE /
October 21, 2019
MM300 Set Up: File Select

ON LINE WINDOW

Click to Expand File Name SETTING AREA

OFF LINE WINDOW

87 /
GE /
October 21, 2019
MM300 – Online Configuration

• Online Confirguration
through Device Setup
or Quick Connect
• Interface
• IP Address or COM
Port
• Slave Address

88 /
GE /
October 21, 2019
MM300 – Online Configuration

• Online Configuration
through Device Setup
or Quick Connect
• Read Order Code
• Software and Device
will communicate and
Order Code will be
written to software
• Device is ready for
Programming

89 /
GE /
October 21, 2019
Main Menu

Info on MM300
CTs, VTs, Inputs
Protection Settings
Control Settings
MODBUS Memory Map
FlexLogic

90 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Motor General Nameplate Settings

91 /
GE /
October 21, 2019
Programming using MM300 Set Up:
CT/VT Info

92 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Contact Sensing Inputs

93 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Contact Outputs

94 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Thermal Protection

95 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Mechanical Protections

96 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Electrical Protections

97 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Temperture Sensor Details

98 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Starter Circuit/Logic Details

99 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Start Inhibits

100 /
GE /
October 21, 2019
Programming using MM300 Set Up:
Interlocks

101 /
GE /
October 21, 2019
Programming using MM300 Set Up:
FlexLogic

Thermal Overload
Emergency Stop
OR VIRTUAL OUTPUT #1
Ground Fault
Mechanical Jam CO-X

102 /
GE /
October 21, 2019
MM300 . . . Motor Management System
Ordering Options
MM300 - * * - * * * * * * * * Description

Control Panel X None


B Basic Control Panel
G Graphical Control Panel inc. USB
Language E English
C Chinese
Power Supply H High (60-300 vac/80-250vdc) (Standard)
Communication S RS485 Modbus RTU (Standard)
D RS485 + DeviceNet Slave + 10/100 Modbus TCP
P RS485 + Profibus DP Slave + 10/100 Modbus TCP
Options S Standard Control and Event Recorder
1 + Undervoltage Auto-restart
2 + Waveform Capture, Data Logger
3 + Flexlogic
I/O X X X X None
A 3 Phase Current + Thermal O/L, Under Current, Single Phase Under Power
B 3 Phase Voltage Metering + 3 Phase Under Power, Under / Over Voltage, Phase reversal
G G G G 3 x RTD : 100PT, 120NI, 100NI - max 2
C C C C C 4 x 10A Relay Form C - max 5
D D D D 2 x 10A Relay Form A and 6 x Digital Input 60-300ac/dc (Standard) - max 5
Base Expansion Expansion
I/O Module 1 Module 2

103 /
GE /
October 21, 2019
MM300 . . . Motor Management System

Questions?

104 /
GE /
October 21, 2019
MM300 . . . Motor Management System
Notes Pages

105 /
GE /
October 21, 2019

You might also like