Professional Documents
Culture Documents
Eaton Arc Flash
Eaton Arc Flash
&
Predictive Diagnostics of Partial Discharge
in
Medium Voltage Power Systems
Presented to
Bogota, Colombia
7 March 2006
(National Fire Protection Association)
NFPA 70E
Reduce ARC-Flash
Hazards
At What Cost?
• $4,000-8,000/each “Simple Systems”
– Dedicated to one type breaker
– Onerous to use
– Difficult to move between cells
• $20,000-35,000/each “Complex Systems”
– Multiple breaker capable
– Constant, complex programming
– Difficult to setup
• $18,000/each “Preferred Systems”
– Universal LV and MV-Multiple breakers
– Simple programming
– Quick Set-up and maneuverable
Universal Design
• LV or MV
• Any breaker *
– Air-Magnetic
– Vacuum
– Vacuum Replacement
– SF6
• 1-2 high MV
• 1-4 high LV
*Breakers must have a rotary racking system
Universal Remote Power
Racking
6.9 kV - 17,000 HP
<<< Corona
Switchgear
Bus Damage
Results of Partial Discharge
Switchgear
Surface Tracking
On Shutter
Results of Partial Discharge
Switchgear
<<<Primary Stab - Tracking
Current Transformer
Corona Damage >>>
Results of Partial Discharge
38 kV Bus Duct
Results of Partial Discharge
25 kV Terminations
Predictive Maintenance Sensors
RTD
Module
RFCT
Sensors
for
Large Power
Transformers
Coupling
Capacitor
Where to Install Coupling Capacitors?
Single-High Gear
Zone of Protection
Where to Install Coupling Capacitors?
Double-High Gear
1 2 3 4 5 6 7 8
On Main Bus
End-Section
On Main Bus in
Transition Section
RFCT Sensor Installation
• Continuous Monitoring
• Online Monitoring
• Critical Signal Filtering and
Conditioning
• Superior Sensor Placement
What’s Inside the Box
Noise Capacitor
InsulGard 1 Channel
Status
4-20 Temperature
MA Dynamics
Load
Display Communication Humidity
Keyboard Modem
Communications
RS485 Mod Bus
PC Local
Before Repair
After Repair
Case Study - 49 MVA Generators
– Visual Inspections
• Unit 2
– No loose wedges found
• Unit 1 Initial Inspection
– No problems Found
– Decided to do offline test
– Additional Testing On Unit 1
• Test #1
– Tested one phase energized at a time
– Remaining phases grounded
– Phase to ground voltage applied
– Low PD levels found
• Test #2
– Second AC source used on other phase to simulate phase
to phase voltage levels
– PD sites were excited and located
Case Study - 49 MVA Generators