ME5304 –Refrigeration & Air

Conditioning
Dr.(Mrs.) K.T.K.Muthumali DeSilva
Department of Mechanical and Manufacturing Engineering
Air Conditioning Systems
Introduction
 Supply and maintain desirable internal atmospheric conditions for human
comfort, irrespective of thermal conditions.
 Factors affecting comfort air conditioning:
 Temperature of air
 Humidity of air
 Purity of air
 Motion of air
 Equipments used in air conditioning system:
- Circulation fan - Supply outlets
- Air conditioning unit - Return outlets
- Supply duct - Filters
DMME_FoE_UoR 3
Classification of air conditioning systems
 According to the purpose
 Comfort air conditioning system
 Industrial air conditioning system
 According to season of the year
 Winter air conditioning system
 Summer air conditioning system
 Year-round air conditioning system
 According to arrangement of equipment
 unitary air conditioning system
 Central air conditioning system

DMME_FoE_UoR 4
Winter/ summer air conditioning system

Summer air-conditioning system

Winter air-conditioning system

DMME_FoE_UoR 5
Room Sensible Heat Factor (RSHF)
𝑹𝒐𝒐𝒎 𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕(𝑹𝑺𝑯)
𝑹𝑺𝑯𝑭 =
𝑹𝒐𝒐𝒎 𝑻𝒐𝒕𝒂𝒍 𝑯𝒆𝒂𝒕(𝑹𝑻𝑯)

𝑹𝒐𝒐𝒎 𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕(𝑹𝑺𝑯)


=
𝑹𝒐𝒐𝒎 𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕(𝑹𝑺𝑯) + 𝑹𝒐𝒐𝒎 𝑳𝒂𝒕𝒆𝒏𝒕 𝑯𝒆𝒂𝒕(𝑹𝑳𝑯)

Effective Room Sensible Heat Factor (ERSHF):

𝑬𝑹𝑺𝑯 𝑬𝑹𝑺𝑯
𝑬𝑹𝑺𝑯𝑭 = =
𝑬𝑹𝑻𝑯 𝑬𝑹𝑺𝑯 + 𝑬𝑹𝑳𝑯

ERSH = Effective room sensible heat = RSH+OASH*BPF


ERLH = Effective room latent heat = RLH+OALH*BPF
ERTH= Effective room total heat = ERSH+ ERLH
BPF = By-pass factor
DMME_FoE_UoR 6
Grand Sensible Heat Factor (GSHF)
𝑻𝒐𝒕𝒂𝒍 𝑺𝒏𝒆𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕 (𝑻𝑺𝑯)
𝑮𝑺𝑯𝑭 =
𝑮𝒓𝒂𝒏𝒅 𝑻𝒐𝒕𝒂𝒍 𝑯𝒆𝒂𝒕 (𝑮𝑻𝑯)

𝑻𝒐𝒕𝒂𝒍 𝑺𝒏𝒆𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕 (𝑻𝑺𝑯)


=
𝑻𝒐𝒕𝒂𝒍 𝑺𝒏𝒆𝒔𝒊𝒃𝒍𝒆 𝑯𝒆𝒂𝒕 𝑻𝑺𝑯 + 𝑻𝒐𝒕𝒂𝒍 𝑳𝒂𝒕𝒆𝒏𝒕 𝑯𝒆𝒂𝒕 (𝑻𝑳𝑯)

𝑹𝑺𝑯 + 𝑶𝑨𝑺𝑯
=
𝑹𝑺𝑯 + 𝑶𝑨𝑺𝑯 + (𝑹𝑳𝑯 + 𝑶𝑨𝑳𝑯)

𝑂𝑢𝑡𝑠𝑖𝑑𝑒 𝐴𝑖𝑟 𝑆𝑒𝑛𝑠𝑖𝑏𝑙𝑒 𝐻𝑒𝑎𝑡 (𝑂𝐴𝑆𝐻) = 0.02044 𝑣1 (𝑡𝑑1 − 𝑡𝑑2 )

𝑂𝑢𝑡𝑠𝑖𝑑𝑒 𝐴𝑖𝑟 𝐿𝑎𝑡𝑒𝑛𝑡 𝐻𝑒𝑎𝑡 (𝑂𝐴𝐿𝐻) = 50 𝑣1 (𝑊1 − 𝑊2 )

𝑂𝑢𝑡𝑠𝑖𝑑𝑒 𝐴𝑖𝑟 𝑇𝑜𝑡𝑎𝑙 𝐻𝑒𝑎𝑡 (𝑂𝐴𝑇𝐻) = 0.02 𝑣1 (ℎ1 − ℎ2 )


DMME_FoE_UoR 7