Shunt Reactors ABB

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 17

Dr. Claes Bengtsson, Global Product Manager, Reactors.

PowerGen Europe June 2010

Variable Shunt Reactors


Optimize Transmission Systems

© ABB Group
February 24, 2020 | Slide 1
Matured products ??

 Is transformer- and
shunt reactor
technology matured?

 Some basics around


reactive power
compensation
 New opportunities in
reactive power
compensation
 Applications and
benefits

© ABB Group
February 24, 2020 | Slide 2
Voltage at line end increases at low load

P2, Q2

U1 U2
Q

Voltage profile at no or low load (P2),”Ferranti effect”

1,0 pu

U1 U2

© ABB Group
February 24, 2020 | Slide 3
The shunt reactor stabilize the system voltage

P2, Q2

U1 U2
Q

Voltage profile at no or low load (P2), with connected SR

1,0 pu

U1 U2

The shunt reactor consumes reactive power


generated by the transmission line
© ABB Group
February 24, 2020 | Slide 4
The shunt reactor stabilize the system voltage

P2, Q2

U1 U2
Q

Voltage profile at no or low load (P2), with connected SR

1,0 pu

U1 U2

Switching in the reactor gives a step change in the


voltage on the transmission line
© ABB Group
February 24, 2020 | Slide 5
The voltage profile is load dependent

(R) + X
P2, Q2

U1 U2
Q

Increased load (P2), voltage profile with connected SR

1,0 pu

U1 U2

© ABB Group
February 24, 2020 | Slide 6
Fundamental challenge

 The is an optimum reactor rating at


a certain load
 Load varies with time
 Seasonal variations
 Daily variations
 Shunt Reactors are by tradition fixed in rating
 Switching fixed reactors in and out leads to
 Voltage steps
 Wear on breakers
 Non-optimal compensation

© ABB Group
February 24, 2020 | Slide 7
ABB is the world leader on HV shunt reactors

 >1000 reactors delivered to >40 countries


 Complete range
 <800 kV, <300 Mvar
 Full 3-phase testing capabilities
 Outstanding performance
 Field reliability
 Low sound and vibrations
 Leading the technology development
 World’s largest 3-phase reactors (300 Mvar)

 So why selling static reactors when the


need of reactive power compensation is
dynamic?
© ABB Group
February 24, 2020 | Slide 8
There are new solutions today

 A new product class: Variable Shunt Reactors


 VSR provides dynamic compensation of
reactive power
 Regulation range around 100%
(e.g. 50-100 Mvar)
 Ratings up to 200 Mvar, 500 kV
 ABB is the world leader for VSRs
 So far 16 VSRs sold to US, Norway,
Denmark, Sweden and Africa
 The world’s largest VSR now in safe operation
 120-200 Mvar, 400 kV

© ABB Group
February 24, 2020 | Slide 9
VSR applications: Wind parks

 Unpredictable and fluctuating active


power exchange
 The variations in reactive power
consumption with varying wind-power
production require control:
 SVC
 Regulated shunt reactor
 Switched shunt reactor
 Grid codes specify the amount of
reactive power exchanged with the main
grid

© ABB Group
February 24, 2020 | Slide 10
VSR applications: Large and long cable networks

 Large and long AC cable networks in


EHV network systems, e.g. USA and Italy.
 Extended use of cables put higher
demand on reactive power
compensation
 Daily and season load variation in
highly populated areas
 Power quality is important

© ABB Group
February 24, 2020 | Slide 11
VSR applications: Daily load variations in regular
networks

 Transmission systems with time variation


of load, generation and power exchange
with other networks
 Interaction with other types of
installations, e.g. SVCs, HVDC
transmission links
 Controllability of the system increase
in importance or is uncertain
 Increased demands on flexibility
 Power quality is important

© ABB Group
February 24, 2020 | Slide 12
Summary of VSR benefits

 Reduced voltage jumps during switching operation


 Voltage stability at varying loads
 Flexibility for new future load conditions
 Improved interaction with other equipment
 Coarse tuning of SVC equipment for best
dynamical operation
 Reactive power compensation related to loading
of HVDC links (a HVDC converter consumes
reactive power)
 No parallel fixed reactors, reduction of number of
breakers, reduced footprint and maintenance
 Flexible spare unit possibility and flexibility to move a
© ABB Group
February 24, 2020 | Slide 13
VSR to other location
Conclusions

 Transmission networks have time varying loads


 Transmission networks have time varying needs for
compensation of reactive power
 VSR is a new product type that provides this

 Do we know the load- and generation patterns of


tomorrow?
 A shunt reactor with fixed rating have a life time of
30+ years...

© ABB Group
February 24, 2020 | Slide 14
Gallery

120-200 Mvar,
400 kV
Statnett,
Norway

50-100 Mvar, 242 kV


Dominion, USA

Active part
50-100 Mvar, 242 kV

© ABB Group
February 24, 2020 | Slide 15
Why to be careful when buying a reactor?

 It should withstand the


load of 40 cars, applied
100 times per second for
30 years continuous
without rattling and high
noise
 Long time field reliability
is a key issue
 Shunt reactors are
difficult

© ABB Group
February 24, 2020 | Slide 17