Following steps are required to be followed while designing the one way slabs:
• Step1: Calculate the thickness of the slab in accordance with the provisions of ACI Code
given the table below:
• Step2: Perform the load calculations and calculate the factored load for slab design.
• Step3: Perform the shear capacity check in accordance with ACI Code to validate the slab
thickness.
• Step4: Calculate the temperature and shrinkage reinforcement required for the slab.
• Step5: Check that the reinforcement provided in any section of the slab is not less than the
temperature and shrinkage reinforcement calculated in step4 .
NUMERICAL PROBLEMS
PROBLEM1: A reinforced concrete slab with dimensions as shown in the figure is supported on the
brick walls at all sides. The slab is reinforced with #3bars spaced at 10in c/c as shown. The
superimposed dead load on the slab is 30 Psf and live load is 30 Psf determine the factored design
load and design the slab according to the load applied. Compressive strength of concrete is 3000
Psi and density is 150 Pcf.
#3@10”c/c 8 feet
#3@10”c/c
20 feet
Data:
Superimposed dead load = DL = 40 Psf.
Superimposed live load = LL = 30 Psf.
Concrete compressive strength = Fc’ = 3000 Psi.
Density of reinforced concrete = ϒ = 150 Pcf.
Length of shorter side = la = 8 feet.
Length of longer side = lb = 20 feet.
Aspact ratio =m=?
Factored design load = Wu = ?
Slab thickness =h=?
Solution:
1. Aspact Ratio:
𝑚 = 𝑙𝑏/𝑙𝑎
𝑚 = 20/8
ℎ = 𝑙/20
ℎ = 8 𝑋 12/20
ℎ = 96/20
ℎ = 4.8"
or
𝒉 = 𝟓"
3. Load calculations:
Vu = 147 𝑋 8Τ
2
Vu = 𝟓𝟖𝟖 𝒍𝒃𝒔
∅ 𝑉𝑐 = ∅2√𝐹𝑐 ′ 𝑏𝑑
We assume that #4 bar is used as the main reinforcement having diameter of 0.5”.
𝑑 = 5 − 3/4" − 0.5/2"
𝒅 = 𝟒“
Then,
∅ 𝑉𝑐 = 0.85𝑋2𝑋 3000𝑋12𝑋4
30 feet
S1 S2 S2 S3
1. Aspact Ratio:
𝑚 = 𝑙𝑏/𝑙𝑎
𝑚 = 30/13
ℎ = 𝑙/24
ℎ = 13 𝑋 12/24
ℎ = 156/20
ℎ = 7.8"
or
𝒉 = 𝟖"
3. Load calculations:
Vu = 336 𝑋 13Τ
2
Vu = 𝟐𝟏𝟖𝟒 𝒍𝒃𝒔
∅ 𝑉𝑐 = ∅2√𝐹𝑐 ′ 𝑏𝑑
𝑑 = 8 − 3/4" − 0.5/2"
𝒅 = 𝟕"
Then,
∅ 𝑉𝑐 = 0.85𝑋2𝑋 3000𝑋12𝑋7
Asmin = ρbh
Asmin = ρbh
Asmin = 0.0018 x 12 x 8
Use #3 @ 7” c/c
PROBLEM 3: A reinforced concrete slab with dimensions as shown in the figure is supported on the
brick walls at all sides. The slab is reinforced with #3 bars spaced at 6in c/c as shown. The
superimposed dead load on the slab is 30 Psf and live load is 30 Psf determine the factored design
load and design the slab according to the load applied. Compressive strength of concrete is 3000
Psi and density is 150 Pcf.
7 feet
Slab
Data:
Superimposed dead load = DL = 100 Psf.
Superimposed live load = LL = 60 Psf.
Concrete compressive strength = Fc’ = 3000 Psi.
Density of reinforced concrete = ϒ = 150 Pcf.
Length of shorter side = la = 13 feet.
Length of longer side = lb = 30 feet.
Aspact ratio =m=?
Factored design load = Wu = ?
Slab thickness =h=?
Minimum steel reinforcement = 𝐴𝑠𝑚𝑖𝑛 = ?
Solution:
ℎ = 𝑙/10
ℎ = 6.25 𝑋 12/10
ℎ = 75/10
ℎ = 7.5"
2. Load calculations:
Vu = 318 𝑥 6.25
Vu = 𝟏𝟗𝟖𝟕. 𝟓 𝒍𝒃𝒔
∅ 𝑉𝑐 = ∅2√𝐹𝑐 ′ 𝑏𝑑
∅ 𝑉𝑐 = ∅2√𝐹𝑐 ′ 𝑏𝑑
Now we can calculate d as
𝒅 = 𝟔. 𝟓"
Then,
∅ 𝑉𝑐 = 0.85𝑋2𝑋 4000𝑋12𝑋6.5
As per ACI Code minimum reinforcement required will not be less than temperature
and shrinkage requirements given as:
As = ρbh
As = 0.002x12x7.5
𝑨𝒔 = 𝟎. 𝟏𝟖 𝒊𝒏𝟐 /𝒇𝒕.