Professional Documents
Culture Documents
VFD
VFD
Drives (VFD)
M.SHAKEEL-UD-DIN
Content
Introduction
Functions of Variable Frequency Drive
Control Arrangements of VFD
Parts & Operation of a VFD
Application Terminology for VFD
Power Input Terminology for VFD
Maintenance of VFD
Squirrel Cage Induction Motor (SCIM)
Power Electronic Convertors
Variable Frequency Drive (By SUD) 2
Content: (Continued)
SCR / Thyristors
Insulated Gate Bipolar Transistor (IGBT)
With the use of a Variable Frequency Drive (VFD) not only can
the AC motor be started and stopped as in the home, but more
sophisticated controls are accomplished. A VFD can send a
modulating signal to the motor, which allows a variety of speeds
to be delivered not just an ON/OFF signal. This variety of speeds
can be used to match the motor to a particular task. There are a
number of functions that the VFD accomplishes with commercial
3-phase AC motors, which are covered in the pages that follow.
To understand function
Of a VFD better, an
Example of cooling
Tower fan is used.
START
One function of the VFD is to start the fans. This could be done locally
off the keypad of the drive or remotely from a switch. This remote
switch could be a continuous single pole- double-throw (SPDT) switch
or a momentary (push button) switch.
STOP
In the picture above, the SPDT switch is used to stop the pump. If
there are 2 separate push button switches, one to Start and one to
Stop, this arrangement is known as a 3-wire Start/Stop. If only one
switch, a continuous switch, is used, then it is referred to as a 2-wire
Start/Stop. In the picture above, since there is one switch, so this is a
2-wire Start/Stop.
The speed of the cooling tower fans must be variable to allow for a
slower speed when there is little demand for cooling and a higher
speed when more cooling is needed. This allows the operator to match
the speed of the fans to a particular demand. The setting of this speed
is known as the Reference. In most examples, reference refers to speed
in Hertz (Hz), maximum reference of 60Hz, and minimum reference of
6Hz for fans and 18Hz for pumps. It could also be used in regards to a
pressure setting, maximum reference of 100psi (690kPa), minimum
reference of 40psi (275kPa), if a transmitter were attached to the VFD.
In the picture above, the display of an VFD, Speed in Hz is the
reference. The plus (+) key is used to increase the reference making the
fans go faster and the minus (-) is used to decrease the reference point
slowing the fans down.
Function #4 – Limits
Function #5 – Ramping
To reduce mechanical
wear, it is important to
control the acceleration,
(ramp up) and deceleration,
(ramp down).
The VFD also ramps the fans up and ramps them down. When
the fans starts, acceleration, it is important that there is no
sudden jump to the reference speed, or there can be stress on
the gear boxes. In the example above, a ramp-up slowly
increases the speed from stopped or 0Hz up to the reference,
34Hz, over a certain amount of seconds perhaps 10. If this
ramp up is too short, the drive can trip on an over current
alarm or torque limit. If the VFD is tripped, the fans stop and it
might require an operator to manually reset the VFD. Many
VFDs have an automatic reset setting of 1 time to infinite
times. Ramping is very important for pumps, to avoid water
hammer.
Function #6 – Forward/Reverse
FORWARD
One function of the VFD is to operate the motor
in a forward direction, to move the air through the
cooling tower and out the top. In its default (factory
set) condition the VFD is only allowed to go
forward. Some fans if driven backwards may have
problems.
REVERSE
In the cooling tower example the
fans need to operate in Reverse in
order to complete a defrost cycle,
when the outside temperature is
very cool. Power going to the motor
must be changed to move the fans
backwards (Reverse). If there were
no VFD, 2 of the 3 leads of the
3-phase motor would be switched
in order for the motor to change
its direction and go backwards.
This switching of the motor leads is
done inside the VFD.
In the picture above, a VFD, motor and fan are operated from the
keypad on the front of the drive. Local (Hand) control of the VFD
means that operation of the VFD is completed strictly through the
keypad on the front of the drive, or Local Control Panel (LCP). An
operator monitors the readings and controls the VFD by using this
keypad. Even if the keypad, LCP is remotely mounted away from the
drive, maximum of 3m (10’), the control arrangement inside the
program of the VFD is still considered as LOCAL. If any line is labeled as
LOCAL in the program, think KEYPAD.
2) Remote Control
3) Multi-Motor Operation
In the example above each of the 4 AC motors is the same size and has a
maximum current rating, Full Load Amps (FLA) of 15 amps. The VFD must
be sized for 60 amps. Note individual overload protection on each motor.
4) Master/Slave (Leader/Follower)
In the picture above, the VFD on the first supply fan is the Master/Leader and it generates
a reference signal for one of its analog outputs (AO). The VFD on the second supply fan is
the Slave/Follower, and it monitors this 4-20mA reference signal from the master using
the slave’s analog input (AI).
One VFD is selected as a Master or Leader drive. It is setup to send a reference signal
and ON/OFF commands to the Slave or Follower drive. In the example above, 2 fans
are used for Supply Air on a Variable Air Volume (VAV) system. The VFD operating the
top fan is considered the Master or Leader. It varies its speed to match the static
pressure needs in the supply duct. The bottom fan and VFD, follows the top supply
fan and is known as the slave or follower. The slave can match the speed to within
0.3Hz of the master, over the operating range from about 6Hz to 60Hz.
Rather than always matching the speed of the master VFD, the slave VFD can operate
at a percentage of the reference. If a positive pressure needs to be maintained in a
zone, the slave VFD on a return fan can be slightly behind (-10% of reference) of the
master VFD on the supply fan. The supply fan always runs faster than the return fan
causing a positive pressure in the zone. In this last application using a volumetric
sensor comparing the CFM (L/s) from supply and return to control the return fan
would give a much greater accuracy than the Master/Slave arrangement.
Up to this point most of the previous control arrangements have been closed
loop, which means that there is feedback signal monitoring the controlled
variable, going directly to the VFD. Closed Loop is used for stand alone
control. In the example above, the VFD monitors the signal coming from the
4-20mA static pressure sensor in the supply duct. In a variable air volume
(VAV) system it is important to maintain Static Pressure in the duct for proper
operation of the VAV boxes.
There is always a difference between the set point and the actual feedback pressure.
This is referred to as Offset, “off the set point” or error. PID settings attempt to
reduce this error.
“P” stands for Proportional Gain which can be considered as a multiplier of the error.
The higher the gain the more accurate, but if it is set too high, the control can
become unstable and jittery. With too high of a gain setting, the VFD oscillates
between maximum speed and minimum speed, “hunting” for the correct speed. The
gain must be high enough to be sensitive but not too high to cause hunting. Each
application is different, but a proper starting setting for pumps is 4.0 and 2.0 for fans.
“I” stands for Integral which looks at the error over a certain amount of time. The
lower the number the more frequently it checks the error. If the I setting is too low,
the motor again appears to be hunting. Based on most applications, a pump has its I
setting for 20 seconds and 30 seconds for fans.
“D” stands for derivative which, if used, compensates for momentary changes in the load. In
most HVAC applications, this parameter is not used, keeping it OFF.
This section covers the parts and operation of the Variable Frequency Drive (VFD).
It is important to keep in mind that the Drive is just one part of a system. In the
diagram above, notice the disconnect switch, fuses, bypass switch, thermal
overloads, BAS, etc. all play an important part in making an application work
correctly.
Inside the VFD there are 4 major sections: rectifier, intermediate circuit (DC Link),
inverter and control/regulation. This fourth section, control and regulation,
interfaces with the other 3 sections.
In very general terms the operation of the drive is as follows. Power first goes into
the rectifier, where the 3-phase AC is converted into a rippling DC voltage. The
intermediate circuits then smoothens and holds the DC Voltage at a constant level
or energy source for the inverter. The last section, the inverter, uses the DC
voltage to pulse the motor with varying levels of voltage and current depending
upon the control circuit. The pattern of the pulses going to the motor makes it
appear similar to an AC sinusoidal waveform.
2) Rectifier Section
The 3-phase AC voltage goes into the rectifier section which is made up of a group of gated
diodes (silicon rectifiers or SCRs). In most VFDs, these diodes are in a group of 6 as diagramed
above. One VFD manufacturer has stressed that there should be more sets of diodes, 12, 18,
even 24.
Diodes (D1 through D6) allow current to flow only in one direction when enabled by the gate
signal. In this diagram, the AC power on L1 goes into Diodes D1 and D2. Because of the position
of these diodes, current flow can only go up. The D1 diode conducts when the AC is positive
and D2 conducts when the AC goes negative. This drives the top line (+) more positive and the
bottom line (-) more negative. Diodes D3 and D4 convert L2 power to DC and Diodes D5 and D6
convert L3. A volt ohmmeter or VOM can be used to measure this DC voltage. In this type of
circuit, the DC voltage is 1.35 times the AC line voltage.
If 240 Vac is coming in, 324 Vdc is generated.
If 380 Vac is coming in, 513 Vdc is generated.
If 460 Vac is the line voltage, 621 Vdc is generated.
If 575 Vac is the line voltage, 776 Vdc is generated.
Because of line (power coming in) and load (power to the motor) changes, the DC Voltage level
is constantly moving above and below this expected value.
On larger drives, 22 – 450kW (30 – 600Hp), a part of the rectifier section is known as the
soft charge circuit, which is used to power up the drive. With this circuit, when power is
applied, the inrush of current is restricted going to the large capacitors in the DC Link, so
that they may charge up slowly (within a couple of seconds). If this circuit was absent, line
fuses would be blown every time the VFD was started. The soft charge circuit on some of
the VFDs has a resistor or two in line with the current to slowly allow charging of the
capacitors. This current resistor even has its own safety, a thermal switch, which shorts out
if the current rush is too high in the soft charge circuit. The shorted thermal switch blows
fuses on the soft charge circuit preventing the drive from starting.
Once main power is applied to the drive, the SCRs in the main rectifier section remain off.
The much smaller rectifier section in the soft charge circuit starts, applying DC power
through the current resistors charging up the capacitors in the DC Link. When these
capacitors are charged to the DC voltage minimum value, the control section starts the
firing of the SCRs in the main rectifier. Because of the amp draw through the current
resistors in the soft charge circuit, time is needed to cool them off, so the 22 – 450kW (30 -
600 Hp) drives are limited to 2 start per minute.
The Intermediate Circuit also known as a DC Link, can be seen as a power storage
facility for the next section, the inverter section. There are 2 major components
to the DC Link section, capacitors and coils. In the diagram above only one
capacitor is shown but it is always a series of capacitors. Intermediate section
always uses DC coils also known as DC Line Reactors or DC chokes. For cost
considerations, most other VFD manufacturers do not offer these DC Line
Reactors as standard equipment. one is the ability to reduce harmonic noise
(interference) by 40% and the other is the ability to ride through a temporary
loss of power. This allows this drive to avoid numerous nuisance shut downs.
In the diagram above, notice that the rippled DC voltage coming in has now been
filtered to a relatively constant voltage. Remember that this DC Link Voltage is
1.35 times the input voltage. The value of the DC Link voltage can be read from
the display on the front of the drive. When ever working around the drive always
be careful and give it a healthy respect. The largest drive produces 620Vdc at 750
A.
5) Brake Circuit
6) Inverter Section
The next part of the VFD is the Inverter section. This section takes
the DC voltage from the intermediate section and, with the help
of the control section, fires each set of IGBT (Insulated Gate
Bipolar Transistors) to the U, V and W terminals of the motor. This
firing of the IGBTs is known as Pulse Width Modulation (PWM)
and is described in the next couple of slides.
The control section coordinates and regulates signals inside the drive.
This is where numerous calculations are completed to properly switch
the IGBTs. This control section uses Vector technology, which separates
the torque producing current from the magnetizing current. In the
diagram above the current going to the AC motor is being monitored.
The VFD has a special program, algorithm, called Automatic Motor
Adaptation (AMA), which determines the electrical parameters for the
connected motor while the motor is at a standstill. Many competitors
must decouple and spin the motor for tuning. Because the AMA
measures the resistance and reactance of the motor’s stator
establishing a motor model, the magnetizing current can be calculated.
This motor model is used to calculate the slip and load compensation.
1. Starting Torque
a) High Overload (HO)
• High Overload allows 160% starting current for 1 min.
• Most CT applications require High Overload.
• If drive exceeds 160% or 1 minute, VFD trips.
b) Breakaway Torque
• High Overload has a breakaway torque that allows 180%
starting current for 0.5 seconds.
• If drive exceeds 180% or 0.5 seconds, VFD trips.
• Open Loop
• Closed Loop
Closed Loop is where the controller inside the VFD can be used to
modulate the speed of a motor to maintain a process. It is the job of
the sensor or transmitter to measure a variable, in the example
above, this is static pressure. This sensor sends a signal (usually a 4-
20mA) to the controller over a particular range, in this example from
0” to 5”wc.
The sensor is wired to the current input of the VFD, the controller.
This signal is programmed in the VFD as the feedback signal. This
feedback signal must be given engineering units, from our example,
“inches of water column (“wc)” or “Pascals”. Inside the VFD the
feedback signal must also be given the range that matches the sensor.
When the sensor sees 4mA it is 0”wc (0 Pascals) and when the sensor
sees 20mA, the reading is 5”wc (1250 Pascals).
The VFD, controller, has a set point, action and PID settings
(explained later) to calculate the response necessary to
maintain the desired value seen at the sensor. The VFD sends
a signal to the fan to speed up or slow down to maintain a
certain level. The fan, controlled device, responds to match
the signal from the VFD, controller. It speeds up when the
level of the static pressure decreases and slows down when
the level of the static pressure is too high.
3. a) Control Action
PID Gain:
Proportional Gain is multiplied by the error to create an output.
The larger the proportional gain, the larger the output change for a
given error. If the proportional gain is too small (0.01) this
multiplier times the error has no effect on the speed of the VFD. If
the proportional gain is too large (3.00 or higher) the system can
become unstable, modulating between minimum speed and
maximum speed which is called “hunting”. A good starting place
for the Proportional Gain is about 1.00 but changes depending on
the application. If Proportional Gain is only used, without I or D
(explained on the next slide), the output is relatively close to set
point but there is always an error.
The first section covers the protection of the VFD from the
changes in incoming power. The first item covered is the
switching of power coming into the drive. There can also be
Surges and Sags in the incoming AC power. If these surges are
too high, or the sags are too low, the VFD shuts down for its
own protection. There must also be protection against
transients or spikes in the incoming power. Another item to be
covered is a Phase Imbalance between the 3 phases of power
coming into the drive. The last item to be covered are Fuses,
connectors and different voltages which might be
encountered.
d) Phase Imbalance
Fuses
No Power factor correction capacitors
•Voltage and current distortions caused by the VFD can effect in-coming
power.
High Noise above 450kHz is called Radio Frequency Interference (RFI) and
low noise below 3kHz is called Harmonics.
Multiples, mainly the 5th and the 7th harmonics of the fundamental
sine wave (60 Hz), caused by the switching current flow through the
VFD’s input rectifiers, causes interference in the incoming power.
Variable Frequency Drive (By SUD) 132
Power Input Terminology: (Continued)
• DC Inductors
• Isolation Transformers
• Expensive option
1) Keep it Clean
Most VFDs fall into the NEMA 1 category (side vents
for cooling air flow) or NEMA 12 category (sealed,
dust-tight enclosure). Drives that fall in the NEMA 1
category are susceptible to dust contamination. Dust
on VFD hardware can cause a lack of air flow,
resulting in diminished performance from heat sinks
and circulating fans (Photo 1).
2) Keep it Dry