Professional Documents
Culture Documents
FPRA Flexi Power Rectifier
FPRA Flexi Power Rectifier
Marko P. Komulainen
November 1st, 2009
• FPRA has the same conceptual approach like any Flexi BTS platform
products
– 3U high chassis build up from IP54 building blocks (rectifier and controller)
– Final IP55 protection achieved with front and rear covers (same covers as used
with FlexiBTS)
– Same FPRA unit used both indoor and outdoor environments
▪ Indoor and any outdoor cabinet installations without front/rear covers
▪ Outdoor stand alone installations (wall/pole/stack) with front/rear covers mounted
– Back to Front airflow like on FlexiBTS modules
• FPRA is
– common solution for any existing or new BTS platforms
– equal to Flexi BTS module in terms of dimensions and weight supporting Flexi
platform modularity
▪ Same fixing points, same mounting options
• No special system specific SW needed
– Only web browser needed for local connection to make the commissioning
• FPRA has no air filters => reduced maintenance needs => lower OPEX
• Output power scaleable from 2kW to 6kW (3 x 2kW)
• No space for batteries inside the FPRA
• Fan cooled rectifier modules
– Fan unit at rear of the each rectifier module
• Wide operating voltage range
– 90…310VAC
• Wide operating temperature range
– -33…+50C, temporarily up to +55C
• Limited DC-distribution
– 2x63A breakers for BTSs
– 3x63A breakers for battery connections
• FPRA has 6 user configurable external alarm (EAC) outputs and one alarm input
• Up to three FPRA’s can be chained to increase power on need basis
– Chaining cable is part of every FPRA delivery
FPRA with front cover mounted FPRA with rear cover mounted
Module front
DC-distribution
- 2 x 63A for BTSs
- 3 x 63A for batteries
Stack installation
UltraSite ID cabinet
FCSA (roof mounting)
FPRA inside FCSA FPRA outside FCSA Flexi ID cabinet With small SiteStar