Off Grid Design of IT Department: Sto. Domingo, Nowell Hayag, Frank Carlo BSEE 402-A

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 18

Off Grid Design of IT

Department
STO. DOMINGO, NOWELL
HAYAG, FRANK CARLO
BSEE 402-A
APPLIANCES in IT DEPT.
CCL 1 CCL 2 CCL 3 CCL 4
• 20PC • 16 PC • 15PC • 16PC
• 4Tube • Koppel • 4 tube • Koppel Aircon
• TV Aircon • 2 ceiling fan • Stand fan
• Koppel Aircon • TV • TV • TV
• Stand Fan • 4 tube • Koppel Aircon • 4tube
CCL 5 CCL 6 CCL 7 DCS 1
• 16PC • 2Stand fan • 4tube • 4 tube
• 4tube • 2tube • 2Ceiling fan • 2 ceiling fan
• Ceiling fan • 9PC • Stand fan
• TV • Condura Aircon
• Koppel Aircon
DCS 2 DCS 3 DCS 4 DCS 5 DCS 6 OFFICE
• 2 Tube • 3 Tube • 3 Tube • 3 Ceiling fan • 2 Ceiling • Koppel
• 2 Ceiling • 4 Ceiling Fan • 1 Ceiling fan • 2 Tube • 4 Tube Aircon
• Stand
HALLWAY RIGHT HALLWAY LEFT HALLWAY FRONT
• 4tube
• 4 Tube • 5 LED • 4 LED • 1 Tube • TV

SUMMARY OF LOAD
LOAD QUANTITY
PC 92
KOPPEL AIRCON 6
CONDURA AIRCON 1
STAND FAN 6
CEILING FAN 19
TUBE 53
LED 9
TV 6
COMPUTATIONS
1. CALCULATE THE LOAD
WATTAGE HOURS QUANTITY WATT-HR
• PC 180 x 12 x 92 =
198,720
• Tube 30 x 5 x 5 = 750
30 x 12 x 48 = 17,280
• TV 100 x 12 x 6 = 7,200
• Koppel Aircon
3400 x 12 x 6 = 244,800
• Stand Fan
65 x 12 x 5 = 3,900
70 x 12 x 1 = 840
• Ceiling fan
75 x 12 x 19 = 17,100
• Condura Aircon
680 x 12 x 1 = 8,160
• LED
9 x 5 x 9 = 405
TOTAL WATT-HR: 499,155 Watt-HR
TOTAL WATTS: 41,731 Watts

Considering 30% energy loss in the system:


Total watt-hour= 499.155kW-hr x 1.3= 650 kW-hr
Solar-Panel Selection
(Assume 6 hrs. of effective sunlight)
• Total Watt of panel capacity needed
=650 kW-hr ÷ 6 hrs. = 108.33kW

(Use 500 W, 48 V Solar Panel)


• Total Number of Panels= 108.33kW ÷ 500W = 217 pcs of panel
BATTERY SELECTION
Battery voltage = 48V
Battery capacity = load ÷ voltage = 650 kW-hr ÷ 48V = 13,541.67A-
hr.
(Let the battery loss is 15%)
Battery Capacity = 13,541.67A-hr. ÷ 0.85 = 15,931.38A-hr.
(Depth of discharges is 60%)
Capacity required = 15,931.38A-hr. ÷ 0.6 =26,552.3A-hr

USE 9 pcs. 3000A-hr, 48V. DEEP CYCLE LEAD ACID


BATTERY
CHARGE CONTROLLER SELECTION
CURRENT RATING = (500W x 217) ÷ (48V) = 2260.42A

But certain factors such as light reflection or cloud effect at


irregular intervals can increase current levels. Therefore, we
increase the charge controller amperage by a margin of 25%.
CURRENT RATING = 2260.42A × 1.25 = 2825.525

USE 10 pcs. 48V , 300A PWM CHARGE CONTROLLER


INVERTER SELECTION
Total Watts = 41,731 Watts
Battery Voltage = 24V/48V
Standard Ph. Voltage Rating = 220V/60

41,731/10kW = 5 Pcs
WE CHOOSE A “PURE SINE WAVE SOLAR POWER
INVERTER 10,000W 24V/48V DC TO AC 100V/220V/230V OF
5PCS”
ITEM SPECIFICATION QUANTITY PRICE TOTAL PRICE

SOLAR PANEL 500W, 48V 217 7,000 1,519,000

BATTERY 3000A-hr, 48V 9 37,000 333,000

CHARGE 48V , 300A 10 1,750 17,500


CONTROLLER
INVERTER 10,000W 24V/48V 5 3,750 18,750

TOTAL COST = 1,888,250 PESO


DESIGN