Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 82

TRANSFORMER PROTECTION

TRANSFORMER PROTECTION
TRANSFORMER PROTECTION

What should you know ?

1. Construction details of transformer


2. Ratings of transformer
3. Faults in a transformer
4. Protection philosophy
5. Relay List for Protection
TRANSFORMER PROTECTION

What is a transformer ?

- A device which transfers electrical energy


from one system to another system

- accepts energy at one voltage and delvers the same at


another voltage

- important link in power transmission

- helps in reduction of line losses


TRANSFORMER PROTECTION

What is inside a transformer ?

- Core
- Primary Winding
- Secondary Winding
TRANSFORMER PROTECTION

TRANSFORMER CONNECTIONS

Py and Sy windings are connected


in the following waysCore
- Wye – Wye ( Star-Star)
- Wye – Delta ( Star – Delta)
- Delta – Wye (Delta – Star)
- Delta – Delta
- Auto
- Zig - Zag
TRANSFORMER PROTECTION

Three Phase Transformer Connections


TRANSFORMER PROTECTION

TRANSFORMER CONNECTIONS

-Letter D is for Delta


-Letter Y is for Star
-Capital letter denotes Py
-Small letter denoteds Sy
TRANSFORMER PROTECTION

TRANSFORMER CONNECTIONS

DY11 means Py is Delta, Sy is Styar


Sy leads Py by 30 degrees

Yd1 means Py is Star, Sy is Delta


Sy lags Py by 30 degrees

Dy7 means Py is Delta, Sy is Star


Sy leads Py by 150 degrees
TRANSFORMER PROTECTION

Ratings of a Transformer

1. Power Out Put kVA / MVA


2. Primary Voltage Vp
3. Primary Current Ip
4. Secondary Voltage Vs
5. Secondary Current Is
6. Percentage Impedance Z
TRANSFORMER PROTECTION

Faults in a Transformer

1. Internal Faults
2. External faults
3. Auxiliary Faults
TRANSFORMER PROTECTION

External Faults

Transformer Internal Faults

External Faults
TRANSFORMER PROTECTION

Auxiliary Faults

- Mainly related to the Tank, Oil, etc


- Detection by Pressure Switches / Temp. Switches
- Linked with the trip circuit logic
TRANSFORMER PROTECTION

Protection Philosophy

1. Main Protection (Internal Faults)


Transformer 2. Back up Protection ( External faults)
3. Location
4. Size
TRANSFORMER PROTECTION

TRANSFORMER PROTECTION PHILOSOPHY

PRIMARY SIDE PROTECTIONS


SECONDARY SIDE PROTECTIONS
COMBINED PROTECTIONS
AUXILIARY PROTECTIONS
TRANSFORMER PROTECTION

EXTERNAL FAULTS
PRIMARY SIDE PROTECTIONS
OVER CURRENT

EARTH FAULT

UNBALANCE

THERMAL OVERLOAD

BREAKER FAILURE
TRANSFORMER PROTECTION

27 59

50 51 50N 51N

Less than 1 MVA


External Faults

50/51 IDMT Over Current


50N/51N IDMT Earth Fault
27 Under Voltage
59 Over Voltage

50 51 50N 51N
TRANSFORMER PROTECTION

27 59

50 51 50N 51N 49 46

External Faults

50/51 IDMT Over Current


50N/51N IDMT Earth Fault
27 Under Voltage
59 Over Voltage
49 Thermal Over Load
46 Current Unbalance

50 51 50N 51N
TRANSFORMER PROTECTION

27 59 24

50 51 50N 51N 49 46
More than 10 MVA
External Faults

50/51 IDMT Over Current


50N/51N IDMT Earth Fault
27 Under Voltage
59 Over Voltage
49 Thermal Over Load
46 Current Unbalance
24 Over Fluxing
50 51 50N 51N
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


OVER CURRENT / EARTH FAULT PROTECTION

LOW SET

HIGH SET

HIGHSET DOUBLING

THIRD HARMONIC FILTER


TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET

- Pick up levels 50 to 200%


- Inverse time characteristics
- Time Multiplier Setting
- Voltage Restrained O/C
- Directional O/C
- Blocking Contact
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET

Pick up setting Low set % of CT


Highset Rating

Time delay setting Definite time TMS


Setting
Inverse time
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET

Pick up settings ----- 50 % to 200 %

Time delays ……
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET

Definite Time
Trip Time delay
Inverse Time

Definite time
-Direct reading
-Setting represents time delay in sec
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET- Inverse Time

-Is not a direct reading


-Is defined by TMS setting and inverse time curve specification

-TMS setting is a number which can vary


from 0.1 to 1 in EM relays and
from 0.5 to 2 ( in steps of 0.05) in Numerical relays

-Inverse time curves are traditionally identified as :


1.3 sec curve or 3 sec curve
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET- Inverse Time

The actual time delay :


The time identity of curve selected ( like 1.3 / 3 sec)
is the time delay when the fault current is
10 times the set value provided the TMS setting =1

Acual time delay for a give fault level ( I/Is) =

TMS x Time delay as per the Curve ID at the fault level


TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET- Inverse Time

1.3 or
3.0 sec

50 msec

1.4 6 10
I/Is
LS HS
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET- Typical Inverse Times

TMS=1

I/Is=2 I/Is=4 I/Is=6 Is=8 I/Is=10 I/Is=15 I/Is=20

Normal Inv 3 sec 10.13 5.03 3.87 3.33 3 2.54 2.29

Normal Inv 1.3 sec 4.39 2.18 1.68 1.44 1.3 1.1 .99

Very Inverse 13.5 4.5 2.7 1.93 1.5 .96 .71

Extremely Inverse 26.66 5.33 2.28 1.27 0.81 0.36 0.20


TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – LOW SET

The actual time delay :


The time identity of curve selected ( like 1.3 / 3 sec)
is the time delay when the fault current is
10 times the set value provided the TMS setting =1

Acual time delay for a give fault level ( I/Is) =

TMS x Time delay as per the Curve ID at the fault level


TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – HIGH SET

- Instantaneous trip
- Time delayed high set
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – HIGH SET

High set Doubling


For Transformer feeders
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – HIGH SET

3rd Harmonic Filter for


Earth Fault circuits
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – Voltage Restrained O/C

FAULT AWAY FROM TERMINALS


(PLAIN O/C PROTECTION)

FAULT CLOSE TO TERMINALS


(VOLTAGE DEPENDENT O/C)
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – Voltage Restrained O/C

- WHEN O/C FAULT, TERMINAL VOLTAGE REDUCES.


- RELAY MAY NOT TRIP, SINCE FAULT CURRENT
THROUGH RELAY MAY BE LESS THAN SET POINT

NECESSARY TO VARY THE O/C PICK UP SETTING


WITH RESPECT TO VOLTAGE
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – Voltage Restrained O/C
VOLTAGE CONTROLLED OVER CURRENT

HAS TWO TRIP CHARACTERISTICS

THE TERMINAL VOLTAGE DECIDES


WHICH CHARCTERISTIC WILL BE
FOLLOWED BY THE RELAY WHEN
A FAULT OCCURS
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – Voltage Restrained O/C
VOLTAGE CONTROLLED OVER CURRENT

Pick up level

I>

kI >

Voltage Level
Vs >
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


O/C +E/F PROTECTION – Voltage Restrained O/C

I*/ [I>]

1.0

0.2

0.2 0.8 1.0 V/Vs


TRANSFORMER PROTECTION

Directional O/C Relay


GRID INCOMER
TRANSFORMER

REVERSE POWER RELAY


LOW FORWARD POWER RELAY
UNDER VOLTAGE RELAY
DIRECTIONAL O/C + E/F RELAY

   

dF/dT RELAY
UNDER FREQ. RELAY
DG
OVER FREQ. RELAY PLANT
VECTOR SURGE RELAY LOADS
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


UNBALANCE PROTECTION – LOW & HIGH SET

Causes for Unbalance


Effects of Unbalance
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


UNBALANCE PROTECTION

 

    

PLANT
LOADS
TRANSFORMER PROTECTION

PRIMARY SIDE PROTECTIONS


THERMAL OVERLOAD PROTECTION

1.4 6 10 I/Is
1.05 LS HS
LS
TRANSFORMER PROTECTION

EXTERNAL FAULTS
SECONDARY SIDE PROTECTIONS

OVER CURRENT

EARTH FAULT
TRANSFORMER PROTECTION

EXTERNAL FAULTS
BREAKER FAILURE PROTECTIONS

Concept of :
Starter Contact
Internal timer
Blocking time
TRANSFORMER PROTECTION

NUMERICAL RELAYS

DSP
Calculated parameters
Last Trip data – with Time stamping
Event log
Waveform Capture
RS485 Communication
Self Dignostic
TRANSFORMER PROTECTION

ADVANTAGES OF NUMERICAL RELAYS

PARAMETER NUMERIC CONVENTIONAL

ACCURACY 1% 5% / 7.5%
BURDEN < 0.5 VA > 5 VA
SETTING RANGES WIDE LIMITED
MULTI FUNCTIONALITY YES NO
SIZE SMALL LARGE
FIELD PROGRAMMABILITY YES NO
PARAMETER DISPLAY YES NO
SYSTEM FLEXILBILITY YES NO
CO-ORDINATION TOOLS MANY TWO
COMMUNICATION YES NO
REMOTE CONTROL YES NO
SPECIAL ALGORITHMS MANY LIMITED
SPECIAL PROTECTIONS YES NO
SELF DIAGNOSTICS YES NO
TRANSFORMER PROTECTION

DIS-ADVANTAGES OF NUMERIC RELAYS

SOFTWARE INTENSIVE

OBSOLESENCE RATE

EMI / EMC PROBLEMS

SERIAL NATURE
TRANSFORMER PROTECTION

RESTRICTED EARTH FAULT


PROTECTION
TRANSFORMER PROTECTION

RESTRICTED EARTH FAULT PROTECTION

REF PROTECTION IS TO DETECT


INTERNAL EARTH FAULTS IN
AC MACHINES LIKE GENERATORS &
TRANSFORMERS
TRANSFORMER PROTECTION

RESTRICTED EARTH FAULT PROTECTION

Any fault in zone A, will cause


Circulating currents within
the zone – currents will not reach
the CTs near breaker

Fault in Zone A can not be


Detected by O/C + E/F relays

Separate scheme – REF –


is necessary
TRANSFORMER PROTECTION

RESTRICTED EARTH FAULT PROTECTION

REF relay should trip for


Internal fault

REF relay should not trip


For external fault
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION

STABILISING RESISTOR FOR REF RELAYS

-CT sy impedances may not be equal


-Lead wires may not be equal
-CT errors may not be equal
-CTs may sturate differently
TRANSFORMER PROTECTION

REF PROTECTION

CALCULATION OF STABILISING RESISTOR Rst

- VALUE OF Rst SHOULD BE SUCH THAT


VOLTAGE DEVELOPED ACROSS THE RELAY
UNDER MAX THROUGH FAULT CONDITIONS,
IS INSUFFICIENT TO OPERATE THE RELAY.

- REFER THE DIAGRAM OF THROUGH FAULT


CT Y HAS SATURATED
V= If * (Rct+Rl))/N

- V SHOULD NOT CAUSE A CURRENT WHICH WILL


OPERATE RELAY
TRANSFORMER PROTECTION

COMBINED PROTECTIONS

DIFFERENTIAL

OVERFLUXING

NEUTRAL MONITORING

UNDER / OVER VOLTAGE

UNDER / OVER FREQUENCY

POWER MANAGEMENT

LOAD SHEDDING
TRANSFORMER PROTECTION

COMBINED PROTECTIONS – DIFFERENTIAL

More than 1 MVA


Internal Faults
87
87 Differential fault
64 Restricted Earth Fault
64
TRANSFORMER PROTECTION

COMBINED PROTECTIONS – DIFFERENTIAL


TRANSFORMER PROTECTION

COMBINED PROTECTIONS – DIFFERENTIAL

Should trip for an internal fault.


Trip time is always instantaneous.

Should not trip for an external fault.


TRANSFORMER PROTECTION

Differential Protection
I1
Id = Relay Pick up setting

Relay will trip if


I1 – I2 > Id
87

Notes :
I2 Under Normal conditions
(when machine is on load)
I1=I2 Id=0, Relay will not trip.
TRANSFORMER PROTECTION

Differential Protection
I1
Id = Relay Pick up setting

Relay will trip if


I1 – I2 > Id
87

Notes :
I2 Under External fault conditions
I1 = I2, Id= 0 ????????????
Relay will not trip.
TRANSFORMER PROTECTION

Differential Protection
I1
Id = Relay Pick up setting

Relay will trip if


I1 – I2 > Id
87

Notes :
I2 Under Internal fault conditions
I2=0, I1-I2 = I1, Id= IL
Relay will trip.
CT CORE CHARACTERISTIC
TRANSFORMER PROTECTION

B1
Notes :
B2
For same H,
CT1 can be at B1
B
CT2 can be at B2

H ( Proportional I1 or I2)
TRANSFORMER PROTECTION

Effect of CT Mis-match

Under an External fault ( through fault ),


Even when the primary side currents of the CTs are same,

The secondary currents I1 & I2 of the CTs will not be same


since CT1 is at B1 and CT2 is at B2

This may result in an unwanted differential current Id


and the relay will trip for a through fault.
TRANSFORMER PROTECTION

Problems of a simple differential relay

Spurious trippings at :

Inrush
Tap change
Load throw off
Through fault
TRANSFORMER PROTECTION

Characteristics of a simple differential relay

Id

0.15

Average Current I.
TRANSFORMER PROTECTION

DIFFERENTIAL

1. PERCENTAGE BIASED
2. DUAL SLOPE
3. DISPLAYS OF Id
4. VECTOR/AMPLITUDE
COMPENSATION (W/O ICTs)
5. 2ND HARMONIC RESTRAINT
6. 5TH HARMONIC RESTRAINT
7. WAVE FORM CAPTURE
8. INBUILT REF
TRANSFORMER PROTECTION

Characteristics of a simple differential relay

Id

0.15

P1 P2 Average Current I.
TRANSFORMER PROTECTION

Over Fluxing Protection


• Grid transformers
Usually only a problem during run-up or shut down, but
can be caused by loss of load / load shedding etc.
Flux   V/ f
• Generator transformers
• Effects of overfluxing :
– Increase in magnetising current
– Increase in winding temperature
– Increase in noise and vibration
– Overheating of laminations and metal parts (caused
by stray flux)
TRANSFORMER PROTECTION

Over Fluxing ….

• CAUSES
– Low frequency
– High voltage
– Geomagnetic disturbances
• EFFECTS
– Tripping of differential element (Transient overfluxing)
– Damage to transformers (Prolonged overfluxing)
TRANSFORMER PROTECTION

Over Fluxing Protection

2m

m

Ie
TRANSFORMER PROTECTION

VOLTAGE, FREQUENCY & NEUTRAL MONITORING


- Large Transformers

THREE PH O/V & U/V


THREE PH O/F & U/F
ZERO SEQUENCE VOLTAGE 2 LEVELS
OVER FLUXING 2 LEVELS
VOLTAGE UNBALANCE 2 LEVELS

VECTOR SURGE OPTION

NO NEED FOR OPEN DELTA PT


TRANSFORMER PROTECTION

NEUTRAL MONITORING - Distribution Transformers

Voltage
V>Low Set

V>High Set
Current
I>Low Set

I>High Set

Voltage Input – Neutral PT or Zero Seq. Voltage


Current Input – Neutral CT Display V & I
Max – Min Values
Time stamping
TRANSFORMER PROTECTION

DISTRIBUTION TRANSFORMER PROTECTION

1 Ph.
SEB Supply MCCB Energy
1Ph. 240 V AC Load
Meter

Contactor

Distribution
Relay
TRANSFORMER PROTECTION

Distribution relay- Features

Micro Controller Based


No settings in field
3 pick up levels
Auto Restore
Measurement Accuracy
Timing Accuracy
Expandable Platform

Suitable for domestic applications also


TRANSFORMER PROTECTION

Distribution relay- Settings

240 V Normal, No trip


270 V 75 to 85 millisec
300 V 55 to 65 millisec
400 V 35 to 45 millisec
TRANSFORMER PROTECTION

FUNCTIONS :
U/O FREQUENCY - 2 LEVELS
U/O VOLTAGE - 2 LEVELS

POWER FACTOR CONTROL - 1 LEVEL


Q/P - 1 LEVEL

FORWARD ACTIVE POWER(U/O) - 2 LEVELS


REVERSE ACTIVE POWER (U/O) - 2 LEVELS

FORWARD CAP. REACTIVE POWER(U/O) - 2 LEVELS


REVERSE CAP. REACTIVE POWER (U/O) - 2 LEVELS

FORWARD IND. REACTIVE POWER(U/O) - 2 LEVELS


REVERSE IND. REACTIVE POWER (U/O) - 2 LEVELS

MAXIMUM DEMAND RECORDINGS


BLOCKING LOGIC MATRIX
TRANSFORMER PROTECTION

Load Shedding

Time Based - Fixed or Cyclic

Based on dF/dT
TRANSFORMER PROTECTION

dF / dT Relays

Rate of Change of frequency

Concept of evaluation cycles

Logic with U/F or O/F


TRANSFORMER PROTECTION

POWER FACTOR MANAGEMENT ……

Avoid Low PF Penalty

-Use of reactors with cap. Banks


-PF Control Relay
-Selection of Cap. Banks
-CT Connections ( Loation, Polarity)
-Faulty Bank Protection
-Ave. PF Alarm
TRANSFORMER PROTECTION

AUXILIARY PROTECTIONS

TEMPERATURE

PRESSURE

LEVEL

VIBRATION

TRIP CIRCUIT SUPERVISION

PT FUSE FAILURE


TRANSFORMER PROTECTION

RECOMMENDATIONS

Less than 1 MVA O/C + E/F + O/V + U/V+REF

1 MVA to 10MVA O/C + E/f + Th. O/L + UNBAL


O/V + U/V + REF

10 MVA & ABOVE O/C + E/f + Th. O/L + UNBAL


O/V + U/V + REF+
DIFFEERENTIAL+
NEUTRAL SHIFT +
OVER FLUXING
TRANSFORMER PROTECTION

PROTECTIVE RELAYS -
RS485 COMMUNICATION
TRANSFORMER PROTECTION

RS485 Converter
RELAY /
I-Mux Unit
METER

PC System
RS 485
RS 422 HT SWITCHGEAR
MC61C /
ER300P

RS 485

LT SWITCHGEAR MV SWITCHGEAR

You might also like