N N N N: - PF Is Not Given, So Assume 0.85 and - Efficiency 88 %
N N N N: - PF Is Not Given, So Assume 0.85 and - Efficiency 88 %
Given,
Grouping Factor G = 0.8
Ambient temp. factor for 400C is t = 0.87 ( table 20)
Assuming
Thermal insulation factor T=1(no thermal insulation)
Semi enclosed fuse factor S=1(no rewirable fuse)
Tabulated current required for conductor
In new 290.61
It = = = 417.52A
GATS 0.8×0.87×1×1
OR
In new 267.36
It = = = 384.14A
GATS 0.8×0.87×1×1
40K
2
× 10 m sec
A =
762