Automation and Drives

Objectives
A&D SD Customer
Service & Support
By the end of this foil set you will be able to:
Installation Rules
- List the installation rules to minimise the effect of EMC.
EMC Practical

EMC incorrectly - Give examples of how each rule can be implemented.


Installed

- Identify good and bad EMC practice in a given installation.


Summary

20A EMC Practice.ppt A&D SD CST 08.05.20 2 of 17


Automation and Drives

EMC: The Installation Rules


A&D SD Customer
Service & Support
1. Ground all metalwork together using thick solid straps.
Installation Rules
2. Separate signal and power cables.
EMC Practical

EMC incorrectly 3. Suppress all coils, contactors, relays, solenoids etc.


Installed using RC suppressors.

4. Use shielded cable or twisted pairs where possible.


Summary
5. Avoid long cable runs or loops. Keep cables close to
grounded metalwork.

6. Ground unused cables at both ends.

20A EMC Practice.ppt A&D SD CST 08.05.20 3 of 17


Automation and Drives

Ground all Metalwork...


A&D SD Customer
Service & Support

Installation Rules
Solid Bussbar for
EMC Practical
main Ground
EMC incorrectly connection.
Installed

Short flat conductor


Summary where possible

Thick Braided ground


wire.

20A EMC Practice.ppt A&D SD CST 08.05.20 4 of 17


Automation and Drives

Ground all Metalwork...


A&D SD Customer
Service & Support

Installation Rules

EMC Practical
Thick Braided ground
wire for grounding of
EMC incorrectly door.
Installed

Summary
Solid Bussbar for
main Ground
connection - connects
between cubicles.

20A EMC Practice.ppt A&D SD CST 08.05.20 5 of 17


Automation and Drives

Separate Signal and Power Cables...


A&D SD Customer
Service & Support

Installation Rules

EMC Practical Signal cables


are screened
EMC incorrectly
Installed
and separated
from other wiring

Summary

20A EMC Practice.ppt A&D SD CST 08.05.20 6 of 17


Automation and Drives

Suppress all Coils


A&D SD Customer
Service & Support

Installation Rules

EMC Practical

EMC incorrectly
Suppress all
Installed contactors
/relays etc using
Varistors, Diodes
Summary
or (best) RC
networks

20A EMC Practice.ppt A&D SD CST 08.05.20 7 of 17


Automation and Drives

Use Shielded Cables or Twisted Pairs...


A&D SD Customer
Service & Support

Installation Rules
Ground cable shields at both ends
EMC Practical

EMC incorrectly
Installed

Summary

20A EMC Practice.ppt A&D SD CST 08.05.20 8 of 17


Automation and Drives

EMC: How to do it
A&D SD Customer
Service & Support

Installation Rules

EMC Practical + Good Groundplane


EMC incorrectly
+ Screened control cables.
Installed

+ Input Choke
Summary
- No separation of input,
output, or signal cables.

- No filter.

20A EMC Practice.ppt A&D SD CST 08.05.20 9 of 17


Automation and Drives

EMC: How to do it
A&D SD Customer
Service & Support + Good Groundplane + Suppressed contactors

Installation Rules

EMC Practical

EMC incorrectly
Installed

Summary

+ Screened control cables.

- No separation of input, output, or signal cables.

20A EMC Practice.ppt A&D SD CST 08.05.20 10 of 17


Automation and Drives

EMC: How to do it
A&D SD Customer
Service & Support

Installation Rules

EMC Practical + Screened PROFIBUS cable


crossing at right angles
EMC incorrectly
Installed + Screened input and output
power cables.
Summary
+ Output Chokes (Long Cables)

+ EMC Filter well grounded to


metal backplane.

- Supply and motor cables


together.

20A EMC Practice.ppt A&D SD CST 08.05.20 11 of 17


Automation and Drives

EMC: How to do it
A&D SD Customer
Service & Support

Installation Rules
+ Input Chokes
EMC Practical

EMC incorrectly
+ Separate
Installed PROFI wiring

Summary

Braking
Resistors

20A EMC Practice.ppt A&D SD CST 08.05.20 12 of 17


Automation and Drives

EMC: How not to do it


A&D SD Customer
Service & Support

Installation Rules

EMC Practical
The filter is achieving very
EMC incorrectly
Installed
little because of poor
grounding and because
cables can cross couple
Summary around it.

Zoning is non existent.

Wires are crossing, clear of


the metalwork and tied
together to encourage
radiated EMI

20A EMC Practice.ppt A&D SD CST 08.05.20 13 of 17


Automation and Drives

EMC: How not to do it


A&D SD Customer
Service & Support

Installation Rules
- Mixed power and
EMC Practical signal wiring.
EMC incorrectly - All cables
Installed
unscreened.

Summary - Unsuppressed
contactor and relay
coils.

- Braking resistor
wiring!

20A EMC Practice.ppt A&D SD CST 08.05.20 14 of 17


Automation and Drives

EMC: How not to do it


A&D SD Customer
Service & Support

Installation Rules

EMC Practical

EMC incorrectly
Installed

Summary - Test
Equipment

- Contactor in screened output lead causes failure of EMC tests


(flights, hotel costs two man/days…..)
20A EMC Practice.ppt A&D SD CST 08.05.20 15 of 17
Automation and Drives

EMC: To Summarise
A&D SD Customer
Service & Support

 Plan the installation with EMC in Mind


Installation Rules

EMC Practical  Segregate the different components screen into different Zones
Consider using cabinets etc with built in screening.
EMC incorrectly
Installed
 Segregate Motor cables from signal cables.
Screen analogue and digital cables at each end.
Summary De-couple if necessary.

 Equipotential bonding for high frequency currents.


Thick flat braided bonding cables.

 Remember - Prevention is better - and cheaper - than cure.

20A EMC Practice.ppt A&D SD CST 08.05.20 16 of 17


Automation and Drives

A&D SD Customer
Service & Support
Siemens AG
Installation Rules
Standard Drives
EMC Practical

EMC incorrectly
Installed
Martin Brown
Summary A&D SD CS Congleton

20A EMC Practice.ppt A&D SD CST 08.05.20 17 of 17

You might also like