Transient Response and Steady-State Response: Week 5 Session 1

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 20

Transient Response and Steady-

State Response
Week 5 Session 1
Introduction
• Time response of control system consist of
transient response and steady state response
• Transient response: the response from initial
state to the final state
• Steady-state response: the response of the
system as the time approaches infinity
Roadmap of Control System
Modeling Analysis Design

Laplace Time Response


Transform • Transient
Transfer Function • Steady state
Design Spec
Model for Stability Root Locus
systems • Routh-Hurwitz Frequency domain
• Electrical • Nyquist PID & Lead-lag
• Mechanical Design examples
Frequency
Blocks Diagram Response
Linearization • Bode Plot
Time response analysis
• Standard test signals
• First order systems
• Second order systems
• High order systems
Standard Test Signals
• The characteristics of actual input signals are a sudden
shock, a sudden change, a constant velocity, and constant
acceleration.

• The dynamic behavior of a system is therefore judged and


compared under application of standard test signals – an
impulse, a step, a constant velocity, and constant
acceleration.

• Another standard signal of great importance is a sinusoidal


signal.
Standard Test Signals
• Impulse signal
– The impulse signal imitate the
sudden shock characteristic of
actual input signal. δ(t)

A t0 A
 (t )  
0 t0
0 t

– If A=1, the impulse signal is


called unit impulse signal.
Standard Test Signals
• Impulse signal
Standard Test Signals
• Step signal
– The step signal imitate
the sudden change u(t)

characteristic of actual
input signal. A

A t0
u( t )   0 t

0 t0

– If A=1, the step signal is


called unit step signal
Standard Test Signals
r(t)
• Ramp signal
– The ramp signal imitate
the constant velocity
characteristic of actual
t
input signal. 0

r(t)
 At t0
r (t )  
0 t0 ramp signal with slope A

r(t)

– If A=1, the ramp signal is unit ramp signal


called unit ramp signal
Standard Test Signals
• Parabolic signal
– The parabolic signal imitate
the constant acceleration
characteristic of actual p(t)
input signal.

 At 2
 t0
p( t )   2
0 t0 t
 0

– If A=1, the parabolic signal


is called unit parabolic
signal.
Relation between standard Test Signals
A t0
• Impulse  (t )  
0 t0
d
 dt
A t0
• Step u( t )  
t0 d
0
 dt
 At t0
• Ramp r(t )  
0 t0 d
 dt
 At 2
• Parabolic 
p( t )   2
t0
0 t0

Laplace Transform of Test Signals

• Impulse
A t0
 (t )  
0 t0

L{ (t )}   ( s )  A

• Step
A t0
u( t )  
0 t0

A
L{u(t )}  U ( s ) 
S
Laplace Transform of Test Signals

• Ramp  At t0
r (t )  
0 t0

A
L{r (t )}  R( s )  2
s
• Parabolic  At 2
 t0
p(t )   2
0 t0

2A
L{ p(t )}  P( s )  3
S
Time Response of Control Systems
• Time response of a dynamic system is response to an input
expressed as a function of time.

System

• The time response of any system has two components


• Transient response
• Steady-state response.
Time Response of Control Systems
• When the response of the system is changed form rest or
equilibrium it takes some time to settle down.

• Transient response is the response of a system from rest or


equilibrium to steady state. 
-3
x 10 Step Response
6

Step Input
• The response of the 5

Steady State Response


system after the transient 4
Response
response is called steady
Amplitude

state response. 2
Transient Response
1

0
0 2 4 6 8 10 12 14 16 18 20
Time (sec)
Time Response of Control Systems
• Transient response dependents upon the system poles only and
not on the type of input.

• It is therefore sufficient to analyze the transient response using a


step input.

• The steady-state response depends on system dynamics and the


input quantity.

• It is then examined using different test signals by final value


theorem.
First-Order System
General form:
C (s) K
G ( s)  
R( s) s  1

Unit-step response:
 1  K 
C ( s )    
 s  s  1 
A B
 
s s  1

B t 
c(t )  A  e

First-Order System
 Transient Response: Gradual change of output from
initial to the desired condition.

Block diagram representation:

K : Gain
 : Time constant

 By definition itself, the input to the system should be a


step function which is given by the following:
First-Order System
Consider the impulse, step, ramp responses computed
earlier. Identify the steady state and the transient parts.
C ( s) 1T
G ( s)   , T 0
R( s) s  1 T
Time domain output response for impulse signal,
step signal and ramp signal input:
1 t T
r (t )   (t ), R( s)  1, c (t )  e 1(t )
T
1
r (t )  1(t ), R( s )  , cstep (t )  1  e  1(t )
 t T

s
1
r (t )  t1(t ), R( s )  2 , cramp (t )  t  T  Te  t T  1(t )
s
Compare steady-state part to input function, transient part to TF.
Second-Order System
Second-order system standard form
C (s) n2
G(s)   2
R( s ) s  2n s  n2
Dynamic behavior of the second order system can be described
in terms of two parameters ζ and ωn
Over damped
•(two real distinct roots = two 1st order systems with real poles)
•ζ>1
Critically damped
•(a single pole of multiplicity two, highly unlikely, requires exact matching)
•ζ=1
Underdamped
•(complex conjugate pair of poles, oscillatory behavior, most common)
•0<ζ<1