DTP

Digital Transformer Protection


Protective Functions
• Digital 3-Phase Current Differential Protection
• 16 Samples/Cycle Protection & Oscillography
• 2, 3, 4 Restraint Windings
• Current Taps Adjustable From (0..5 - 10) * In, 0..01 Steps)
• 2nd & 5th Harmonic Cross-Restraint (12 - 50%,, 0..1 Steps)
• Through Current Percentage Restraint (15 - 50%,, 0..1 Steps)
• Instantaneous Overcurrent Backup Unit (6 - 12 tap,, 0..1
Steps)
• 1 Setting Group
Features
• Any Transformer Type
Wye, B Delta, C Delta, B Zig-Zag, C Zig-Zag

• Any CT Connection
Wye, B Delta, C Delta

• Choice of Internal or External Compensation


Internal Phase Shift Correction To Eliminate Zero Sequence
Components of Currents
Features
• Trip Outputs (5)
(User Selects Which Trip Signals Operate All 5 Outputs)

– Phase A Differential Trip


– Phase B Differential Trip
– Phase C Differential Trip
– Phase A Instantaneous Trip
– Phase B Instantaneous Trip
– Phase C Instantaneous Trip
– Buchholz Trip Digital Input
– Over temperature Trip Digital Input
Features
• Digital Inputs (5)

– Buchholz Alarm & Trip


– Over temperature Alarm & Trip
– Latching Relay Reset (Lockout Relay NC Contact)

• Auxiliary Outputs (7)

– Phase A, B or C Instantaneous Signaling


– Phase A Diff. or Inst. Signaling
– Phase B Diff. or Inst. Signaling
– Phase C Diff. or Inst. Signaling
– Buchholz Alarm Signaling
– Over temperature Alarm Signaling
– Trip Signaling
Features
• Sequence of Event Recorder (255)
– User Can Select Which Events Will Be Recorded

• Present Value Monitoring


– Phase A, B, C Differential Currents
– Phase A, B, C Through Currents

• Maximum Phase A RMS Through-Current Recorded


– One Hour Interval for Seven Days

• Self-Test Diagnostics with Alarm Contact


– Critical & Non-Critical Alarms

• Events and Current Logs are Maintained for Two Days after Loss of DC Power
Event Masks
– Phase A Instantaneous Pick-up – Buchholz Alarm Signaling
– Phase B Instantaneous Pick-up – Overtemperature Alarm Signaling
– Phase C Instantaneous Pick-up – Trip
– Phase A Differential Pick-up – Auxiliary Trip Signal
– Phase B Differential Pick-up – Non-Critical Alarm 101
– Phase C Differential Pick-up – End of Non-Critical Alarm 101
– Overtemperature Trip Input – Setting Change
– Overtemperature Alarm Input – Program Reset
– Buchholz Trip Input – Critical Alarm 204
– Buchholz Alarm Input – Critical Alarm 201
– Latching Relay Reset Input – End of Critical Alarm
– Phase A, B, or C Instantaneous Signaling – Clear Event File
– Phase A Instantaneous or Differential Signaling – Relay Synchronize
– Phase B Instantaneous or Differential Signaling
– Phase C Instantaneous or Differential Signaling
Features
• Eight Fault Reports Stored:

– RMS Differential Current


– RMS Through Current
– RMS Harmonic Restraint (2nd & 5th)
– Trip Type
– Fault Type
– Date and Time
– Settings in effect at time of fault
Features
Communications
• 2 Line LED Display
• Local Keypad
• Present Values Viewed on Display by Pressing “ENT” Key
• Programmable Banks of Indicating LED’s
– Pick-ups, Inputs, Outputs, LED Test
• Ready LED
• Remote Communication via M -LIINK Software
– Display Present Values, Fault Report, Retrieve Oscillography,
• Retrieve Sequence of Events, Change Settings
– Password Protected
– Real-Time Monitoring of Differential & Through Currents
• Rear RS232 or Fiber Optic Remote Communication
Packing

– 19” Rack Unit


– Horizontal Mounting (4 RU)
– Modular Construction
– Optional Built-in Test Blocks
– Optional Oscillography
– Choice of Input Contact Converter DC Supply Voltage
TR 230/66kV
Parameter Settings
PARAMETER UNIT RANGE DEFAULT STEP SETTING

1st Winding CT RATIO   1-4000 1 1 400

2nd Winding CT RATIO   1-4000 1 1 240

1st Winding Tap In 0.5-20 1 0.01 0.78

2nd Winding Tap In 0.5-20 1 0.01 0.91

1st Winding Configuration   Y, D, ZZ Y N/A Y

2nd Winding Configuration   Y, D, ZZ Y N/A D

2nd Winding time group   0-11 0 1 11

1st Winding CT Config   Y0,Y6,D1,D5,D7,D11 Y0 N/A Y0

2nd Winding CT Config   Y0,Y6,D1,D5,D7,D11 Y0 N/A Y0

Sensitivity Itap 0.2-0.4 0.3 0.01 0.3

K1-K2 Inflexion Itap 0-10 5 0.01 2.5

K1 percentage restraint % 15-100 30 0.01 25

K2 percentage restraint % 15-100 30 0.01 70

2nd harmonic restraint % 12-100 100 0.01 20

5th harmonic restraint % 12-100 100 0.01 20

87B tap Itap 4-12 8 0.01 12


Ordering