Outdoor Eltek Commissioning Guide

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 52

Outdoor Eltek Rectifier Commissioning

Guide
General Objectives

To be familiarize into Eltek Commissioning


Set properly the standard parameters
Activate some features incorporated into Eltek
rectifier system
Tools Needed

 Laptop
 PowerSuite software
 LAN cable
Accessing Eltek Rectifier System
Access via LAN cable
 Set Laptop IP Address into 192.168.10.21/24

Open Web Browser


 Type on the URL; 192.168.10.20
Accessing Eltek Rectifier System
Enter needed parameters
 UN & PW: admin
Accessing Eltek Rectifier System
Successfully Connected
Accessing Eltek Rectifier System
Activating Parameters for PowerSuite connection
 Click System Conf
Accessing Eltek Rectifier System
Activating Parameters for PowerSuite connection
 Click Device Settings
Accessing Eltek Rectifier System
Activating Parameters for PowerSuite connection
 Click TCP/IP Security
 Check the needed set up
Accessing Eltek Rectifier System
Open PowerSuite software
Accessing Eltek Rectifier System
Click Connect Button
Accessing Eltek Rectifier System
Choose Network
 Set the need parameters
Accessing Eltek Rectifier System
Select Log In
 Type 3 as password
Accessing Eltek Rectifier System
Successfully Connected
Commissioning Proper: System Voltage Levels
Click System Voltage Levels
Commissioning Proper: System Voltage Levels
Set the following
 Reference: 2.25*
 Boost: 2.35*
 Rectifier Standby: 1.85
 Battery Disconnect: 1.8
 Battery Reconnect: 1.9666
 Rectifier OSV limit: 2.4583

*-depends on the battery specs


Commissioning Proper: Alarms Overview
Click Alarms Overview
Commissioning Proper: Alarms Overview
Defined the Alarms that need to be monitor
Commissioning Proper: Alarms Overview
 Set the Alarms into their specific Alarm output number
 Battery High Voltage: Alarm Output 81.1
 Rectifier Failure: Alarm Output 81.2
 Mains Fail: Alarm Output 81.3
 Battery Low Voltage: Alarm Output 81.4
 Load MCB Fail: Alarm Output 81.5
 Battery MCB Fail: Alarm Output 81.5
 High Temperature: Alarm Output 81.6
 Symmetry Fault: Alarm Output 81.6
Commissioning Proper: Power System
Click Power System
 Modify:
Site Name: 552 San
Fernando 2 Rectifier #
Responsible: name of
personnel
Commissioning Proper: Mains
Click Mains
 Number of Phases: 2
Commissioning Proper: Mains
Click MainsPhase 1
 Click MainsVolt 1
Commissioning Proper: Mains
Set the following
 Check Enable
 Major High: 270
 Minor High: 270
 Minor High: 185
 Major High: 185
 Alarm Group: Mains Fail
 Apply then Ok
Commissioning Proper: Mains
Click MainsPhase 2
 Click MainsVolt 2
Commissioning Proper: Mains
Set the following
 Check Enable
 Major High: 270
 Minor High: 270
 Minor High: 185
 Major High: 185
 Alarm Group: Mains Fail
 Apply then Ok
Commissioning Proper: Rectifier
Click Rectifier
 Click Rectifier Error
Commissioning Proper: Rectifier
Set the following
 Check Enable
 Major alarm: 1
 Minor alarm: 1
 Alarm Group: Rectifier Alarm
 Apply then Ok
Commissioning Proper: Rectifier
Click Rectifier
 Click Rectifier Comm Error
Commissioning Proper: Rectifier
Set the following
 Check Enable
 Major alarm: 1
 Minor alarm: 1
 Alarm Group: Crict Rect Alarm
 Apply then Ok
Commissioning Proper: Rectifier
Click the Configuration Tab
 Number of rectifiers: x
 Check the Suppress..
 Walk in time: Long time
 OSV limit: 2.4583
 Apply then Ok
Commissioning Proper: Rectifier
Click the Efficiency Tab
 Enable efficiency manager
 Rectifier-off delay: 10
 Shuffle time: 2
 Apply then Ok
Commissioning Proper: Load
Click LoadBank 1
 Click LoadFuse 1
Commissioning Proper: Load
Set the following:
 Click Enable
 Alarm Group: Load MCB Fail
 Apply then Ok
Commissioning Proper: Battery
Click Battery
 Click Status Tab
 Click Battery Voltage
Commissioning Proper: Battery
Set the following
 Click Enable
 Major High: 57
 Minor High: 57
 Alarm Group: High Voltage
 Minor Low: 48
 Major Low: 48
 Alarm Group: Low Voltage
 Apply then Ok
Commissioning Proper: Battery
Click Battery
 Click Status Tab
 Click Battery Temp
Commissioning Proper: Battery
Set the following
 Click Enable
 Major High: 40 (35*)
 Minor High: 35 (30*)
 Alarm Group: High Temp
 Apply then Ok

*-for indoor type


Commissioning Proper: Battery
Click Battery
 Click Status Tab
 Click LVBD
Commissioning Proper: Battery
Set the following
 Click Enable
 Disconnect Voltage: 43.2
 Reconnect Voltage: 47.2
 Apply then Ok
Commissioning Proper: Battery
Click Battery
 Click Configuration Tab
 Number of banks: 1
 Number of Strings: 4
 Description:
 Capacity AH: 150
Commissioning Proper: Battery
Click Battery
 Enable Temp comp
 Reference voltage: 2.25
 Reference temp: 25
 Temp slope: 3*
 Min comp voltage: 2.1*
 Max comp voltage: 2.35*

*-depends on battery specs


Commissioning Proper: Battery
Click Battery
 Click Current Limitation
 Enable Current Limitation
 Enable string current limit
 Set Current Limit: 60*
 Apply then Ok

*-current limit always 10%


of total battery capacity
Commissioning Proper: Battery
Click Battery
 Click Test Tab
 Click Interval test
 Click Enable
 Next start date: yyyy-mm-dd
 Next start time: HH:MM
 Interval period: 90*

*-one quarter cycle period


Commissioning Proper: Battery
Click Currents
 Click BattCurrent1.1
Commissioning Proper: Battery
Click General Tab
 Click Enable
 Apply then Ok
Commissioning Proper: Battery
Click Fuses
 Click BattFuse1.1
Commissioning Proper: Battery
Click General Tab
 Click Enable
 Alarm group: Battery
MCB Fail
 Apply then Ok
Commissioning Proper: Battery
Click Temperatures
 Click BatteryTemp1.1 (only BatteryTemp1.1 will
be configure)
Commissioning Proper: Battery
Click General Tab
 Click Enable
 Major High: 40
 Minor High: 35
 Alarm group: High
Temperature
 Apply then Ok
Commissioning Proper: Battery
Click BattMonStr.1
 Configure all BattMonSym1.1 to 1.4
 Repeat process for BattMonStr.2 to 4
Commissioning Proper: Battery
Click General Tab
 Click Enable
 Major alarm: 1.5
 Minor alarm: 1.5
 Alarm group: Symmetry
Fault
 Apply then Ok
Repeat process for 1.2 to
1.4
THANK YOU!!!