Generator Room Proposal

Presented By: Muhammad Ansar AM (Engineering)


Current Generator Room Layout
Drawbacks of current Generator Room Design

 Most of the area of generator room is not covered.


 The height of the roof is not enough for the ventilation.
 The space between 275kva CAT generator and 500KVA CAT generator is
not enough.
 The heat generated by generator is the air inlet to the other generator.
 There is no proper ventilation for the fresh air inlet to the generator and
hot air from the radiators of the generator.
 The generator room is very congested and the sound canopy did not allow
the heat generated to maintain the cool environment.
IMPACTS of current Generator Room Design

 The temperature of the generators gets high in very little time.


 Breakdown occurs often.
 The life expectancy of the generator reduces.
 Efficiency of the generator reduces (Fuel , Power).
 Waste of water for cooling purpose.
 Life expectancy of radiator reduces.
 In case of emergency, heavy parts cannot be pulled out.
Proposed Design
 Fresh air should enter the generator room through
exhaust fans.
 Current design need more air to be enter to make

the environment around the generator cool.


 Height of the room must be increased.
 Generator room must be covered from top.
 Canopy must be removed.
 Ventilation of air from radiators must be improved.
500kva Generator Air Flow

Total Air Flow needed

690 cubic meter/min


Images of a good design
Ventilation for Generator Room
Cooling Tower System For Engine Cooling