BMS Training Note

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 23

BMS Training

Date: April 17-2015


Agenda
 System Configuration
 Agilent & Tem Sensors Configuration
 Items controlled/monitored by BMS system
 Chiller System Training & Other Equipment/System Controls &
Monitoring
 Log in system/Web Access
 Set Time Schedule
 BMS Trending
 SMS paging
System Configuration
Lift Server (CMO, Level 6)
BMS Workstation (FCC) SMS Modem

EMS
IBMS Server

IBMS Server

BMS Network

Agilent Data Logger


10/100 Mb IP Switch

NCE

NAE 35

NAE 45 NAE 35
NAE 55
NAEs Serving B3 to 17sty
And Roof

E-Link

Chiller Interface
DDC (PAHU, AHU, FCU, MVFAN)
PM
PM
DDC (CHWP,CWP, Cooling Tower) PM
DDC (ELECTRICAL, P&S)
Bacnet Power Meter
Modbus Power Meter

BTU / Flow Meter


VAV
BMS NETWORKLINK -
SEVER,OWS, SW ON
ICT NETWORK

ICT Network
Jem IBMS Server-1

BMS SWITCHES

FROM network controllers and


field controller

BMS Workstation (FCC)

IBMS Server-2
Agilent & Tem Sensors Config
uration
Chiller System Training
Agenda
1.. Chiller Plant Configuration

2. Chiller System Overview

3. Chiller System Controls Strategies

4. Chiller Operation

5. Q & A Session
Chiller Plant
Configuration
Chiller System
Schematic
CT Grouping CT Grouping
Set A Set B

CT-1 =2380 HRT CT-4 = 714 HRT


CT-2 = 2856 HRT CT-5 = 714 HRT
CT-3 + CT4 = 2380 HRT
CT-3 + CT5 = 2380 HRT
Chiller System
Control
Strategies
Cooling Tower VSD Controls
Calculation of Wet Bulb temperature based on OA
Dry Bulb Temperature and RH
Condenser water supply setpoint = actual wetbulb + 2.4 deg C
Max setpoint is set at 29 C
Respective cooling towers supply temperature
Compares against setpoint to control VSD speed

Minimum VSD is set at 20 Hz

In the event Condenser water supply temperature


Drops less than 27 deg C after a delay cooling tower VSDs
Will be set to 0 Hz

All fans will be stopped but inlet and outlet valves will remain
OPEN
Condenser Pump Controls

Condenser pumps speed is set for constant design flow to the Chiller

Chilled Water Pump Controls

LT and HT system have its own DP sensors

LT DP is at
AHU B1-3
AHU B3-1
PAHU 17-3

HT DP is at
PAHU 5-4
PAHU 17-3
Chiller Controls

LT System

Stage 1 - 2 x1000 RT Chiller (SCF)


Stage 2- 4 x 1000 RT Chiller (SCF)

ACS-LTCH-L5-1/4 ( 9 to 13.5 C) & ACS-LTCH-L5-2/4 Lead ( 13.5 to 18 C)


ACS-LTCH-L5-3/4 ( 9 to 13.5 C) & ACS-LTCH-L5-4/4 Lead ( 13.5 to 18 C)

In the event ACS-LTCH-L5-2/4 or ACS-LTCH-L5-4/4 is required to run


by itself the Leaving Chilled water setpoint is changed to 9 C automatically.

The system can be programmed to to run 1 x 1000 RT LT chiller.


During this operation the other SCF chiller will be stopped but
The condenser and chilled water MV will be OPENED for chilled water
And conndeser water to flow through.
HT System

Stage 1 - 1 x 500 RT Chiller ( 15 to 20 C)


Stage 2 - 1 x 1000 RT Chiller ( 15 to 20 C)
Stage 3 - 1 x 1000 RT + 1 x 500 RT Chiller ( 15 to 20 C)

When Both HT and LT system is in operation


MV-CHW-BP 9 AND BP10 is CLOSED

When LT system if OFF and HT is serving LT area


MV-CHW-BP 9 AND BP10 is OPENED

When HT is serving LT area, the chw Leaving setpt is set at 9 C


Other Equipment/System Controls &
Monitoring
 PAHU
 AHU(Mall), AHU(Office)
 FCU(1ph, 3ph)
 MV Fans-

-TEAF
-CEAF&CFAF
- KEAF&KFAF
-PEAF,EAF& FAF
- ST Fans
- SSL Fans
Other Equipment/System Controls &
Monitoring
 Heat Recovery Wheel
 Filtration System
 Condensate Water Recovery
 P&S
 Electrical System
 Fire System
 Vertical Transportation System