IBMS Control Schematic

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 57

IBMS CONTROL

SCHEMATICS
CONTENT
 CHILLER SYSTEM
 HEAT EXCHANGER
 PAHU
 AHU-VAV
 AHU-VAV (F&B AND RETAIL TENANT)
 DX AHU-VAV - RAMP TOWER
 AHU-CAV
 AHU-CAV WITH DIRECT FRESH AIR
 AHU-CAV – RESTAURANTS
 SC AHU
 MTB CHW FCU
 MTB CHW FCU WITH FRESH AIR INTAKE
 MTB CHW FCU+VRV FCU FOR CRITICAL/ELECTRICAL
ROOM
CONTENT
 CHW FCU+VFCU FOR TRANSFORMER ROOM
 VFCU+VFCU FOR TRANSFORMER ROOM
 VFCU FOR CRITICAL/ELECTRICAL ROOM AT RT
 CAR PARK JET FAN
 EQUIPMENT ROOM VENTILATION FAN
 TRANSFORMER SPARE ROOM FRESH AIR FAN
 EXHAUST AIR FAN FOR FM200 SYSTEM
 STAIRCASE FAN-NORMAL
 STAIRCASE FAN AT RAMP TOWER WITH AIR
PRESSURE DIFFERENTIAL SENSORS
 STAIRCASE FAN(LEADING TO BASEMENT
CORRIDOR)WITH AIR PRESSURE DIFFERENTIAL
SENSORS
 FFL,SSL,PWD LOBBY FAN
CONTENT
 CRAC UNIT
 SMOKE CONTROL SYSTEM
 FIRE PROTECTION SYSTEM AND FIRE ALARM SYSTEM
 IRRIGATION SYSTEM/IRRIGATION FOGGING SYSTEM
 DOMESTIC WATER SYSTEM
 NEW WATER SYSTEM
 CT MAKE UP SYSTEM
 SUMP PITS WITH PUMP
 GREASE EJECTOR PUMP/EJECTOR SYSTEM
 PNEUMATIC WASTE PUMPS
 VERTICAL TRANSPORTATION SYSTEM
 PASSENGER LOADING BRIDGE SYSTEM
 AIRCRAFT DOCKING GUIDANCE SYSTEM
CONTENT
 MASTER CLOCK SYSTEM
 FLIGHT INFORMATION DISPLAY SYSTEM
 LIGHTING CONTROL MANAGESYSTEM
 ENERGY MANAGEMENT SYSTEM
 HT SYSTEM
 LT SYSTEM(LV MSB, SDB,DB)
 LT SYSTEM(CHECK IN COUNTER DB, FINAL DB)
 GENERATOR WITH FUEL SYSTEM
 UPS WITH DC BATTERY BANK SYSTEM
 DATA CENTER MONITORING SYSTEM
Legend
• VAV - Variable Air Volume
• T - Thermostat
• FM - Flow Meter
• IAT - Inlet Air Temperature Sensor
• SAT- Supply Air Temperature Sensor
• M- Modulating Valve with Actuator
• DDC- Direct Digital Controller
• SP- Air/Water Static Pressure Sensor
• CHWST - Chilled Water Supply Temperature Sensor
• CHWRT- Chilled Water Return Temperature Sensor
• CO2- Carbon Dioxide Sensor
• CO Carbon Monoxide Sensor
• MDA- Fresh Air Motorized Damper Actuator
• FSW- Filter Switch
• RH – Humidity Sensor
• RH/T- Humidity + Temperature Sensor
• R/S Tem- Room Space Temperature
• SD- Smoke Detector
• MD- Modulating Damper with Actuator
• CONTROL LOOP
• CABLE FROM DDC TO ITB IS BY IBMS - LOW LEVEL INTERFACE
• (FOR ACMV, CABLE FROM SENSORS TO DDC IS BY IBMS; AND FOR OTHER
• SERVICES, CABLE FROM SENSORS/CONTACTS TO ITB IS BY M&E SUBCON)
• CABLE BY IBMS (HIGH LEVEL INTERFACE)
• CABLE BY VARIOUS M&E SUBCONS
• ACMV SENSORS BY IBMS (CONNECTED TO DDC PANEL)
(All OTHER SERSORS OR EQUIPMENT ARE BY M&E SUBCONS, ITB IS ALSO BY M&E SUBCONS)
CHILLER PLANT OPTIMIZATION
PROPOSED NETWORK ARCHITECTURE
(HIGH LEVEL INTERFACE WITH IBMS)
IBMS core switch IBMS WORKSTATION

i-Vu BAS Panel


MPC-OPN-XP
Chillers
CHWP IBMS Distribution switch
CWP

Flow Temp
Meter Sensor MS/TP Bus
Link IP Cat-6 HIGH LEVEL
i-Vu Pro Server
IP Cat-6
PSM
IBMS End switch

DAQ
IP Cat-6
IP Cat-6

IP Cat-6
GWY
Chillers
Variable Speed
i-Vu BAS Drive
Panel
Link
Digital Power Meter VSD
MS/TP
Bus

Temp DPM CCN Bus


Flow RS-485
Sensor
Meter VSD
DPM MPC-OPN-
XP
Cooling
Towers VSD
DPM

DPM VSD
IBMS Control Schematic (CHILLER SYSTEM)

Note : Below system are included


under Chiller Optimization

-Water Cooled Chiller


-Cooling Tower
-Primary Chilled Water Pumps
-CW Pumps
-Condenser Water Filter System
-CHW,CW Header
-Cooling Tower Make Up Tank and Feed
-Condenser Water Treatment
-Chilled Water Treatment
-Cooling Tower Filtration System
IBMS Control Schematic (HEAT EXCHANGER proposed by AST)

DDC

PRIMARY CHW ITB


SECONDARY CHW
CIRCUIT CIRCUIT

VSD DELTA-P

T T P
CHWS
HEAT
EXCHANGER
T M VSD T P
CHWR
FM FM

BP
IBMS Control Schematic (HEAT EXCHANGER proposed by AST)

1) Secondary circuit control

a) If the heat load in the control space increased, the motorized damper
will open to allow more CHW flow

b) SCHWS line pressure will decrease and signal the VSD to increase pump
speed to increase the SCHWS line pressure

c) If the FCU motorized valve is fully open, and heat load is still high,
the SCHWR temperature will go above the set point

d) The increased in the SCHWR temperature above set point will open the
PCHWS motorized valve to increase the primary flow into the heat exchanger
to bring down the SCHWS temperature

e) The process is reverse if heat load decreased.

2) Primary circuit control

a) On top of being able to regulate the PCHW flow based on the temperature
feedback of SCHW, the PCHW flow also could be regulated by the PCHWR
temperature

b) If PCHWR temperature is higher than the set point, this indicate the
secondary circuit CHW temperature had been increased due to high head load

c) The motorized valve at the PCHWR line could be opened to allow more CHW
flow to meet the load requirements.
IBMS Control Schematic (PAHU) DDC
LMCP
FROM LMCP/TO
DDC
ITB
LOW LEVEL

SAT
IAT VSD
SP AT 2/3 OF MAIN DUCT
SP

COOLING COIL
Outdoor Air

AHU FILTER
TO AHU
EAC UV MDA
LIGHT
TO AHU
FSW MDA

TO AHU

M
MDA
TO DDC

CHWRT
CHWST
T

TO AHU
T
HIGH LEVEL
MDA
F

FM MDA
BTU
TO AHU
IBMS Control Schematic (AHU-VAV- OFFICE AREA)

LOW LEVEL

RA LMCP

LOW LEVEL
DDC

SD
ITB

CO2

RH
FROM LMCP/TO
DDC
IAT
VSD
SAT

COOLING COIL
Pre-cooled FA

AHU FILTER
SP AT 2/3 OF MAIN DUCT

EAC UV
LIGHT
MDA FSW
SP

M
TO DDC

CHWRT
CHWST
T

T
F HIGH LEVEL

FM
BTU
VAV VAV VAV

T T T
IBMS Control Schematic (AHU-VAV FOR F&B and RETAIL TENANT)
DDC
RA LMCP

LOW LEVEL

SD
ITB

FROM LMCP/TO DDC

CO2

RH
IAT VSD SAT

COOLING COIL
AHU FILTER
Pre-cooled FA

EAC
UV
LIGHT
SP AT 2/3 OF MAIN DUCT
MDA FSW
SP

M
HIGH LEVEL
TO DDC

CHWRT
CHWST
T

T
F

FM
BTU
DA DA DA

VAV VAV VAV

T T T
IBMS Control Schematic (DX AHU- VAV-RAMP TOWER)

LMCP
RA

LOW LEVEL
ITB DDC

SD
CO2
FROM LMCP/TO DDC
IAT VSD SP about 2/3 OF MAIN
SAT
DUCT
Direct Fresh Air SP

AHU FILTER
Intake

REF COIL
EAC
UV
LIGHT
MDA
FSW

TO LMCP

RH/T
VAV VAV VAV

CU

T T T
IBMS Control Schematic (AHU-CAV)

RA LOW LEVEL
LMCP

ITB
LOW LEVEL DDC

CO2

SD
FROM LMCP/TO DDC

IAT VSD SAT

Pre-cooled FA

COOLING COIL
AHU FILTER
EAC
UV
LIGHT

MDA FSW

CHWRT
CHWST

TO DDC
T

T
HIGH LEVEL
F

SPACE RH/TEMP
FM SENSOR
BTU

TO DDC
IBMS Control Schematic (AHU-CAV WITH DIRECT FRESH AIR)

RA LOW LEVEL
LMCP

LOW LEVEL
ITB
DDC
FROM/TO DDC

CO2

SD
IAT VSD SAT

Direct Fresh Air

COOLING COIL
AHU FILTER
Intake
EAC UV
LIGHT
MDA FSW

CHWRT
CHWST

TO DDC
T

HIGH LEVEL
T
F

SPACE RH/TEMP
FM SENSOR
BTU

TO DDC
IBMS Control Schematic (AHU-CAV-RESTAURENT)

RA LMCP DDC

LOW LEVEL
ITB

SD
RH
CO2 VSD
IAT
SAT
FSW

COOLING COIL
AHU FILTER
Pre-cooled FA
UV
LIGHT
MDA

IONIZER
M

CHWRT
CHWST

TO DDC
T

HIGH LEVEL
T
F

FM
BTU
ROOM TEMP -1

ROOM TEMP -2
IBMS Control Schematic (SC AHU)

TEA BELT OPERATION

DDC
LMCP

LOW LEVEL
ITB

RUN AROUND COIL

FA
FROM LMCP/TO
DDC SAT
IAT VSD

COOLING COIL
AHU FILTER
UV
LIGHT

FSW

M
HIGH LEVEL
TO DDC

CHWRT
CHWST
T

T
SOFTWARE
1. SC AHU is interlocked with Belt operation. AHU LMCP can also BUTTON TO
activate the SC AHU to be on. iBMS can activate AHU to on F ACTIVATE
CHW VALVE
manually from workstation. FM
BTU
2. iBMS will activate CHW valve to operate if AHU is on and IBMS WORKSTATION
temperature is above the set point. From IBMS, CHW valve can
be activated or deactivated when SC AHU is on. CHW valve will
be deactivated by iBMS if the set point is below set point for
10min (can be changed) or AHU is off.
3. iBMS will generate the high temperature alarm when FMC
temperature is above set point.
IBMS Control Schematic (MTB CHW-FCU)

LMCP
DDC

LOW LEVEL
ITB

SAT

COOLING COIL
Return Air

FILTER

CHWRT
CHWST

T
Rm/Space Tem
IBMS Control Schematic (MTB CHW-FCU WITH FRESH AIR INTAKE) MSCP Lobby,
Mgmt Office, K9 Office, PLB Office

RA
LMCP DDC

LOW LEVEL
ITB

SAT

COOLING COIL
FRESH Air
FILTER

CHWRT
CHWST

Rm/Space Tem
IBMS Control Schematic (MTB CHW-FCU+ VFCU FOR CRITICAL/ELECTRICAL ROOM )

LMCP
DDC

LOW LEVEL
ITB

SAT

COOLING
FILTER
NRD

COIL
M
CHWS

SAT

CHW
T

RT
T

Rm/Space Return Air


Tem
REF COIL
REF COIL

NRD
FILTER

24 ̊C ON

CU
IBMS Control Schematic (CHW-FCU+ VFCU FOR TRANSFORMER ROOM )

LMCP
DDC

LOW LEVEL
ITB

SAT

COOLING
FILTER
NRD

COIL
M
CHWS

SAT

CHW
T

RT
T

Rm/Space Return Air


Tem
REF COIL
REF COIL

NRD
FILTER

24 ̊C ON

CU
IBMS Control Schematic (VFCU+VFCU FOR TRANSFORMER ROOM )
LMCP
DDC

LOW LEVEL
ITB

SAT

REF COIL
FILTER
NRD

FROM LMCP

Return Air
CU
SAT

REF COIL
NRD
FILTER

Rm/Space
Tem

FROM LMCP

CU
IBMS Control Schematic (VFCU + VFCU FOR CRITICAL/ELECTRICAL ROOM AT RT)

LMCP DDC

LOW LEVEL
ITB

SAT

REF COIL
NRD

FILTER

FROM LMCP

Return Air
CU SAT

REF COIL

NRD
FILTER

Rm/Space
Tem

FROM LMCP

CU
IBMS Control Schematic (CARPARK JET FAN )
MSCP-A

LMCP DDC

LOW LEVEL
ITB

Jet fan group-1 normally running


CO level are Above 25ppm

CO Sensor CO Sensor
Jet fan group-2
IBMS Control Schematic (EQUIPMENT ROOM VENTILATION FAN) MSCP Potable Water
Tank Room, Newater Tank Room, RW HT room)

FA
F

LMCP DDC

LOW LEVEL
ITB

R/S -Tem 36C ON


32 ˚C OFF
EAF
IBMS Control Schematic (SPARE TRANSFORMER ROOM VENTILATION FAN)

DDC

LOW LEVEL
ITB

LMCP
R/S -Tem

FA
F

36 ˚C ON
32˚C OFF
IBMS Control Schematic (EXHAUST AIR FAN FOR FM 200 PURGING)

LMCP DDC

LOW LEVEL
ITB

MONITORING ONLY
EAF
IBMS Control Schematic (STAIRCASE FAN-NORMAL)

DDC
LMCP
SAP
LOW LEVEL
ITB

FIRE REMOTE PANEL


IBMS Control Schematic (STAIRCASE FAN LEADING TO BASEMENT CORRIDOR /LINK
BRIDGE WITH AIR PRESSURE DIFFERENTIAL SENSOR)
DDC
SAP
LMCP

LOW LEVEL
ITB

FIRE REMOTE PANEL


VSD

DPS
IBMS Control Schematic (STAIRCASE FAN AT RAMP TOWER WITH AIR PRESSURE
DIFFERENTIAL SENSOR) DDC
LMCP
SAP
LOW LEVEL
ITB

VSD
FIRE REMOTE PANEL

1. Staircase MV system consists of 2 separate mode of MV fans: One emergency mode fan
and one normal mode fan
2. The emergency mode fan is VSD controlled. DPS
3. The normal mode fan could be started by manually or remotely (by BMS)
4. In case of fire, a fire alarm signal will trigger the emergency fan to start.
5. The differential pressure sensor(DPS) in the staircase is to be controlled at 50pa and this
pressure sensor could be regulated the emergency fan during fire mode only
6. When the differential pressure in between lift lobby and staircase is more than 50 pa the
differential pressure sensor will send a signal to the VSD to regulate the emergency fan.
7. Dynamic differential pressure value will feedback to the remote controller at real time.
8. The differential pressure sensor could be installed on the 5 th floor soffit level
IBMS Control Schematic (FFL,SSL,PWD FAN)

SAP
DDC
LMCP

LOW LEVEL
ITB

FIRE REMOTE PANEL


IBMS Control Schematic (CRAC UNIT)

CRAC UNIT

DDC

MODBUS RS 485 HIGH LEVEL INTERFACE

WATER DETETION SYSTEM


IBMS Control Schematic (SMOKE CONTROL SYSTEM)

DDC
LMCP

LOW LEVEL
ITB

LOW LEVEL

SEF

Smoke Curtains

Automatic Doors - Sliding/Swing

Motorized Smoke Damper

Motorized Smoke Fire Damper


IBMS Control Schematic (Fire Protection System & Fire Alarm System)
FM 200/VESDA

DDC

MOBUS RS485 HIGH LEVEL INTERFACE LOW LEVEL

MAP/SAP/RP

           
            HOSEREEL
TANK/SPRINKLER TANK
           
           
           
            ITB
 
WATER METER

HOSEREEL PUMP/SPRINKLER/JOCKEY PUMP


PANEL
HOSEREEL
PUMP/SPRINKLER/JOCKEY
PUMP
IBMS Control Schematic (Irrigation System)

DDC

LOW LEVEL
Irrigation
Control
Panel
ITB

TO EXTERNAL
LANDSCAPE

SOLENOID VALVE

           
            ISOLATION VALVE
           
           
           
           
  IRRIGATION PUMP
TO EXTERNAL
IRRIGATION TANK
LANDSCAPE AND BRIDGE
IBMS Control Schematic (Irrigation Fogging System)

DDC
FOGGING
PUMP Panel LOW LEVEL

ITB

ISOLATON VALVE
FOGGING PUMP-1 TO TREE AT 2ND STOREY

DOUBLE CHECK VALVE

FOGGING PUMP-2 TO TREE AT 2ND STOREY


IBMS Control Schematic (DOMESTIC WATER SYSTEM)

WATER METER DDC


LOW LEVEL

LOW LEVEL
ITB
DOMESTIC WATER
TANK
               
               
                DOMESTIC WATER
                PUMP PANEL
               
               
LOW LEVEL
 

DOMESTIC WATER
PUMP

WATER METER-TENANT
UNIT ,TOILET,CP, ROOF,PLANT
ROOM.
IBMS Control Schematic (NEW WATER SYSTEM)

DDC
LOW LEVEL

LOW LEVEL
NEW WATER PUMP
NEW WATER TANK PANEL
               
                ITB
                POWER METER (High
                level interface via EMS)
               
               
 
LOW LEVEL

NEW WATER PUMP

WATER METER-TOILET,PLANT ROOM, (EG-


SPRINKLER , IRRAGATION)
IBMS Control Schematic (CT MAKE UP SYSTEM)

DDC
LOW LEVEL
LOW LEVEL

ITB

CT MAKE UP WATER
PUMP PANEL

CT MAKE UP WATER TANK


               
               
               
               
               
               
 

CT MAKE UP WATER
PUMP
IBMS Control Schematic (SUMP PITS WITH PUMP SYSTEM)

SUMP PUMP SYSTEM –SANITORY/SURFACE DDC


DRAINAGE/PLANTER DRAIN

LOW LEVEL

ITB

SUMP PUMP
PANEL
IBMS Control Schematic (GREASE EJECTOR PUMP AND EJECTOR SYSTEM)

GREASE EJECTOR PUMP

GREASE EJECTOR PUMP PANEL

GREASE
ITB DDC
TANK

LOW LEVEL

EJECTOR SYSTEM
EJECTOR PUMP PANEL

ITB
IBMS Control Schematic (PNEUMATIC WASTE PUMPS)

DDC

MODBUS RS 485 HIGH LEVEL INTERFACE

BIN CENTER

PNEUMATIC ITB

WASTE SYSTEMS
PANEL
IBMS Control Schematic (LIFT/ESCALATOR/TRAVALATOR SERVICES)

LIFT/ESCALATOR/TRAVALATOR
WORKSTATION
IBMS WORKSTATION

OPC HIGH LEVEL INTERFACE


IBMS Control Schematic (PASSENGER LOADING BRIDGE SYSTEM)

PASSENGER LOADING BRIDGE


SERVER (MCER NORTH)
IBMS WORKSTATION

TCP/IP HIGH LEVEL INTERFACE

IBMS SWITCH
IBMS Control Schematic (AIRCRAFT DOCKING GUIDANCE SYSTEM)

AIRCRAFT DOCKING
GUIDANCE SYSTEM
WORKSTATION
IBMS WORKSTATION

TCP/IP HIGH LEVEL INTERFACE


IBMS Control Schematic (PLB and FGW Lighting and Air Con Control System)

FIDS WORKSTATION
IBMS WORKSTATION

TCP/IP HIGH LEVEL INTERFACE

PLB WORKSTATION

TCP/IP HIGH LEVEL INTERFACE

LIGHTING CONTROL SYSTEM


DDC
LOW LEVEL ITB

BACNET HIGH LEVEL INTERFACE

GW FCU-1 GW FCU-2
IBMS Control Schematic (MASTER CLOCK SYSTEM)

MASTER CLOCK
WORKSTATION
IBMS WORKSTATION

SNMP HIGH LEVEL INTERFACE


IBMS Control Schematic (FLIGHT INFORMATION DISPLAY SYSTEM)

FIDS WORKSTATION
IBMS WORKSTATION

TCP/IP HIGH LEVEL INTERFACE


IBMS Control Schematic (LIGHTING CONTROL MANAGEMENT SYSTEM)

LIGHTING CONTROL
MANAGEMENT SYSTEM IBMS WORKSTATION

OPC HIGH LEVEL INTERFACE


IBMS Control Schematic (ENERGY MANAGEMENT SYSTEM)

ENERGY MONITORING
SYSTEM
IBMS WORKSTATION

HIGH LEVEL INTERFACE


IBMS Control Schematic (HT SYSTEM)

DDC
HT Panels

LOW LEVEL
ITB
IBMS Control Schematic (LT SYSTEM - MSB, SDB & DB)

LV MSB Panels

ITB

DDC

LOW LEVEL
SDB Panels

ITB

DB Panels

ITB
IBMS Control Schematic (LT SYSTEM- SPECIAL DB)

CHECK IN COUNTER DB
Panels

ITB

DDC

LOW LEVEL
SPECIAL FINAL DB
Panels

ITB
IBMS Control Schematic (GENERATOR WITH FUEL SYSTEM)

GENERATOR

MODBUS RS 485 HIGH LEVEL INTERFACE

DDC

FUEL SYSTEM

LOW LEVEL
ITB
IBMS Control Schematic (UPS WITH DC BATTERY BANK SYSTEM)

DC BATTERY BANK SYSTEM

ITB

DDC

HIGH LEVEL INTERFACE

UPS
IBMS Control Schematic (DATA CENTER MONITORING SYSTEM)

DATA CENTER MONITORING


SYSTEM

HIGH LEVEL INTERFACE

DDC

LOW LEVEL

TEM/RH
SENSOR

FM 200 PURGINGMV
FAN

PDU