SCHEMATICS
CONTENT
CHILLER SYSTEM
HEAT EXCHANGER
PAHU
AHU-VAV
AHU-VAV (F&B AND RETAIL TENANT)
DX AHU-VAV - RAMP TOWER
AHU-CAV
AHU-CAV WITH DIRECT FRESH AIR
AHU-CAV – RESTAURANTS
SC AHU
MTB CHW FCU
MTB CHW FCU WITH FRESH AIR INTAKE
MTB CHW FCU+VRV FCU FOR CRITICAL/ELECTRICAL
ROOM
CONTENT
CHW FCU+VFCU FOR TRANSFORMER ROOM
VFCU+VFCU FOR TRANSFORMER ROOM
VFCU FOR CRITICAL/ELECTRICAL ROOM AT RT
CAR PARK JET FAN
EQUIPMENT ROOM VENTILATION FAN
TRANSFORMER SPARE ROOM FRESH AIR FAN
EXHAUST AIR FAN FOR FM200 SYSTEM
STAIRCASE FAN-NORMAL
STAIRCASE FAN AT RAMP TOWER WITH AIR
PRESSURE DIFFERENTIAL SENSORS
STAIRCASE FAN(LEADING TO BASEMENT
CORRIDOR)WITH AIR PRESSURE DIFFERENTIAL
SENSORS
FFL,SSL,PWD LOBBY FAN
CONTENT
CRAC UNIT
SMOKE CONTROL SYSTEM
FIRE PROTECTION SYSTEM AND FIRE ALARM SYSTEM
IRRIGATION SYSTEM/IRRIGATION FOGGING SYSTEM
DOMESTIC WATER SYSTEM
NEW WATER SYSTEM
CT MAKE UP SYSTEM
SUMP PITS WITH PUMP
GREASE EJECTOR PUMP/EJECTOR SYSTEM
PNEUMATIC WASTE PUMPS
VERTICAL TRANSPORTATION SYSTEM
PASSENGER LOADING BRIDGE SYSTEM
AIRCRAFT DOCKING GUIDANCE SYSTEM
CONTENT
MASTER CLOCK SYSTEM
FLIGHT INFORMATION DISPLAY SYSTEM
LIGHTING CONTROL MANAGESYSTEM
ENERGY MANAGEMENT SYSTEM
HT SYSTEM
LT SYSTEM(LV MSB, SDB,DB)
LT SYSTEM(CHECK IN COUNTER DB, FINAL DB)
GENERATOR WITH FUEL SYSTEM
UPS WITH DC BATTERY BANK SYSTEM
DATA CENTER MONITORING SYSTEM
Legend
• VAV - Variable Air Volume
• T - Thermostat
• FM - Flow Meter
• IAT - Inlet Air Temperature Sensor
• SAT- Supply Air Temperature Sensor
• M- Modulating Valve with Actuator
• DDC- Direct Digital Controller
• SP- Air/Water Static Pressure Sensor
• CHWST - Chilled Water Supply Temperature Sensor
• CHWRT- Chilled Water Return Temperature Sensor
• CO2- Carbon Dioxide Sensor
• CO Carbon Monoxide Sensor
• MDA- Fresh Air Motorized Damper Actuator
• FSW- Filter Switch
• RH – Humidity Sensor
• RH/T- Humidity + Temperature Sensor
• R/S Tem- Room Space Temperature
• SD- Smoke Detector
• MD- Modulating Damper with Actuator
• CONTROL LOOP
• CABLE FROM DDC TO ITB IS BY IBMS - LOW LEVEL INTERFACE
• (FOR ACMV, CABLE FROM SENSORS TO DDC IS BY IBMS; AND FOR OTHER
• SERVICES, CABLE FROM SENSORS/CONTACTS TO ITB IS BY M&E SUBCON)
• CABLE BY IBMS (HIGH LEVEL INTERFACE)
• CABLE BY VARIOUS M&E SUBCONS
• ACMV SENSORS BY IBMS (CONNECTED TO DDC PANEL)
(All OTHER SERSORS OR EQUIPMENT ARE BY M&E SUBCONS, ITB IS ALSO BY M&E SUBCONS)
CHILLER PLANT OPTIMIZATION
PROPOSED NETWORK ARCHITECTURE
(HIGH LEVEL INTERFACE WITH IBMS)
IBMS core switch IBMS WORKSTATION
Flow Temp
Meter Sensor MS/TP Bus
Link IP Cat-6 HIGH LEVEL
i-Vu Pro Server
IP Cat-6
PSM
IBMS End switch
DAQ
IP Cat-6
IP Cat-6
IP Cat-6
GWY
Chillers
Variable Speed
i-Vu BAS Drive
Panel
Link
Digital Power Meter VSD
MS/TP
Bus
DPM VSD
IBMS Control Schematic (CHILLER SYSTEM)
DDC
VSD DELTA-P
T T P
CHWS
HEAT
EXCHANGER
T M VSD T P
CHWR
FM FM
BP
IBMS Control Schematic (HEAT EXCHANGER proposed by AST)
a) If the heat load in the control space increased, the motorized damper
will open to allow more CHW flow
b) SCHWS line pressure will decrease and signal the VSD to increase pump
speed to increase the SCHWS line pressure
c) If the FCU motorized valve is fully open, and heat load is still high,
the SCHWR temperature will go above the set point
d) The increased in the SCHWR temperature above set point will open the
PCHWS motorized valve to increase the primary flow into the heat exchanger
to bring down the SCHWS temperature
a) On top of being able to regulate the PCHW flow based on the temperature
feedback of SCHW, the PCHW flow also could be regulated by the PCHWR
temperature
b) If PCHWR temperature is higher than the set point, this indicate the
secondary circuit CHW temperature had been increased due to high head load
c) The motorized valve at the PCHWR line could be opened to allow more CHW
flow to meet the load requirements.
IBMS Control Schematic (PAHU) DDC
LMCP
FROM LMCP/TO
DDC
ITB
LOW LEVEL
SAT
IAT VSD
SP AT 2/3 OF MAIN DUCT
SP
COOLING COIL
Outdoor Air
AHU FILTER
TO AHU
EAC UV MDA
LIGHT
TO AHU
FSW MDA
TO AHU
M
MDA
TO DDC
CHWRT
CHWST
T
TO AHU
T
HIGH LEVEL
MDA
F
FM MDA
BTU
TO AHU
IBMS Control Schematic (AHU-VAV- OFFICE AREA)
LOW LEVEL
RA LMCP
LOW LEVEL
DDC
SD
ITB
CO2
RH
FROM LMCP/TO
DDC
IAT
VSD
SAT
COOLING COIL
Pre-cooled FA
AHU FILTER
SP AT 2/3 OF MAIN DUCT
EAC UV
LIGHT
MDA FSW
SP
M
TO DDC
CHWRT
CHWST
T
T
F HIGH LEVEL
FM
BTU
VAV VAV VAV
T T T
IBMS Control Schematic (AHU-VAV FOR F&B and RETAIL TENANT)
DDC
RA LMCP
LOW LEVEL
SD
ITB
CO2
RH
IAT VSD SAT
COOLING COIL
AHU FILTER
Pre-cooled FA
EAC
UV
LIGHT
SP AT 2/3 OF MAIN DUCT
MDA FSW
SP
M
HIGH LEVEL
TO DDC
CHWRT
CHWST
T
T
F
FM
BTU
DA DA DA
T T T
IBMS Control Schematic (DX AHU- VAV-RAMP TOWER)
LMCP
RA
LOW LEVEL
ITB DDC
SD
CO2
FROM LMCP/TO DDC
IAT VSD SP about 2/3 OF MAIN
SAT
DUCT
Direct Fresh Air SP
AHU FILTER
Intake
REF COIL
EAC
UV
LIGHT
MDA
FSW
TO LMCP
RH/T
VAV VAV VAV
CU
T T T
IBMS Control Schematic (AHU-CAV)
RA LOW LEVEL
LMCP
ITB
LOW LEVEL DDC
CO2
SD
FROM LMCP/TO DDC
Pre-cooled FA
COOLING COIL
AHU FILTER
EAC
UV
LIGHT
MDA FSW
CHWRT
CHWST
TO DDC
T
T
HIGH LEVEL
F
SPACE RH/TEMP
FM SENSOR
BTU
TO DDC
IBMS Control Schematic (AHU-CAV WITH DIRECT FRESH AIR)
RA LOW LEVEL
LMCP
LOW LEVEL
ITB
DDC
FROM/TO DDC
CO2
SD
IAT VSD SAT
COOLING COIL
AHU FILTER
Intake
EAC UV
LIGHT
MDA FSW
CHWRT
CHWST
TO DDC
T
HIGH LEVEL
T
F
SPACE RH/TEMP
FM SENSOR
BTU
TO DDC
IBMS Control Schematic (AHU-CAV-RESTAURENT)
RA LMCP DDC
LOW LEVEL
ITB
SD
RH
CO2 VSD
IAT
SAT
FSW
COOLING COIL
AHU FILTER
Pre-cooled FA
UV
LIGHT
MDA
IONIZER
M
CHWRT
CHWST
TO DDC
T
HIGH LEVEL
T
F
FM
BTU
ROOM TEMP -1
ROOM TEMP -2
IBMS Control Schematic (SC AHU)
DDC
LMCP
LOW LEVEL
ITB
FA
FROM LMCP/TO
DDC SAT
IAT VSD
COOLING COIL
AHU FILTER
UV
LIGHT
FSW
M
HIGH LEVEL
TO DDC
CHWRT
CHWST
T
T
SOFTWARE
1. SC AHU is interlocked with Belt operation. AHU LMCP can also BUTTON TO
activate the SC AHU to be on. iBMS can activate AHU to on F ACTIVATE
CHW VALVE
manually from workstation. FM
BTU
2. iBMS will activate CHW valve to operate if AHU is on and IBMS WORKSTATION
temperature is above the set point. From IBMS, CHW valve can
be activated or deactivated when SC AHU is on. CHW valve will
be deactivated by iBMS if the set point is below set point for
10min (can be changed) or AHU is off.
3. iBMS will generate the high temperature alarm when FMC
temperature is above set point.
IBMS Control Schematic (MTB CHW-FCU)
LMCP
DDC
LOW LEVEL
ITB
SAT
COOLING COIL
Return Air
FILTER
CHWRT
CHWST
T
Rm/Space Tem
IBMS Control Schematic (MTB CHW-FCU WITH FRESH AIR INTAKE) MSCP Lobby,
Mgmt Office, K9 Office, PLB Office
RA
LMCP DDC
LOW LEVEL
ITB
SAT
COOLING COIL
FRESH Air
FILTER
CHWRT
CHWST
Rm/Space Tem
IBMS Control Schematic (MTB CHW-FCU+ VFCU FOR CRITICAL/ELECTRICAL ROOM )
LMCP
DDC
LOW LEVEL
ITB
SAT
COOLING
FILTER
NRD
COIL
M
CHWS
SAT
CHW
T
RT
T
NRD
FILTER
24 ̊C ON
CU
IBMS Control Schematic (CHW-FCU+ VFCU FOR TRANSFORMER ROOM )
LMCP
DDC
LOW LEVEL
ITB
SAT
COOLING
FILTER
NRD
COIL
M
CHWS
SAT
CHW
T
RT
T
NRD
FILTER
24 ̊C ON
CU
IBMS Control Schematic (VFCU+VFCU FOR TRANSFORMER ROOM )
LMCP
DDC
LOW LEVEL
ITB
SAT
REF COIL
FILTER
NRD
FROM LMCP
Return Air
CU
SAT
REF COIL
NRD
FILTER
Rm/Space
Tem
FROM LMCP
CU
IBMS Control Schematic (VFCU + VFCU FOR CRITICAL/ELECTRICAL ROOM AT RT)
LMCP DDC
LOW LEVEL
ITB
SAT
REF COIL
NRD
FILTER
FROM LMCP
Return Air
CU SAT
REF COIL
NRD
FILTER
Rm/Space
Tem
FROM LMCP
CU
IBMS Control Schematic (CARPARK JET FAN )
MSCP-A
LMCP DDC
LOW LEVEL
ITB
CO Sensor CO Sensor
Jet fan group-2
IBMS Control Schematic (EQUIPMENT ROOM VENTILATION FAN) MSCP Potable Water
Tank Room, Newater Tank Room, RW HT room)
FA
F
LMCP DDC
LOW LEVEL
ITB
DDC
LOW LEVEL
ITB
LMCP
R/S -Tem
FA
F
36 ˚C ON
32˚C OFF
IBMS Control Schematic (EXHAUST AIR FAN FOR FM 200 PURGING)
LMCP DDC
LOW LEVEL
ITB
MONITORING ONLY
EAF
IBMS Control Schematic (STAIRCASE FAN-NORMAL)
DDC
LMCP
SAP
LOW LEVEL
ITB
LOW LEVEL
ITB
DPS
IBMS Control Schematic (STAIRCASE FAN AT RAMP TOWER WITH AIR PRESSURE
DIFFERENTIAL SENSOR) DDC
LMCP
SAP
LOW LEVEL
ITB
VSD
FIRE REMOTE PANEL
1. Staircase MV system consists of 2 separate mode of MV fans: One emergency mode fan
and one normal mode fan
2. The emergency mode fan is VSD controlled. DPS
3. The normal mode fan could be started by manually or remotely (by BMS)
4. In case of fire, a fire alarm signal will trigger the emergency fan to start.
5. The differential pressure sensor(DPS) in the staircase is to be controlled at 50pa and this
pressure sensor could be regulated the emergency fan during fire mode only
6. When the differential pressure in between lift lobby and staircase is more than 50 pa the
differential pressure sensor will send a signal to the VSD to regulate the emergency fan.
7. Dynamic differential pressure value will feedback to the remote controller at real time.
8. The differential pressure sensor could be installed on the 5 th floor soffit level
IBMS Control Schematic (FFL,SSL,PWD FAN)
SAP
DDC
LMCP
LOW LEVEL
ITB
CRAC UNIT
DDC
DDC
LMCP
LOW LEVEL
ITB
LOW LEVEL
SEF
Smoke Curtains
DDC
MAP/SAP/RP
HOSEREEL
TANK/SPRINKLER TANK
ITB
WATER METER
DDC
LOW LEVEL
Irrigation
Control
Panel
ITB
TO EXTERNAL
LANDSCAPE
SOLENOID VALVE
ISOLATION VALVE
IRRIGATION PUMP
TO EXTERNAL
IRRIGATION TANK
LANDSCAPE AND BRIDGE
IBMS Control Schematic (Irrigation Fogging System)
DDC
FOGGING
PUMP Panel LOW LEVEL
ITB
ISOLATON VALVE
FOGGING PUMP-1 TO TREE AT 2ND STOREY
LOW LEVEL
ITB
DOMESTIC WATER
TANK
DOMESTIC WATER
PUMP PANEL
LOW LEVEL
DOMESTIC WATER
PUMP
WATER METER-TENANT
UNIT ,TOILET,CP, ROOF,PLANT
ROOM.
IBMS Control Schematic (NEW WATER SYSTEM)
DDC
LOW LEVEL
LOW LEVEL
NEW WATER PUMP
NEW WATER TANK PANEL
ITB
POWER METER (High
level interface via EMS)
LOW LEVEL
DDC
LOW LEVEL
LOW LEVEL
ITB
CT MAKE UP WATER
PUMP PANEL
CT MAKE UP WATER
PUMP
IBMS Control Schematic (SUMP PITS WITH PUMP SYSTEM)
LOW LEVEL
ITB
SUMP PUMP
PANEL
IBMS Control Schematic (GREASE EJECTOR PUMP AND EJECTOR SYSTEM)
GREASE
ITB DDC
TANK
LOW LEVEL
EJECTOR SYSTEM
EJECTOR PUMP PANEL
ITB
IBMS Control Schematic (PNEUMATIC WASTE PUMPS)
DDC
BIN CENTER
PNEUMATIC ITB
WASTE SYSTEMS
PANEL
IBMS Control Schematic (LIFT/ESCALATOR/TRAVALATOR SERVICES)
LIFT/ESCALATOR/TRAVALATOR
WORKSTATION
IBMS WORKSTATION
IBMS SWITCH
IBMS Control Schematic (AIRCRAFT DOCKING GUIDANCE SYSTEM)
AIRCRAFT DOCKING
GUIDANCE SYSTEM
WORKSTATION
IBMS WORKSTATION
FIDS WORKSTATION
IBMS WORKSTATION
PLB WORKSTATION
GW FCU-1 GW FCU-2
IBMS Control Schematic (MASTER CLOCK SYSTEM)
MASTER CLOCK
WORKSTATION
IBMS WORKSTATION
FIDS WORKSTATION
IBMS WORKSTATION
LIGHTING CONTROL
MANAGEMENT SYSTEM IBMS WORKSTATION
ENERGY MONITORING
SYSTEM
IBMS WORKSTATION
DDC
HT Panels
LOW LEVEL
ITB
IBMS Control Schematic (LT SYSTEM - MSB, SDB & DB)
LV MSB Panels
ITB
DDC
LOW LEVEL
SDB Panels
ITB
DB Panels
ITB
IBMS Control Schematic (LT SYSTEM- SPECIAL DB)
CHECK IN COUNTER DB
Panels
ITB
DDC
LOW LEVEL
SPECIAL FINAL DB
Panels
ITB
IBMS Control Schematic (GENERATOR WITH FUEL SYSTEM)
GENERATOR
DDC
FUEL SYSTEM
LOW LEVEL
ITB
IBMS Control Schematic (UPS WITH DC BATTERY BANK SYSTEM)
ITB
DDC
UPS
IBMS Control Schematic (DATA CENTER MONITORING SYSTEM)
DDC
LOW LEVEL
TEM/RH
SENSOR
FM 200 PURGINGMV
FAN
PDU