Professional Documents
Culture Documents
2020 - Chapter-5 Loss Less Lines - ON LINE - A - 1
2020 - Chapter-5 Loss Less Lines - ON LINE - A - 1
Is
L
VL O
VS A
d
VS VR VX VL
VS R I jX I VL
Fida Muhammad (Air University)
Transmission Lines Voltage Regulation
Lagging Power Factor R jX IS -
VS VR VX VL
VS
VR
VX
VL VS > VL
IS
VNL VFL
% VR 100 Posistive
VFL
Fida Muhammad (Air University)
Transmission Lines Voltage Regulation
Lagging Power Factor R jX IS -
VR=RI VX=XI L
o
VS VL a
d
Vs
Veq
Vx
VL VR
: Load Power Factor angle (Between VL & Is)
VS VR VX VL
VX
Vs
VS < VL
IS
VR
VS VL
% VR 100 Negative
VS
VL
Fida Muhammad (Air University)
(Ferranti Effect)
Transmission Lines Voltage Regulation
Unity Power Factor Reqp jXeqp IS -
VReq VjXeq L
Unity
Vs =RIS =XIS VL
o
a Power Factor
d Load
Vs VR VX VL
Not: The Load PF is
Unity but the source
Vs PF is lagging due to
line inductance
VX
VS > V L
VS VL
% VR 100 ?
VR
IS VL VS
Fida Muhammad (Air University)
Positive
Types of Power Transmission Line
cosh( l) 1 Z c
sinh( l ) Z /
1
2
f jZ c sin(l) j sin(l)
LC cos( l)
Losssless : (R=G=0) Zc
Formula Sheet
VR VS A D B C
z (1 YZ1 ) ( Z1 Z 2 YZ1Z 2 ) P sin W per unit s
Zc X
y Y (1 YZ 2 ) 1 Z 0
VS
VRN L YZ YZ
A 1 Z Y 1
(1 Y2 Z) Z 2 4
zy sinh( l)
( Y1 Y2 Y1Y2 Z) (1 Y1Z ) LC m 1
Y / Z/
Z c sinh( l) Z /
1 cosh( l) 1 2
Zc
f jZ c sin( l) j sin(l)
LC cos(l)
Zc
5.4 LOSSLESS LINES (R=G=0) (Page 262)
(Over Head Lines not Under ground cables)
When Line's var (QL) Usage = Line's var (QC) Production this
Phenomenon in transmission line's is called Surge Impedance
Loading or SIL. (simply the MW loading Or unity PF) at which the
2
V
I2 X L
Line's Mvar Usage = Line's Mvar Production = SIL XC
Line's Mvar Usage = Line's Mvar Production.
V2 2fL V2 V L
I XL
2
Z Surge Im pedance
2fC
0
XC I 2
I C
Note: The theoretical significance of the surge impedance is that if
a purely resistive load that is equal to the surge impedance were
connected to the end of a transmission line with no Transmission
line Resistance(R), a voltage surge introduced to the sending end
of the line would be absorbed completely at the receiving end.
VS=VR
VS=VR and would have a phase angle that is lagging with respect
to the sending end by an amount equal to the time required to
travel across the line from sending to receiving end.
(kVLL ) 2
SIL , (MW )
Z0
Loading of any transmission line depends:
(kVLL )2 L
Surge Impedance Loading or SIL (MW ) Z0
C
Z0
This is defined as the load (of unity power factor) that can be
delivered by the line of negligible resistance. OR
V2
I XL
2
Unity PF Voltage Reg? XC
Vs VS=VR Surge Impedance Loading (SIL)
VS=VR
VS>VR Lagging PF Voltage Reg?
Full Load Condition
XC
VS AV R BI R ; VS
VR ( No Load )
No Load I R 0 A
A 1 VR( SIL ) VS
B0
In practice, power lines are not terminated by their surge impedance. loadings
can vary from a small fraction of SIL during light load conditions
No Load Condition
1. At no-load, IRNL=0 & yields
Vs
(Ferranti Effect)
Surge Impedance Loading (SIL)
VR ( No Load )
VS VNL(x)=(cos x)VRNL The no-load
A
Full Load Condition
voltage increases from VS=(cos
Short Circuit Condition l)VRNL at the sending end to VRNL
at the receiving end (where x =
0).
Sending Voltage Receiving Voltage
Formula Sheet
Zc
2. the voltage
A D
per unit
B
X
profile
C
VR VS
z (1 YZ1 ) (Z1 Z2 YZ1Z2 ) P sin W
s
at SIL is flat.
y Y (1 YZ2 ) 0
VS AV R BIR Volts VRNL
VS
1
1
YZ
Z
Z
YZ
Y 1
A
(1 Y2 Z) Z 2 4
IS CVR DIR Amps zy LC m1
( Y1 Y2 Y1Y2 Z) (1 Y1Z)
Y /Z/
sinh( l)
cosh( l ) 1 Z c sinh( l) Z / Zc
1 2
f jZ c sin(l) j sin(l)
LC cos( l)
Zc