Professional Documents
Culture Documents
CT-01 Solutions
CT-01 Solutions
Solutions:
(a) 𝐸 𝐴 =𝑉 𝜙 − 𝑗 𝑋 𝑠 𝐼 𝐴
= 3 V 𝜙 𝐸𝐴
(b) 𝑃 𝑚𝑎𝑥
𝑋𝑠
𝐸
𝐴2 = 𝐼 𝐹 2
𝐸 𝐴1 𝐼 𝐹 1
Synchronous motors
Synchronous motors are synchronous machines used to convert electrical
power to mechanical power
Fig. 6.1
Equivalent circuit of synchronous motor:
Fig. 6.2a
The synchronous motor from a magnetic field perspectives:
Fig. 6.3
=
The synchronous motor from a magnetic field perspectives:
Fig. 6.4
Steady-state synchronous motor operation:
Fig. 6.5
The synchronous motor Torque-Speed characteristic curve:
=
=
Or,
=
=
Or,
=
Fig. 6.6
Solution:
Initially, the motor’s output power is 15 hp. This corresponds to an
output of,
= 15 X 0.746 =11.19 kW
Therefore, the electric power supply to the machine is,
=++
= 11.19 + 1.5 + 1.0 + 0
=13.89 kW
Since the motor’s power factor is 0.8 leading, the resulting line
current flow is,
=
As the power on the shaft is increased to 30 hp, the shat slows down
momentarily, and the internal generated voltage EA swings out to a larger
angle while maintain phasor diagram is shown in Fig. 6-7b.
Fig. 6.7
After the load changes, the electric input power of the machine
becomes,
=++
= 30 X 0.746 + 1.5 + 1.0 + 0
=24.88 kW
Now,
P =
= =
EA = 255 V
= = A
== 41.2 =71.4 A
Fig. 6.8
The effect of field current change on a synchronous motor:
Fig. 6.9
The effect of field current change on a synchronous motor:
Fig. 6.8b
Fig. 6.10
The inverted V-curves:
=constant
Solution:
The resulting phasor diagram is shown in Fig. 6-11, together with the results for part (b).
Fig. 6.11
(b) If the flux is increased by 25%, then EA will increase by 25% too, as EA = k,
∴ 𝐸 𝐴 =182 X 1.25=227.5 V
However, the power supplied to the load must remain constant. Since P EA sin , that
distance on the phasor diagram must be constant from the original flux level to the new
flux level. Therefore,
𝐸 𝐴 1 𝑠𝑖𝑛 𝛿 1= 𝐸 𝐴 2 𝑠𝑖𝑛 𝛿 2
𝐸𝐴 1 182
⟹ 𝛿 2 =𝑠𝑖𝑛 −1
[ 𝐸𝐴 2 ] [
𝑠𝑖𝑛 𝛿 1 =𝑠𝑖𝑛−1
227.5 ]
sin ( −17.5 ° ) = −13.9 °
22.5
Finally, the motor’s power factor is now,
𝑃𝐹=cos
( 13.2 ° )=0.974𝑙𝑒𝑎𝑑𝑖𝑛𝑔
The resulting phasor diagram is shown in Fig. 6-11.
(c) Because the flux is assumed to increase linearly with field current, EA will also
vary linearly with field current. So,
𝐸 𝐴2 𝐼𝐹 2
=
𝐸 𝐴1 𝐼𝐹 1
𝐼𝐹2 𝐼 𝐹2
∴ 𝐸 𝐴 2 =𝐸 𝐴 1 =182 . =45.5 𝐼 𝐹 2
𝐼𝐹1 4
The torque angle for any given field current can be found from the fact that the
power supplied to the load must remain constant:
𝐸 𝐴 1 𝑠𝑖𝑛 𝛿 1= 𝐸 𝐴 2 𝑠𝑖𝑛 𝛿 2
𝐸𝐴
⟹ 𝛿 2 =𝑠𝑖𝑛
−1
[ 𝐸𝐴
1
2
𝑠𝑖𝑛 𝛿 1
]
These two pieces of information give us the voltage E A. Once EA is available, the new
armature current can be calculated from the equation,
𝑉 𝜙 − 𝐸𝐴 2
𝐼 𝐴 2=
𝑗 𝑋𝑠
Similarly, IA can be calculated for
Fig. 6.12
several values of IF and plotted as
shown in Fig. 6-12.
Fig. 6.13
Solution:
(a) Load 1:
Load 2:
Load 3:
So, overall,
Now, 𝑃𝑡𝑜𝑡 3
450 𝑋 10
𝐼 𝐿= = =667 A
√3 𝑉 𝐿 𝑐𝑜𝑠 𝜃 √ 3 X 480 X 0.812
(b)
So, overall,
𝑃𝑡𝑜𝑡 450 𝑋 10
3
Now,
𝐼 𝐿= = =566 A
√3 𝑉 𝐿 𝑐𝑜𝑠 𝜃 √ 3 X 480 X 0. 957
𝑃 2 2
(c) First case:
𝐿𝐿 =3 𝐼 𝑅
𝐿 𝐿 =3 X 667 X 𝑅 𝐿 =1,334,667 𝑅 𝐿
Second case:
Note that in second case the power loss is 28% less than in the first case, while
power supplied to the load is the same for both cases.
Having one or more leading loads (overexcited synchronous motors) on the system
can be useful for the flowing reasons:
1. A leading load can supply some reactive power Q for nearby lagging loads,
instead of it coming from the generator. It reduces transmission line losses
2. Since the transmission lines carry less current, they can be smaller for a given
power flow. A lower equipment current rating reduces the cost of power system
Fig. 6.14
𝑉 𝜙=𝐸 𝐴 − 𝑗 𝑋 𝑠 𝐼 𝐴
The synchronous capacitor or synchronous condenser:
Fig. 6.15
• Today conventional static capacitors are more economical to buy and use than
synchronous capacitors
Starting synchronous motors
60 Hz generator: one
complete rotation
needs 1/60 seconds
𝜏 𝑖𝑛𝑑 =𝑘 𝐵𝑅 ×𝐵 𝑠
Fig. 6.16
Starting synchronous motors
Three basic approaches can be used to safely start a synchronous motor:
• Using reduced frequency power supply
• Using external prime mover
• Using damper/ amortisseur windings
Fig. 6.17
Fig. 6.18
𝑒 𝑖𝑛𝑑=( 𝑣×𝐵 ) ⋅𝑙
𝜏 𝑖𝑛𝑑 =𝑘 𝐵𝑊 × 𝐵𝑠
Fig. 6.19
Starting synchronous motors
Steps to start synchronous motor using amortisseur windings:
• Disconnect the field windings from their dc power supply source and
short them out
Fig. 6.20
Synchronous motor ratings
• The difference is, large EA gives leading power factor, instead of lagging
one
Fig. 6.21