Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 28

ZXM10 EISU Training

Unitrans D&T Group


Overview
Overview
 The ZXM10 EISU is an imbedded microprocessor system.
 It can monitor supervision signals of various base station
power equipment and environments in real time, generate
alarms, and make corresponding control as required.
 it is capable of networking downlink base stations, and
networking by making effective use of base station
communication resources.

2
Description
Description of
of EISU
EISU Models
Models
 The ZXM10 EISU (V1.0) is a series product.

ZXM10 EISU ( - - - )
48 -48 VDC power
24 +24 VDC power

Null Basic functions


BT Battery capacity analysis function added

Null Basic configurations


SS Extended configuration

Null Basic mode, network interface (master comm port) and serial port
for master communication
1E One E1 interface (master comm port) and timeslot back board for
master communication
2E Two E1 interfaces (master comm port), 2M ring and timeslot front
board for master communication
4E Four E1 interfaces (master comm port), 2M ring + chain networking

3
Description
Description of
of Common
Common Models
Models of
of the
the EISU
EISU
No Model Description
.
1 ZXM10 EISU Serial port and network interface for master comm
(48) unication, basic configuration for supervision facto
r, ­-48 V
2 ZXM10 EISU 2M ring and front board for master communication
(2E-48) , basic configuration for supervision factor, ­-48 V
3 ZXM10 EISU Back board for master communication, basic confi
(1E-48) guration for supervision factor, ­-48 V
4 ZXM10 EISU Back board for master communication, extended c
(1E-SS-48) onfiguration for supervision factor, ­-48 V
5 ZXM10 EISU Back board for master communication, extended c
(1E-SS-BT-4 onfiguration for supervision factor, battery capacity
8) analysis function being integrated, ­-48 V

4
Functions
Functions
 In the basic configuration, the ZXM10 EISU provides 12 general
AI/DI measurement channels, two general DI measurement channels
and four DO channels to implement data collection and control of the
unintelligent equipment. If an extended supervision unit is
configured, eight general AI/DI measurement channels, two general
DI measurement channels and four DO interfaces are added.
 The ZXM10 EISU has the dedicated sensor interface, where one
digital temperature sensor, two battery channels for total voltage and
one smog detector can be connected.
 The ZXM10 EISU provides multiple intelligent equipment protocol
resolution interfaces to implement data collection and control of the
intelligent equipment. (There are four to six interfaces and 20
intelligent devices can be connected.)
 The ZXM10 EISU has the picture supervision function. It provides
two USB camera interfaces to process, store and forward picture
data. The picture resolution is up to 640  480.

5
Functions
Functions
 The ZXM10 EISU provides multiple communication interfaces and
networking modes. These transmission interfaces contain
asynchronous serial ports, Ethernet interfaces and E1 interfaces.
They provide the following networking modes: order wire channel,
network, 2M protection ring, 2M chain, separate 2M and 2M
extracted timeslot.
 The ZXM10 EISU provides the local storage function. The data
within 15 days can be stored locally after the master communication
is interrupted.
 The ZXM10 EISU provides the function of remotely or locally
downloading the running program and intelligent equipment
communication protocol program.
 The ZXM10 EISU has the functions of equipment self-diagnosis and
fault self-location.
 The ZXM10 EISU provides the management function of real-time
clocks.

6
Functions
Functions
 The ZXM10 EISU configured with the extended transmission
board provides transparent Ethernet interfaces.

 The ZXM10 EISU provides the Web browsing function.

 The ZXM10 EISU supports the intelligent equipment center


resolution function.

 The ZXM10 EISU supports energy saving for air conditioners.

7
Panel
Panel Indicators
Indicators
 There are nine indicators on the EISU panel,

8
Jumper
Jumper and
and DIP
DIP Settings
Settings of
of EISU
EISU
 Basic configuration of EISU includes configuration to EISUP
board, EISUM board, ETNM board, and EISUL board.

EISUL board

EISUP board EISUM board

ETNM board EISUS board

9
Jumper
Jumper and
and DIP
DIP Settings
Settings on
on EISUP
EISUP Board
Board
 Key components on EISUP board are as follow. In engineering
practice,

X5

EISUP
S2

X4 X7

S1

10
Jumper
Jumper and
and DIP
DIP Settings
Settings on
on EISUP
EISUP Board
Board
 the jumper X7 on EISUP board must be at pin 2 and 3. DIP swi
tch S2 use default setting.

11
Jumper
Jumper and
and DIP
DIP Settings
Settings on
on EISUM
EISUM Board
Board
 here are two DIP switches on EISUM

EISUM

S2

S1

12
Jumper
Jumper and
and DIP
DIP Settings
Settings on
on EISUM
EISUM Board
Board
 boardS1.1~S1.8 and S2.1~S2.4 are AI type switches, ON mea
ns current type, OFF means voltage type.

13
Description
Description of
of External
External Interfaces-EISUM
Interfaces-EISUM
 External interfaces of the EISU can be viewed when the cable
cover is removed. The external interfaces are provided by the
EISUM, EISUS and ETNM. The interfaces in the lower row are
provided by the EISUM, and the interfaces in the upper row by
the EISUS and the ETNM. The EISUS can change its location
with the ETNM .

Switch

14
Configuration
Configuration EISUconfig
EISUconfig
 Log in EISUconfig

15
Basic
Basic Configuration
Configuration
 EISU network parameters and security console connection pa
rameters.

16
Board
Board Management
Management
 On Channel Configuration subpage, sensor type, channel typ
e, upper and lower limits of alarm, and return difference, and s
o on,

17
Serial
Serial Port/Intelligent
Port/Intelligent Port
Port Management
Management
 EISU has 7 serial ports in total.

18
Intelligent
Intelligent Analysis
Analysis Settings
Settings
 the red numbers are the order of the steps in setting intelligent
analysis function.

19
USB
USB Video
Video Management
Management
 If USB device is closed, then all management and operation
related to this USB device are unavailable. If USB device is
available, relevant operation may be done.

20
Access
Access Control
Control Communication
Communication Settings
Settings

21
External
External access
access control
control mode
mode
 Connect external access controller with EISU applied in
dynamic IP networking.
For example, connect CHD805AE in wireless dynamic IP
networking or dynamic IP networking.
1. Set the serial port connecting the device as soft transparent;
2. Set up serial port parameters: baud rate, receive mode.

22
EISU
EISU built-in
built-in access
access control
control mode
mode

23
Operation
Operation steps
steps
 1.Select the serial port that is specified on engineering drawing in
Serial Port box, and select Access Control in the Function box;
 2.Click Modify button to set serial port parameters.
 If Baud Rate is 9600, then the Waiting Time after Sending should
be set as 2083;
 If Baud Rate is a value other than 9600, then the Waiting Time after
Sending will be automatically set to appropriate value. EISU
configuration program above V1.10 supports this function.
 3.For receive mode, you must select [Header (7E) +Tail (0D)];
 4.Set Function Parameters of Access Control Port:
 Server IP and Port No. do not need to be set.
 5.Door Magnetic Channel must be set as the exact channel that is
connected in construction practice.

24
Update
Update of
of Application
Application Program
Program and
and Driver
Driver
 EISU supports remote downloading application program and
driver.

25
Faults
Faults and
and Alarm
Alarm Handling
Handling

26
Faults
Faults and
and Alarm
Alarm Handling
Handling

27
univ.zte.com.cn

You might also like