Coal Fired PP at WHTC Mangla
Coal Fired PP at WHTC Mangla
Coal Fired PP at WHTC Mangla
Main machines:
Boiler Steam turbine Electric generator
Diagram of a Typical steam-cycle Coal Power Plant
Coal-fired Power Plant Schematic
Systems
The power plant consists of the following major systems :
Electrical system
Steam water system
Air and flue gas system
Coal handling system
Circulating water system
Ash handling system
Chemical water treatment system
Instrument & Control system
Environmental control system
Boiler
Furnace Wall
(a) Thermally induced, also called thermal, thermo-syphonic, or "natural", with inherent
circulation.
It’s a prime mover. As we know, there are a lot of prime movers, such as internal
combustion engine and steam engine. But the working manner of the steam turbine,
The Company's 2×660MW steam turbines are supercritical, single shaft, four-
cylinder, four- exhaust, once intermediate reheating and condensing turbines
made by Shanghai Turbine Company Ltd. The N660-24.2/566/566 turbine with
an eight-stage regenerative steam extraction system, has a maximum
continuous rating of 681MW, a rated output of 660MW, and a rated speed of
3000r/min. The turbine unit adopts composite variable pressure operation
mode.
Steam Turbine specifications for Sahiwal Coal PP
The circulation part of steam turbine consists of high pressure, medium pressure
and low pressure parts, 79 stages in total, which are all reaction type. The high
pressure part is divided into 19 stages. The medium pressure part is of two-way
split flow type and there are 32 stages in total with 16 stages for either flow. The
low pressure part is of two-cylinder two-way split flow type and there are 28
stages in total with 7 stages for either split flow,.
Layout for Steam Turbine at Sahiwal Coal PP
Generator Specifications of Shahiwal Coal PP
Model QFSN-660-2 Rated capacity (MVA) 776.5
Self-shunt excitation static
Rated power (MW) 660 Excitation method
excitation
22 Rated stator current (A) 20377
Rated stator voltage (kV)
Rated excitation voltage (V) 491 Rated excitation current (A) 4669
No-load excitation voltage (V) 150 No-load excitation current (A) 1497
Manufacturer
Shanghai Electric Group Co., Ltd.
Electrical System of Shahiwal Coal PP
The 500kV system adopts double-bus 3/2 wiring approach, which is connected with incoming
lines of two main transformers, outgoing lines of two lines and one startup standby transformer to
form two complete series and one incomplete series (semi-series) system.
The main transformer is produced by Xian XD Transformer Co., Ltd. The single phase model is
DFP10-270000/500 and 270MVA forced oil circulation air cooling method is used.
The startup/standby transformer is produced by Xian XD Transformer Co., Ltd. The model is
SFFZ10-70000/500, and 70/45-45MVA natural oil circulation air cooling and on-load voltage
regulation with split winding are used.
The HV auxiliary transformer is produced by Xian XD Transformer Co., Ltd. The model is
SFF10-70000/22, and 70/45-45MVA natural oil circulation air cooling and no-load voltage
regulation transformer with split winding are used.
Electrical System of Shahiwal Coal PP