C.

START UP
C.01 Parameterization steps

It is possible to insert parameters manually


by means of PMU and OP1S
Function diagrams:
Parameter list:

PC with
Drive Monitor

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.02 Drives commissioning

The functions stored in the units are adapted to the


specific application by means of parameters identified with
name and number. Many parameter also have an index.
The values can only be changed under certain conditions:

• The parameter must be a changeable parameter.


• Parameter access must be granted.
• The units must be in a status witch permits parameters
to be changed.
• The lock and key mechanism must not be activated

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.03 Parameterization tools

PMU

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.04 PMU Unit

4 Digits Display ADDRESSES

B0008
Raise/lower to
select:
B0009

Switch ON  Parameters
P -----
 Indices
Switch OFF B0006
 Parameter B0007
values

B0005
Parameter number
Fault acknowledgement and
changeover between:

 Parameter number
Parameter Parameter
index value
 Parameter index

 Parameter value

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.05 SIMOVERT MASTERDRIVES OPERATOR PANEL

Features Customer benefits


 4-line clear text  Indicates physical values
display
with 16 characters  No measuring equipment
required
 Numerical keyboard
 Can also be used as
 Removable hand-held unit
 Parameter saving  Data storage
(up to 8 Data sets)
 Simple commissioning
 Parameter sets can
be UPREAD  Fast, direct
(DOWNLOAD) parameter access

 Menu prompted  Fast, routine


commissioning
 Applicable for all
SIMOREG DC-MASTER
and SIMOVERT
MASTERDRIVES

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.06 OP1S

ADDRESSES

B2113

B2114

P -----
B2111
B2112

B2100
B2101
B2102

Reset B2107

Jo B2108
g

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.07 OP1S

The OP1S switches to operational


display a few seconds after
initialization.
By pressing the <P> key, you can
switch from the operating display to
the Basic Menu in which you can
either select "Free access" to all
parameters or a variety of functions.
The converter parameters can be set
in "Free access" status.
You can return to the operating
status display by pressing the <R>
key (several times if necessary).

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.08 SIEMENS MASTERDRIVES SW FOR DRIVE
COMMISSIONING AND MONITORING (Drive Monitor)
Customer
Features
benefits

 Menu prompted  Rapid


commissioning commissioning

 Parameter sets can  Simple operator


be loaded and saved control
and monitoring
 Operator control via
control word  User-friendly
service
 Monitoring via
status word

 Fault messages can


be read

 Trace buffer can be


read-out

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.09 Drive monitor start up

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.10 Drive monitor drive model selection

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.11 Drive monitor

When activated the drives


programming software
installed in a PC appears as
indicated.
Drive Navigator provide
several functions to facilitate
the parameterization
procedure such as “Assisted
Commissioning”.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.12 Assisted commissioning

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.13 Drive monitor

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.14 Drive monitor

Possible options available

Parameter selected

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.15 Drive monitor- status of the drive

4 ON/OFF Command

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.16 DC Drives Parameterization steps
If the exact application condition of the unit is not known,
the parameter reset to the factory setting is suggested.
P051 = 21. Then the following procedure:

• Adjustment of converter • Selection of basic


rated currents. (P076) technological functions.
• Adjustment to actual • Execution of optimization
converter supply voltage runs.
(P078) • Checking and possible fine
• Access authorization (P051 adjustment of maximum
and P052) speed.
• Input of motor data (P100 • Manual post-optimization (if
– P114) necessary)
• Actual speed sensing data • Setting of supplementary
• Field data functions

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP

C.17 DC Drives Enabling optional technology software


The technology option can only be utilized on SIMOREG DC
Master converters on which this option has been
enabled by a proper PIN number. The procedure to
activate it is:
1. Find out the serial number of your unit.
2. Find out the PIN number
3. Enter the PIN number in parameter U977.
4. Check this by the setting in n978

n978 = 0 The optional technology software is disabled


n978 = 1xxx The optional technology software is
temporarily enabled.
n978 = 2000 The optional technology software is enabled.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C.18 DC Drives Block Diagram Overview

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.19 AC Drives Parameterization steps

If the exact application condition of the unit is not known,


the parameter reset to the factory setting is suggested.
Detailed parameterization should always be used on initial
start-up.

• Power section definition.

• Board definition.

• Drive definition.

• Function adjustment.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.20 Parameter reset to factory setting
The factory setting is the defined initial state of all parameters of a
unit. The parameters for defining the power section and for releasing
the technology options and the operating hours counter and fault
memory are not changed by a parameter reset to factory setting.
PROCEDURE
Grant parameter access

Select “Fixed settings” menu

Select desired factory setting

Start parameter reset

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.21 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.22 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.23 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.24 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.25 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.26 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.27 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.28 DRIVE CONFIGURATION BLOCK DIAGRAM

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.29 Drive definition

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.30 Calculation motor model

1. Automatic parameterization. Calculation of parameters for v/f


open-loop control and closed-loop control from the rating plate
data of the motor.
2. Motor data identification at standstill. As pos. 1 without
setting the n/f controller, including ground fault test.
3. Complete motor data identification. Contain pos. 1, 2, 4, 5,
7, specific for vector control configuration.
4. No-load measurement.
5. n/f controller optimization.
6. Self-test. Correspond to pos. 2, but no parameters are
changed.
7. Tachometer test.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.31 Free blocks parameterization

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.32 ProfiBus communication

Data transfer from the PROFI BUS master to the drive.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.33 ProfiBus communication

U734.01
U734.02
...
U734.10

Data transfer from the drive to the PROFI BUS master.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.34 R.R.U. unit
Rectifier/Regenerative Unit include same concepts of Master Drive.
“Control Words” and “Status Words” are still present. To parameterize,
two different procedures are available, the “standard application” and
the “Expert application”.
Control word 1 Control word 2
Bit 0 On Command Bit 16
Bit 1 OFF2 Pulse disable Bit 17
Bit 2 Always high Bit 18 RDS bit 0
Bit 3 Operating conditions Bit 19 RDS bit 1
Bit 4 Always high Bit 20
Bit 5 Always high Bit 21
Bit 6 Always high Bit 22
Bit 7 Edge fault acknowledgement Bit 23 12-pulse mode select
Bit 8 Inching bit 0 Bit 24
Bit 9 Inching bit 1 Bit 25
Bit 10 Control request Bit 26 External fault 2
Bit 11 Ud reduction request Bit 27 Master/slave drive
Bit 12 Regenerating enable Bit 28 External alarm 1
Bit 13 External fault 3 Bit 29 External alarm 2
Bit 14 Motoring Bit 30 Select BICO data set
Bit 15 External fault 1 Bit 31 HS Check back signal

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.35 R.R.U. parameterization “standard application”

P050 = Language

P051 = 2 Access stage 2 = standard mode

P053 = Parameterization enable 6 = PMU and serial interface

Operator control

Commands Yes
via OP1?

No P554 = 2001 Source for control command ON/OFF1

P555 = 2001 Source for control command OFF2

P052 = 5 Function select 5 = drive setting

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.36 R.R.U. parameterization “standard application”

P071 = Supply voltage

Mode variants

Regen. No
Transformer?

Yes
No Permanent
reduction?

Yes

P571 = 0001 Reduce DC volt 1 = permanent Ud reduction

DC link forming
Idle time Yes
of converter
>1 year

No P408 = Forming time [1.0 ÷ 600.0 minutes]

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.37 R.R.U. parameterization “standard application”
DC link forming
P052 =20
P Key Function selection 20 = forming of DC link
Switch-on

Forming

r000≤°009 Operation display

Wait to
Ud<50V

Circuit identification

P052=21 r949.i009=? Fault value (first acknowledge)


P Key
Switch-on
r000≤°009 Operation display

Identification
Acknowledge
Function selection 21 = Circuit identification

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.38 R.R.U. parameterization “standard application”
Circuit identification

Eliminate
Cause of fault

Yes
Fault message

No Documenting the settings

r000≤°009 Operation display

P052 = 22 Function selection 22 = Display parameters with modified values

Logbook

P052 = 0 Function selection 0 = Return

Ready

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.39 R.R.U. parameterization “expert mode”

More parameterization possibilities are available selecting parameter


P51 = 3 (expert mode).

• Factory setting. Used to reset the parameter values.


• Hardware configuration. Used to select option boards (SCB, CB,
TB)
• Drive setting. Used to change the drive setting system data.
• Initialization. Used to change the rectifier/regenerative unit MLFB.
• 12 pulse mode.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.40 Technology Board

Also the T100 technology board is characterized by the free


configurability of the available function blocks. It performs
various process-related functions depending on the
installed software module. A software module must be
ordered separately and is required to operate the T100.

This document contains proprietary information of Danieli Automation S.p.A. not disclosable, not reproducible. All Rights Reserved
C. START UP
C.41 Process data exchange