FYP 2 PRESENTATION

OPTIMAL LOCATION AND SIZING FOR


PHOTOVOLTAIC PANEL FOR DISTRIBUTION
GENERATION
OBJECTIVE

• Investigate the relationship between placement and sizing


of the DG with
• Total Power Loss of the System
• Voltage Profile of the System
• To find the optimal placement and sizing of the DG
METHODOLOGY
Run the Base Case without DG
using NR load Find out the
After Load flow Identify the
flow using MATLAB software optimum location for approximate losses for each bus
and calculate the bus voltage by placing DG using given
each bus by
magnitude, and Real Power equation
Respectively

Locate the bus at which the loss


is minimum after
Find out the approximate losses
DG placement and this is the Check for Constraint Violation
for each bus by placing DG at
optimum location after DG placement.
the corresponding location.
for DG.

Find optimal size & Run Record the Voltage Profile and
simulation total power loss of the System
• The simulation is tested on the 26 bus arrangement test system by Hadi Saadat
Text Book
• Base case of the simulation is simulated and is used as the comparison for each
simulation
• Each simulation is conducted by introducing a 30MW real power injection on
each bus one by one as solar power only cater Real Power generation and the
total power loss and voltage profile is recorded
• The optimal placement is chosen by picking the placement of DG which
improves the total power loss of the system.
• The optimal size is chosen using matlab coding between the size of 20MW to
50MW by referring to the constrain total power loss.
CONSTRAINTS

Voltage Constraint For Simulation

0.95 p.u. <Vpu<1.05

No of DG Constraint For Simulation


0 unit<DG<1 unit
RESULT AND DISCUSSION
BUS NE TWORK SYS TEM
LOAD DATA
Bus No Load (MW) Bus No Load (MW)
1 51 14 30
• Real power load : 1332 MW 2 22 15 70
3 64 16 60
• Branches : 46
4 25 17 78
5 50 18 165
6 76 19 80
7 0 20 48
8 0 21 46
9 89 22 55
10 0 23 30
11 25 24 80
12 89 25 28
13 31 26 40
BASE CASE

• BASE CASE TOTAL SYSTEM POWER LOSS: 18.174 MW


CASE WITH DG PLACEMENT

BUS • BASE CASE TOTAL POWER LOSS TOTAL POWER LOSS CHANGE IN POWER LOSS PERCENTAGE CHANGE (%)

18.1074 Increase +2.25


1 18.5155

18.1074 Decrease -0.67


2 17.9856

18.1074 Decrease -2.13


3 17.7212

18.1074 Decrease -0.93


4 17.9389

18.1074 Increase +5.16


5 19.0424

18.1074 Decrease -0.52


6 18.0137

18.1074 Decrease -1.09


7 17.9095

18.1074 Decrease -1.06


8 17.9157

18.1074 Decrease -1.88


9 17.7668

18.1074 Decrease -2.38


10 17.6756

18.1074 Decrease -0.23


11 18.0666

18.1074 Decrease -1.45


12 17.8444
BUS BASE CASE TOTAL TOTAL POWER CHANGE IN PERCENTAGE CHANGE (%)
POWER LOSS LOSS POWER LOSS

13 18.1074 18.1725 Increase -0.36

14 18.1074 17.9918 Decrease -0.64

15 18.1074 17.9918 Decrease -0.64

16 18.1074 17.6561 Decrease -2.49

17 18.1074 18.3956 Increase +1.59

18 18.1074 18.2624 Increase +0.86

19 18.1074 17.5255 Decrease -3.21

20 18.1074 17.4661 Decrease -3.54

21 18.1074 17.7335 Decrease -2.06

22 18.1074 17.3213 Decrease -4.34

23 18.1074 17.1579 Decrease -5.24

24 18.1074 16.9099 Decrease -6.61

25 18.1074 17.3503 Decrease -4.18

26 18.1074 18.4052 Increase +1.64


• When the 30 MW DG is introduced at bus 1,5,13 ,17 and 26 , the total system
power loss has increased.
• DG placement at bus 5 shows the worst case as it increases the total power
system loss by 5.16 %
• The highest power loss increase is recorded at 19.0424 MW compared to base
power loss at 18.1074 MW
• The best placement is recorded to be at bus 24 as it improves the total power
system loss by 6.61%
• This improves the total power loss from 18.1074 MW to 16.9099 MW
COMPARISON OF
WORST PLACEMENT WITH BASE
VOLTAGE PROFILE
CASE

BEST PLACEMENT WITH BASE Voltage Profile Base case VS DG at bus 5


CASE 1.06

Voltage Profile of Base Case vs Bus 24 1.04

1.06
1.02

1.04
1

1.02
0.98

1
0.96

0.98
0.94
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

0.96
Base case Dg at bus 5

0.94
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Base Case DG at Bus 24

Although the voltage profile decreases minorly ,


it still did not violate the voltage profile
constraint of 0.95<V<1.05 p.u.
SIZING

• Sizing of DG is done by algorithm coding


• No of interation : 1000
• No of population : 20
• MW constraint : 30MW <PgenDG <50MW
• PowerLossSystem < 16.9099 MW
• DG is placed at bus 24 and simulated
S I M UL AT I ON R E S U LT

Population DG Size (MW) Total Power Loss


1.0000 48.6939 16.0908
2.0000 48.6939 16.0908
3.0000
4.0000
48.6939
48.6939
16.0908
16.0908
Based on the
5.0000
6.0000
48.6938
48.6938
16.0908
16.0908 simulation the best
7.0000
8.0000
48.6938
48.6938
16.0908
16.0908 Size for the PV DG
9.0000 48.6938 16.0908
10.0000 48.6938 16.0908 will be 48.6938 MW
11.0000 48.6938 16.0908
12.0000 48.6938 16.0908
13.0000 48.6938 16.0908
14.0000 48.6938 16.0908
15.0000 48.6938 16.0908
16.0000 48.6938 16.0908
17.0000 48.6938 16.0908
18.0000 48.6938 16.0908
19.0000 48.6938 16.0908
20.0000 48.6938 16.0908
21.0000 48.6938 16.0908
CONCLUSION

• The best bus for the placement of the PV DG is at bus 24


• The optimal sizing will be 48.6938 MW
• The placement of the DG can bring negative and positive effect to the
overall system as it increases and decreases the total power loss of the
system
• The voltage profile decreases from the base case but only in a small
difference in this test system but did not violate any constrains.
FUTURE WORK

• Comparison of two simulation software EX: PSSE & GAMS


• Simulation which include the involvement of the photovoltaic power electronic
component and real day simulation of irradiation.
• Simulation based on real local utility network for more realistic approach.
• Simulation on combination of multiple PV DG and other type of DG.
THANK YOU