City Multi: Troubleshooting
City Multi: Troubleshooting
Error Code
Error units
address
Easy & Convenient Diagnosis Function
Error Code &
Units address
shows
ERROR HISTORY & TEST RUN
SW1
Self diagnosis mode
SW1
Error History (Latest)
SW1
Error Details of
inverter (Latest)
SW3 SW5 SW4 SW3 SW2 SW1
Test Run
ERROR Code
Error Pre-Error Error detail Error code definitionSearched
Code code code units
1102 1202 - Discharge temp error O/U
1302 1402 - High pressure fault O/U
1500 1600 - Refrigerant O/U
overcharge
- 1605 - Preliminary suction O/U
pressure fault
2500 - - I/U
2502 - - I/U
2503 - - I/U
4250 - 101 O/U
- 104 O/U
- 105 O/U
- 106 O/U
- 107 O/U
51** - - Temp sensor fault O/U, I/U
1102(1202) – If TH4 (O/U) of 120'C or higher is detected
Valve closed
Sensor failure
1302(1402) – If 63HS (O/U) of 3.87(3.78)MPa or higher is detected
Cause, check method and remedy
Valve closed
Valve closed
Sensor failure
Power failure
1500(1600) – If TdSH (O/U) of 10 degC or lower is detected
* TdSH = TH4 – Satulated temp of 63HS
Gas overcharged
Sensor failure
Sensor failure
Valve broken
4250 – Overcurrent / IPM error
Dip switch
Address setting
Outdoor unit
Dip switch
Dip switch
MNT Tool
SW1
(1) While the unit is stopped, compare the gauge pressure and the
pressure on LED or MNT-tool.
1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal
pressure is caused due to gas leak.
2) When the pressure displayed on LED is between 0 and 0.098MPa [14psi],
the connector may be defective or be disconnected.
Check the connector and go to (4).
3) When the pressure displayed on self-diagnosis LED1 exceeds 4.15MPa
[601psi], go to (3).
4) If other than 1), 2) or 3), compare the pressures while the sensor is
running. Go to (2).
High-Pressure Sensor (63HS1)
(2) Compare the pressure gauge and the pressure displayed on LED
while the unit is running. (Compare them by MPa [psi] unit.)
1) When the difference between both pressures is within 0.098MPa [14psi],
both the high pressure sensor and the control board are normal.
2) When the difference between both pressures exceeds 0.098MPa [14psi],
the high pressure sensor has a problem. (performance deterioration)
3) When the pressure displayed on LED does not change, the high pressure
sensor has a problem.
High-Pressure Sensor (63HS1)
(4) Displug the high-pressure sensor from the control board, and
short-circuit between the No.2 and 3 connectors (63HS1) to
check the pressure on LED or M-tool.
1) When the pressure displayed on the self-diagnosis LED1 exceeds 4.15MPa
[601psi], the high pressure sensor has a problem.
2) If other than 1), the control board has a problem.
MNT Tool
SW1
(1) While the sensor is stopped, compare the gauge pressure and
the pressure displayed on self-diagnosis LED1.
1) When the gauge pressure is between 0 and 0.098MPa [14psi], internal
pressure is caused due to gas leak.
2) When the pressure displayed on self-diagnosis LED1 is between 0 and
0.098MPa [14psi], the connector may be defective or be disconnected.
Check the connector and go to (4).
3) When the pressure displayed on self-diagnosis LED1 exceeds 1.7MPa
[247psi], go to (3).
4) If other than 1), 2) or 3), compare the pressures while the sensor is
running. Go to (2).
Low-Pressure Sensor (63LS)
(2) Compare the gauge pressure and the pressure displayed on LED
while the sensor is running. (Compare them by
MPa [psi] unit.)
1) When the difference between both pressures is within 0.03MPa [4psi],
both the high pressure sensor and the control board are normal.
2) When the difference between both pressures exceeds 0.03MPa [4psi],
the high pressure sensor has a problem. (performance deterioration)
3) When the pressure displayed on LED does not change,
the high pressure sensor has a problem.
Low-Pressure Sensor (63LS)
(4) Remove the low-pressure sensor from the control board, and
short-circuit between the No.2 and 3 connectors (63LS:CN202)
to check the pressure with self-diagnosis LED1.
1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa
[247psi], the low pressure sensor has a problem.
2) If other than 1), the control board has a problem.
(5) Remove the high pressure sensor (63HS1) from the control
board, and insert it into the connector for the low pressure
sensor (63LS) to check the pressure with the self-diagnosis
LED1.
1) When the pressure displayed on the self-diagnosis LED1 exceeds 1.7MPa
[247psi], the control board has a problem.
2) If other than 1), the control board has a problem.
- Check whether the output signal from the control board and the operation
of the solenoid valve match.
- Setting the self-diagnosis switch (SW1) as shown in the figure next slide
causes the ON signal of each relay to be output to the LED's.
- Each LED shows whether the relays for the following parts are ON or OFF.
LEDs light up when relays are ON. (*SV5b is closed when the relays are ON)
Note:
When a valve malfunctions, check if the wrong solenoid valve coil is not
attached the lead wire of the coil is not disconnected, the connector on the
board is not inserted wrongly, or the wire for the connector is not
disconnected.
Solenoid Valve
ON signal of each relay to Upper
be output to the LEDs
Lower
SW1
Solenoid Valve
sound.
2) To check whether the valve is open or closed, check the change of the
SV1a downstream piping temperature while the valve is being powered.
Even when the valve is closed, high-temperature refrigerant flows inside
the capillary next to the valve.
(Therefore, temperature of the downstream piping will not be low with the
valve closed.) Checked by down stream piping
temp while SV1a being powered
Solenoid Valve
- To check the revolution of the fan, check the inverter output state on the
self-diagnosis LED, as the inverter on the outdoor fan controls the
revolutions of the fan.
- When starting the fan, the fan runs at full speed for 5 seconds.
- When setting the DIP SW1 as shown in the figure below, the inverter output
[%] will appear. 100% indicates the full speed and 0% indicates the
stopping.
- As the revolution of the fan changes under control, at the interphase or
when the indoor unit operation capacity is low, the revolution of the fan
may change.
- If the fan does not move or it vibrates, Fan board problem or fan motor
problem is suspected. Refer to IX [4] -6- (2) [5] "Check the fan motor
ground fault or the winding."(page 235 in YHA service handbook) and IX [4]
-6- (2) [6] "Check the Fan board failure."(page 236 in YHA service
handbook)
LEV (Indoor LEV / Outdoor LEV1 / Outdoor LEV2)
Malfunction Judgment method Remedy Target
mode LEV
Microcomputer Disconnect the control board connector and When the drive I/U
driver circuit Connect the check LED as shown in the circuit has a O/U
failure Figure below. problem,
replace the
resistance : 0.25W 1k control board.
LED : DC15V 20mA
or more
When the main power is turned on, the
indoor unit circuit board outputs pulse
signals to the indoor unit LEV for 10
seconds, and the outdoor unit circuit board
outputs pulse signals to the outdoor unit
LEV for 17 seconds.
If any of the LED remains lit or unlit, the
drive circuit is faulty.
LEV (Indoor LEV / Outdoor LEV1 / Outdoor LEV2)
Malfunction Judgment method Remedy Target
mode LEV
LEV If the LEV is locked, the drive motor Replace the I/U
mechanism runs idle, and makes a small clicking LEV. O/U
is locked sound. When the valve makes a closing
and opening sound, the valve has a
problem.
Disconnected Measure the resistance between coils Replace the I/U
or short- with a tester, and check that the LEV. O/U
circuited LEV resistance is in the range of 150 ohm (LEV2)
motor coil
±10%.
Measure resistance between the coils Replace the I/U
using a tester. They are normal if LEV. O/U
resistance is 46 ohm ±3%. (LEV1)
LEV (Indoor LEV / Outdoor LEV1 / Outdoor LEV2)
Malfunction Judgment method Remedy Target
mode LEV
Incomplete Run the target indoor unit in the fan If there is a I/U
sealing (leak mode, and the other indoor units in the large amount
from the cooling mode. of leakage,
valve) Then, check the liquid temperature replace the
(TH22). If the temperature is extremely LEV.
low compared with the inlet
Temperature displayed on the remote
controller, the LEV is not properly
sealed, however, if there is a little leak,
it is not necessary to replace the LEV
when there are no effects to
Other parts.
LEV (Indoor LEV / Outdoor LEV1 / Outdoor LEV2)
Malfunction Judgment method Remedy Target
mode LEV
Faulty wire 1. Check for loose pins on the Check the I/U
connections connector and check the colors of continuity at O/U
in the the lead wires visually the points
connector or 2. Disconnect the control board's where an error
faulty contact connector and conduct a continuity occurs.
check using a tester.
Inverter (Compressor / Fan motor)
2) Close BV2
5) Close BV1
Tc TH6
SW1
Refrigerant Leak
- Leak Spot: In the case of outdoor unit (Cooling season)
3. Stop all the indoor units, and stop the compressor.
1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when
SW3-1 on the outdoor control board is ON.
2) Check that all the indoor units are being stopped.
4. Close the service valves (BV1 and BV2).