Professional Documents
Culture Documents
Area Hazard Analysis: Example of Possible Approach
Area Hazard Analysis: Example of Possible Approach
HVAC
duct
above
Isolation
Penetration Valve
B11
Methodology
• Functions identified for system or area to be studied
• Equipment contributing to these functions identified
• Initiating events (RPrS) assumed to occur and impact onto functions determined
• Specific mitigation requirements were identified and then generic guidelines
developed
ti on
a
pe netr
p i ng
pi
74 B2
11- B
to B
pli e d
ap
f A HA
pl e o
Exam
Notable guidelines extracted from AHA
• For non-combustible pipes, without open ends, below the size that pipes
are considered to behave as ducts, isolation valves are not automatically
required. The drivers for isolation valves are related to the ability to
common pipe rupture on both sides of a penetration due to a postulated
event or combination
SL2 Penetration pipe between isolation valves shall be designed to withstand SL2
LD Systems above shall have same seismic rating, or be demonstrated not to collapse in seismic event (but may fail to
function) or sufficient dropped load protection provided between penetration and first isolation valve (note that if
no isolation valves exist then the whole line shall be protected) #1
FP2 FP1 plus fire protection of isolation valves body and any pipe between valve and first support #3
FP3 FP1 or FP2 plus fire protection of valve actuators and the full chain #3
FL Demonstration that static pressure associated with flooding level can be withstood by infilling
U Valve, actuator and full chain below flooding level to be functional underwater
Notes and Schema
#1 Does this criteria conflict with implemented design for compressed air tubing
#2 What are the factors (materials, size, fluid, etc.) that specify that a pipe behaves as
a duct and hence enables fire propagation across penetration
#3 schema of possible configurations for protection against fire:
FC FC
FP1:
FC FC FC FC
FP2:
FP3:
Worked Example
HCC Non- Highest seismic System No valves Valve(s) Valves DUCT Below FL+FP3
HCC rating not Above or Valves on one one side flooding
propagated on both side and not level
throughout sides fail closed
system
FP0 or
SL3 SL2 V LD FP1 FP2 FP3 FL U
V+FP2
X X X
6211B2-TW- SL3 for HVAC
0145 / 0001 X penetration, SL2 above one Valves on
both sides
rest of system side
• Penetration requires fire protection from penetration to first support only, the valves,
which are distant from the penetration do not require fire protection
• HVAC duct crosses above the penetration on one side only hence failure of HVAC
cannot cause bypass of penetration through the pipe. HVAC must be demonstrated not
to cause excessive action on penetration infilling in the event of failure onto
penetration pipe
Next Steps
• Agreement on approach
• Other penetrations
– Cables, busbars
– Ducts
– Transmission lines
– Special cases (NBI penetrations, etc..)
• Comparison with what has been implemented
in the PBS
• Commence with L2
Next Steps
• Kick off meeting to be organised mid-Jan for L2. MOE
• Identify the penetrations and the related equipment on
L2
– Emmanuel Carlier to be contacted. CHL
• System engineers to perform high level analysis of the
relevant safety functions. ZWG/RRA
– documentation identification + critical analysis. SCI
– Clarification of the relevant functions
• Discuss with PBS 31 regarding the PC penetrations. CHL