Professional Documents
Culture Documents
Heating, Ventilation An D Air Conditioning (Hva C) System
Heating, Ventilation An D Air Conditioning (Hva C) System
N 02 REFRIGERATION CYCLE
T
E 03 TECHNICAL STANDARD
N
04
T TYPICAL DESIGN CONSIDERATION
S
HVAC SYSTEM BASIC
INTRODUCTION
Building ventilation is the process The main purpose of ventilation is
of bringing outdoor air into a to provide acceptable indoor air
building, circulating it, and later quality by diluting and removing
purging it to the environment. contaminants from the indoor air.
A B
1 - Supply duct
2 - Fan compartment
3 - Flexible connection
4 - Heating or cooling coil
5 - Filter compartment
6 - Return and fresh air duct
REFRIGERATION CYCLE
Refrigeration Flow Sheet
FIRE DAMPERS
2. PTS 50.013 - Handling, Storage and 8. PTS 33.10.00.31 - Symbols and Identification
Preservation of Materials/Equipment System Electrical
3. PTS 20.085 - The Design and Installation 9. PTS 31.10.00.31 - Noise Control
of Ventilation and Air Conditioning Systems 10. PTS 31.76.10.11 - Installation, Testing, and
Offshore Balancing and Commissioning of HVAC
4. PTS 30.31.00.32 - Instrumentation for Systems
Measurement and Control
11. PTS 32.31.09.31 - Instrumentation for
5. PTS 32.37.20.10 - Instrument Signal Lines Equipment Packages
6. PTS 31.76.10.10 - Heating Ventilation and 12. PTS 33.66.05.31 - Electric Motor Cage
Air Conditioning for Plant Buildings Induction and Synchronous Type
13. PTS 20.142 - Painting and Coating of 20. BS 5422 - Specifications for the use of
Offshore Facilities Thermal Insulating Materials
14. BS 848 - Part 1 - Methods of Testing 21. SMACNA - HVAC Duct Construction
Performance Standards - Metal and Flexible
15. BS 2831 - Methods of Test for Air filters
used in Air-Conditioning and General 22. SMACNA - HVAC Systems
Ventilation - Testing, Adjusting and Balancing
02BS 4718 - Methods of Test for Distribution
16. 23. SOLAS - Sections on Ventilation
Systems Trunking Passing Through Bulkhead and
03BS 4856 - Methods for Testing & Rating
17. Class of Bulkheads
Fan Coil Units, Unit Heaters & Unit Coolers
24. ASHRAE - Standard 62.1-2007
18. BS 5141 - Air Heating & Cooling Coils
04
19. BS 5345 - Selection, Installation & Maintenance
25. ASHRAE - Standard 55-1992
(with 1995 Addenda) Thermal Environmental
of Electrical Apparatus for use in Potentially
Conditions for Human Occupancy
Explosive Atmosphere
TYPICAL DESIGN CONSIDERATIONS
1. In Malaysian waters , typically the environmental conditions for which the HVAC
skids and equipment are designed including :
40 – 100 %. 39 m/s.
Internal Room Condition Room Overpressure
24 ℃ / 65 % Relative Humidity. 30 Pa
2. Environmentally harmful refrigerants such as R-22 are not
used. The recommended refrigerant is HFC - 134 a.
3. HVAC Systems are usually designed for reliability and safety, particularly of the
equipment and controls. The location is considered and also the impact on maintenance and
replacement.
4. The operation of the HVAC system shall be fully integrated with the electrical, instrumentation, fire
and gas detection and protection systems to provide a safe environment under all foreseeable operating
conditions.
5. A Direct Expansion ( DX ) System with 100% backup capacity shall provide air
conditioning to the area that requires air-conditioning.
6. The condensing unit shall be controlled on the principle of average supply air
temperature
7. The temperature shall be regulated by a temperature control system located in the
return air supply. The settings of the temperature control system located in the condensing
unit shall be site adjustable.
8. Duct heaters shall be individually controlled by solid -state temperature sensors in the
air-conditioned rooms. Duct heaters shall be sized to maintain the room condition
within the design range during part load operation.
9. Fire dampers shall be installed as per the requirements of SOLAS to maintain the
integrity/fire rating of any walls or partitions where duct penetration is required to be made.
HVAC ducts shall not penetrate any blast wall.
10. Noise levels within rooms being air-conditioned are typically 65 dB . The minimum
number of air changes within rooms being air conditioned is typically 12 air changes per
hour.
1 HVAC system
operation and
fire protection TYPICAL DESIGN C
devices;
such as fire
ONSIDERATIONS
dampers shall 2Noise limits for
be developed
in accordance HVAC equipment
are as follows;
in a safe area
4 away from the
Fresh air inlets to
Air Cooled exhaust of other
with the
enclosures shall be
Condensing Units equipment such
requirements & Air Handling
located
as
of the Safety, Units: 80 dB turbines.
Fire and Gas
Detection and to minimise the
FGS Alarm and
3 The location effect of wind
Shutdown
Philosophies of inlet/outlet on the HVAC
openings are selected system
Enclosed spaces that are being air-conditioned shall be The design of the HVAC
maintained at a minimum of +0.3 mbarg over-pressure system shall comply with
with respect to the surrounding atmosphere. Over- the requirements of the
pressurisation shall be avoided by the use of pressure platform safety philosophy.
relief dampers. Care must be taken to
1 ensure that the following
are provided for the
detection of gas/smoke:
2
Gas detection at
all fresh air
intakes from the
TYPICAL DESIGN atmosphere
Smoke
CONSIDERATIONS detection
where
applicable
All equipment , accessories, Major equipment such as AHU and ACCU
wiring , piping located outdoor shall shall be mounted on a structural steel skid
incorporate all necessary in accordance with
weatherproofing and PTS 30.48.00.31-P
protection for installation or other acceptable standard.
The ACCU is typically an air-cooled unit with direct it is skid mounted and suitable
drive fans. for year round outdoor
operation in a corrosive salt-
laden
The condenser section shall include the Marine environment.
coil assembly constructed of seamless
copper tubing with copper fins. The coil
shall be tested according to BS 5141. The ACCU fans shall be direct
driven anti-static propeller type
with low noise levels.
TYPICAL DESIGN CONSIDERATION
The fans are normally
equipped with a
The AHU is typically a complete and backdraft damper to
integral unit equipped with centrifugal prevent short circuit of airflow
fans, evaporator coil, motors, filters etc..