Professional Documents
Culture Documents
Presentation 2
Presentation 2
Presentation 2
By: Gashaw A.
March 17,2020 1
Brainstorming
March 17,2020 2
Objectives
March 17,2020 3
DRY AND ATMOSPHERIC AIR
Air in the atmosphere normally contains some
water vapor (or moisture) and is referred to as
atmospheric air.
Atmospheric air is the most commonly
encountered gas–vapor mixture in practice.
Air that contains no water vapor is called dry air.
Although the amount of water vapor in the air is
small, it plays a major role in human comfort.
Therefore, it is an important consideration in air-
conditioning applications.
March 17,2020 4
The temperature of air in air-conditioning
applications ranges from about -10 to 50°C.
In this range both dry air and atmospheric air
(including water-vapor) can be treated as
ideal gas, with negligible error. Thus the
ideal-gas relation Pv = RT can be applied.
The partial pressures of atmospheric air are:
March 17,2020 5
The enthalpy of dry-air with cp = 1.005
kJ/kg.°C (in the range of interest) ; one
obtains:
March 17,2020 7
Consider 1 kg of dry air. By definition, dry air
contains no water vapor, and thus its specific
humidity is zero.
Now let us add some water vapor to this dry
air. The specific humidity will increase.
As more vapor or moisture is added, the
specific humidity will keep increasing until
the air can hold no more moisture.
At this point, the air is said to be saturated
with moisture, and it is called saturated air.
March 17,2020 8
• The relative humidity is defined as the
ratio of the mass of the water vapor to the
maximum amount of water vapor the air
can hold at the same temperature.
March 17,2020 9
The relative humidity ranges from 0 for dry
air to 1 for saturated air.
Note that the amount of moisture air can
hold depends on its temperature. Therefore,
the relative humidity of air changes with
temperature even when its specific humidity
remains constant.
March 17,2020 10
ENTHALPY OF ATMOSPHERIC AIR
March 17,2020 11
The enthalpy of water-vapor in atmospheric air
can be considered as saturated vapor,
hv = hg ; Hence:
But ha = CpT
Hence, h = CpT + ω hg
March 17,2020 12
DEW-POINT TEMPERATURE
March 17,2020 13
Example:
•1. The air at 25and 100kpa in a 150 room has a
relative humidity of 60%. Calculate (a) the
humidity ratio, (b) the dew point, (c) the mass of
water vapor in the air, and (d) the mole fraction
of the water vapor.
March 17,2020 14
2. An air-conditioning unit is shown in Fig.
below with pressure, temperature, and relative
humidity data. Calculate the heat transfer per
kilogram of dry air, assuming that changes in
kinetic energy are negligible.
March 17,2020 15
ADIABATIC SATURATION
Adiabatic saturation process is a process used to
determine the absolute or relative humidity.
The system consists of a long insulated channel
that contains a pool of water.
A steady stream of unsaturated air that has ω1
(unknown) and T1 is passed through this channel.
March 17,2020 16
As the air flows over the water, some water
evaporates and mixes with the airstream.
The moisture content(ω) of air increases during
this process, and its temperature decreases,
since part of the latent heat of vaporization of
the water that evaporates comes from the air.
If the channel is long enough, the airstream
exits as saturated air (ø = 100%) at temperature
T2, which is called the adiabatic saturation
temperature.
March 17,2020 17
The process involves no heat or work
interactions, and the kinetic and potential energy
changes can be neglected.
Then the conservation of mass and conservation
of energy relations for this two-inlet and one-exit
steady-flow system reduces to the following:
Mass balance:
Energy balance:
March 17,2020 19
Thus we conclude that the specific humidity
(and relative humidity) of air can be determined
from the above equations, by measuring the
pressure and temperature of air at the inlet and
the exit of an adiabatic saturator.
The adiabatic saturation process discussed
above provides a means of determining the
absolute or relative humidity of air, but it
requires a long channel or a spray mechanism to
achieve saturation conditions at the exit.
March 17,2020 20
wet-bulb temperature Twb
The temperature of an
air measured by a
thermometer whose
bulb is covered with a
cotton wick saturated
with water. This
temperature is the
same as the adiabatic
saturation
temperature, T2.
March 17,2020 21
Sling Psychrometer: a rotating set of
thermometers one of which measures wet
bulb temperature Twb and the other dry bulb
temperature Tdb which are sufficient to fix the
state of the mixture.
March 17,2020 22
Dry-bulb temperature
dry-bulb temperature refers simply to the
temperature that would be measured by a
thermometer placed in the mixture. Often a
wet-bulb thermometer is mounted together
with a dry-bulb thermometer to form an
instrument called a psychrometer.
March 17,2020 23
In general, the adiabatic saturation temperature
and the wet-bulb temperature are not the same.
However, for air–water vapor mixtures at
atmospheric pressure, the wet-bulb temperature
happens to be approximately equal to the
adiabatic saturation temperature.
Therefore, the wet-bulb temperature Twb can be
used in the above Eq in place of T2 to
determine the specific humidity of air.
March 17,2020 24
Example
March 17,2020 25
2. The air in a room has a dry-bulb
temperature of 22°C and a wet-bulb
temperature of 16°C. Assuming a pressure of
100 kPa, determine
(a) the specific humidity,
(b) the relative humidity, and
(c) the dew-point temperature.
March 17,2020 26
THE PSYCHROMETRIC CHART
and
PSYCHROMETRIC PROPERTIES
March 17,2020 27
Common properties used in the
Psychrometric chart includes
dry-bulb temperature Tdb
wet-bulb temperature Twb
relative humidity (ø, RH)
humidity ratio, ω
specific volume, v
dew point temperature Tdp
enthalpy, h
March 17,2020 28
The chart which is most commonly used is the
ω-t chart, i.e. a chart which has specific
humidity or water vapor pressure along the
ordinate and the dry bulb temperature along
the abscissa.
The chart is normally constructed for a
standard atmospheric pressure of 760 mm Hg
or 101.325 Kpa, corresponding to the pressure
at the mean sea level.
March 17,2020 29
March 17,2020 30
CONSTANT PROPERTY LINES ON A
PSYCHROMETRIC CHART
March 17,2020 31
1. Saturation Line (ø=100%)
March 17,2020 32
March 17,2020 33
2. Relative Humidity Lines
March 17,2020 34
March 17,2020 35
The lines on psychrometric chart for any other
desired value of RH can be constructed as
follows.
1. At the given Tdb find pv corresponding to
RH=100% which is psat@T.
2. Pv for the new RH is obtained by multiplying the
new RH by the Pv corresponding RH=100%.
• Then find ω using the new Pv ;
March 17,2020 37
3. Constant Specific Volume Lines
March 17,2020 38
4. Wet Bulb Temperature Lines
The wet bulb temperature lines are inclined straight
lines and non-uniformly spaced as shown in Figure.
The values are read on the saturation curve following
the inclined straight lines.
Any point on the saturation curve have the same dry
bulb and wet bulb temperature values.
March 17,2020 39
5. Constant Enthalpy Lines
The enthalpy lines are inclined straight lines and
uniformly spaced as shown in Figure. These lines are
parallel to the wet bulb temperature lines, and are drawn
up to the saturation curve. Some of these lines coincide
with the wet bulb temperature lines also.
The values of total enthalpy are given on a scale above the
saturation curve as shown in the Figure.
March 17,2020 40
Example
The air in a room has a pressure of 1 atm, a dry-bulb
temperature of 24°C, and a wet-bulb temperature of
17°C.Using the psychrometric chart, determine
(a) the specific humidity,
(b) the enthalpy (in kJ/kg dry air),
(c) the relative humidity,
(d)the dew-point temperature, and
(e) the specific volume of the air (in m3/kg dry air).
March 17,2020 41
HUMAN COMFORT AND AIR-CONDITIONING
March 17,2020 45
And disregarding the kinetic and potential
energy changes, the steady-flow energy
balance relation can be expressed in this
case as
March 17,2020 46
Simple Heating and Cooling
(ω = constant)
• Heating
March 17,2020 47
Cooling
March 17,2020 48
where h1 and h2 are enthalpies per unit mass of dry
air at the inlet and the exit of the heating or cooling
section, respectively.
March 17,2020 49
Heating with Humidification
March 17,2020 50
If steam is introduced in the humidification section, this will
result in humidification with additional heating (T3 > T2).
If humidification is accomplished by spraying water into the
airstream, part of the latent heat of vaporization comes from the
air, which results in the cooling of the heated airstream (T3 <
T2). Air should be heated to a higher temperature in the heating
section in this case to make up for the cooling effect during the
humidification process.
March 17,2020 51
Cooling with Dehumidification
March 17,2020 52
If the cooling section is sufficiently long, air
reaches its dew point (state x, saturated air).
Further cooling of air results in the
condensation of part of the moisture in the air
March 17,2020 53
Evaporative Cooling
Cooling in hot, relatively dry climates can be
accomplished by evaporative cooling.
This process is based on a simple principle:
As water evaporates, the latent heat of
vaporization is absorbed from the water body
and the surrounding air. As a result, both the
water and the air are cooled during the
process.
March 17,2020 54
Adiabatic Mixing of Airstreams
March 17,2020 55
The mass and energy balances for the adiabatic
mixing of two airstreams reduce to
March 17,2020 56
when two airstreams at two different states (states 1 and 2)
are mixed adiabatically, the state of the mixture (state 3)
lies on the straight line connecting states 1 and 2 on the
psychrometric chart, and the ratio of the distances 2-3 and
3-1 is equal to the ratio of mass flow rates ma1 and ma2.
March 17,2020 57
COOLING TOWERS
March 17,2020 58
An induced-draft counter-flow cooling tower A natural-draft cooling tower.
March 17,2020 59
Example
March 17,2020 61
• Air
2. at 38and 10% relative humidity enters an
evaporative cooler with a volumetric flow rate of
140 m3/min. Moist air exits the cooler at 21. Water
is added to the soaked pad of the cooler as a liquid
at 21and evaporates fully into the moist air. There is
no heat transfer with the surroundings and the
pressure is constant throughout at 1 atm. Determine
(a)the mass flow rate of the water to the soaked
pad, in kg/s, and
(b)the relative humidity of the moist air at the exit
to the evaporative cooler
March 17,2020 62
March 17,2020 63
2. The cooling water from the condenser of a power
plant enters a wet cooling tower at 40°C at a rate of 90
kg/s. The water is cooled to 25°C in the cooling tower
by air that enters the tower at 1 atm, 23°C, and 60
percent relative humidity and leaves saturated at 32°C.
Neglecting the power input to the fan, determine
(a) the volume flow rate of air into the cooling tower
and (b) the mass flow rate of the required makeup
water.
March 17,2020 64
March 17,2020 65