Intelligent Control Panel SLC

HONEYWELL BUILDING SOLUTIONS


04-0001-1
NFPA Style 4 SLC
M M M

Branch Line Resistor from End of Line to FACP


Shall Not Over 50 ohms per Branch

M M M

5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG)

M M M

Twisted Unshielded Pair 12 to 18 AWG


SLC Distance
12 AWG 3810 M 16 AWG 1828 M
FACP 14 AWG 2895.6 M 18 AWG 1127 M

HONEYWELL BUILDING SOLUTIONS


04-0001-3
Isolator Application - Style 4 Riser

Max 25 standard devices between Isolators

HONEYWELL BUILDING SOLUTIONS


04-0001-4
NFPA Style 6 SLC
M M

M
M
Loop Resistor from End of
M Line to FACP
Shall Not Over 50 ohms
5000 ft ( 1500 M) for Shield Twisted Pair Cable
M (12 to 18 AWG) M

M M

Twisted Unshielded Pair 12 to 18 AWG


SLC Distance
12 AWG 3810 M 16 AWG 1828 M
14 AWG 2895.6 M 18 AWG 1127 M

HONEYWELL BUILDING SOLUTIONS


04-0001-5
Isolator Application - Style 6

Max 25 standard devices between Isolators

HONEYWELL BUILDING SOLUTIONS


04-0001-6
Style 6 with Isolators
M M

M
M

M M

M M

HONEYWELL BUILDING SOLUTIONS


04-0001-7
Floating Shield

(+) SLC Channel A

no connection

(-) SLC Channel A

NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030

HONEYWELL BUILDING SOLUTIONS


04-0001-10
SLC Data Formats

FlashScan is an algorithm that greatly enhances the speed of communication between the
Analog intelligent devices. If one of the devices within a single group has new information,
The panel CPU stops the group poll and concentrates on single points. The net effect is a
response speed greater than five times that of earlier designs.

HONEYWELL BUILDING SOLUTIONS


04-0001-11
LED Operation

CLIP Mode FlashScan Mode


Control Device Standby Activated Standby Activated
Panel
Monitor Module Blink Red Steady Red Blink Green Steady Red
Onyx Panels Control Module Blink Green Steady Green Blink Green Steady Green
Detector Blink Red Steady Red Blink Green Steady Red

FDM-1 Blink Red Steady Red Blink Red Steady Red

HONEYWELL BUILDING SOLUTIONS


04-0001-12
SLC Loop Devices

 A Signaling Line Circuit can contain a variety of devices,


each with a specific function to perform.

 Intelligent Detectors to identify a variety of threat conditions


– various smoke levels, heat, etc.

 Addressable Modules to interface the system to conventional


input/output circuits and devices – notification appliances,
smoke detectors, waterflow and supervisory devices, etc.

 Addressable Pull Stations for manual alarm activation.


These devices actually contain an Addressable Module inside.

 Loop Isolators to prevent total loop failure from a SLC short.

HONEYWELL BUILDING SOLUTIONS


04-0001-13
FlashScan Intelligent Detectors

 FSP-851 Intelligent Photoelectric Detector.


 FSP-851T Intelligent Photo/Thermal Detector.
 FAPT-851 Acclimate™ Intelligent Photoelectric/Thermal Detector.
 FSI-851 Intelligent Ionization Detector.
 FST-851 Intelligent Thermal Detector.
 FST-851R Intelligent Rate-of-Rise Thermal Detector.
 FST-851H Intelligent High-Temperature Thermal Detector.
 FSD-751PL Intelligent Duct Photo Detector - Low-Flow
 FSD-751RPL Intelligent Duct Photo Detector with Relay - Low-Flow
 FSH-751 Intelligent HARSH (Hostile Area Smoke Head) Detector.
 FSL-751 Intelligent Laser Detector, low profile.
 Base Options:
 B501 Intelligent Detector Base without flange.
 B501BP Intelligent Detector Bases, without flange – 10 pack.
 B710LP Intelligent Detector Base with flange.
 B710LPBP Intelligent Detector bases with flange – 10 pack.
 B501BH Intelligent Sounder Base/Assembly.
 B501BHT Intelligent Temporal Sounder/Base Assembly.
 B224BI Intelligent Isolator base.
 B224RB Intelligent Relay base.
 B710HD Intelligent Base for the HARSH Detector.

HONEYWELL BUILDING SOLUTIONS


04-0001-14
FlashScan Monitor Modules

 FMM-1 Addressable Monitor Module. Monitors normally-


FMM-1
open contact type devices on either a Class A or Class B
circuit.
 FDM-1 Addressable Dual Monitor Module, 2 Class B circuits
for normally-open contact type devices.
 FZM-1 Addressable Monitor Module for compatible two-wire
conventional smoke detectors.
 FMM-101 Addressable Mini Module. Monitors a single
normally-open contact type device on a Class B connection.

The FMM-101 can be mounted


inside the enclosure of a
single monitored device.

HONEYWELL BUILDING SOLUTIONS


04-0001-15
FlashScan Control Modules

FCM-1  FCM-1 Addressable Control Module. Configured for one


NFPA Style Y (Class B) or Style Z (Class A) circuit. 24 VDC
power must be supplied. 3-amps max.
 FRM-1 Addressable Relay Module. Provides two Form-C dry
contacts that switch together (DPDT). Use for elevator
recall, damper control, door holding, auxiliary control
functions, etc.
 FTM-1 Addressable Firephone Control Module.**Compatible
with NFS-3030 and NFS-640 with FlashScan Software Ver.
2.0, Ver. 3.0 respectively.

HONEYWELL BUILDING SOLUTIONS


04-0001-16
Addressable Multiple Input Modules
 XP10-M - 10 Class B or Five Class-A Initiating Device
Circuits for normally open alarm contact devices.
 XP6-MA - Six Class B or Three Class A Initiating Device
Circuit Module for Monitoring UL Listed two-wire smoke
detectors (requires filtered, resettable 24 volts.)
XP6-MA
 Mounts in BB-XP backboxes – two modules, surface
mount. Mount up to six modules on a CHS-6 chassis.

HONEYWELL BUILDING SOLUTIONS


04-0001-17
Addressable Multiple Output Modules
 XP6-C Transponder Control Module. six Notification Appliance
Circuits, Class A or B.
 SYNC-1 Synchronization daughter module for XP6-C using
System Sensor appliances.
 XP6-R Transponder Relay Module. Six Form-C Dry Contact
Relays.
 Mounts in BB-XP backboxes – two modules, surface mount.

XP6-C

HONEYWELL BUILDING SOLUTIONS


04-0001-18
NBG-12LX Addressable Pull Station

 Key Resettable Dual Action.


 Can be opened without initiating an alarm condition!
 Addressable Mini-Module mounted inside station.
 Polling LED viewable through front handle.

Addressable
FlashScan
Module

HONEYWELL BUILDING SOLUTIONS


04-0001-19
Isolator Modules

 ISO-X SLC Loop Isolator Module. Isolates against short


circuits on the SLC.

HONEYWELL BUILDING SOLUTIONS


04-0001-20
FlashScan Modules
Break-off address stop
for panels with FlashScan
Mode.

9 6 7 8 9 10
0
5
11
8 4
3 12 1
2 13
1 0 15 14
7 TENS 2
6 789
5
6 4 3
3
2
5 10
ONES
4
LOOP ADDRESS

HONEYWELL BUILDING SOLUTIONS


04-0001-21
HONEYWELL BUILDING SOLUTIONS
04-0001-22
HONEYWELL BUILDING SOLUTIONS
04-0001-23
HONEYWELL BUILDING SOLUTIONS
04-0001-24
HONEYWELL BUILDING SOLUTIONS
04-0001-25
HONEYWELL BUILDING SOLUTIONS
04-0001-26
HONEYWELL BUILDING SOLUTIONS
04-0001-27
HONEYWELL BUILDING SOLUTIONS
04-0001-28
HONEYWELL BUILDING SOLUTIONS
04-0001-30
Devices - Modules
 Isolator Module (ISO-X)
 Supervises loop wiring for short
circuit conditions
 Allows critical component
functions
 Required for Style 7 operation
 Supported by FlashScan and
1
CLIP systems
2

HONEYWELL BUILDING SOLUTIONS


04-0001-31
FDM-1 Wiring Class B Style B

9 6 7 8 9
0
5 10
11
8 4
3 12 1
2 13
1 0 14
7 TENS
15
2
6 8

6 4 3
2
5 0 4
ONES
LOOP ADDRESS

The circuit connected to terminals 6 & 7 are assigned the base address.
The circuit connected to terminals 8 & 9 are assigned the base address plus 1.
RED LED lights for either circuit 1 or circuit 2 alarm.

HONEYWELL BUILDING SOLUTIONS


04-0001-32
Wiring an NBG-12LX Pull Station
+ +
SLC SLC
- -

HONEYWELL BUILDING SOLUTIONS


04-0001-35
Wiring Surge Suppressor

Building 2

Building 1
P P

P = Primary
S= Secondary S

P P S

HONEYWELL BUILDING SOLUTIONS