Presentation On Energy Conservation 2019: Presented by Energy Management & Audit Department Masood Textile Mills LTD
Presentation On Energy Conservation 2019: Presented by Energy Management & Audit Department Masood Textile Mills LTD
Presented By
Energy Management & Audit Department
Masood Textile Mills Ltd.
Future Inside
territory
the
we
mills
were
We are replacing all
To replace every
single old light source
with LED technology.
400W light source
using 400W Flood with 100 W LED’s and
lights of both mercury To save energy by
Before Energy Management starting our journey to
availing latest
and sodium type. In save energy with
Department no one some areas we were technology in all
practice “how to save efficient output. Also
using huge quantity areas from machines
we are replacing
energy with efficient of fluorescent tube fluorescent tube rods
running to controlling.
output.” rods too. & energy savers with
LED technology to
In office areas we save energy.
were using
fluorescent tube rods In Office areas
& energy savers. replacing with 18W to
40W LED light
In Outside & sources.
boundary we were
using all type of old
lighting sources. One by one we are
upgrading our motor
All high & medium controlling methods
capacity motors were through VFD’s.
running with star
delta or DOL method.
Before
Lighting Sodium Flood Light
Flood Light Watt: 400 W
Quantity: 1202
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 400*16 = 6400/1000 = 6.4 KWh
Per Month: 6.4*30 = 192 KWh
Per Year: 192*12 = 2304 KWh
Total
2304*1202 = 2769408 KWh = 2769.408 MWh
After
LED Flood Light
Watt: 100 W
Quantity: 1152
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 100*16 = 1600/1000 = 1.6 KWh
Per Month: 1.6*30 = 48 KWh
Per Year: 48*12 = 576 KWh
Total
576*1152 = 663552 KWh = 663.552 MWh
Before
Lighting Fluorescent Tube Light
Tube Light 36 W Watt: 36 W
Quantity: 9431
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 36*16 = 576/1000 = 0.576 KWh
Per Month: 0.576*30 = 17.28 KWh
Per Year: 17.28*12 = 207.36 KWh
Total
207.36*9431 = 1955612.16 KWh = 1955.61
MWh
After
LED Tube Light
Watt: 18 W
Quantity: 8510
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 18*16 = 288/1000 = 0.288 KWh
Per Month: 0.288*30 = 8.64 KWh
Per Year: 8.64*12 = 103.68 KWh
Total
103.68*8510 = 882316.8 KWh = 882.32 MWh
Before
Lighting Fluorescent Tube Light
Tube Light 18 W Watt: 18 W
Quantity: 4593
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 18*16 = 288/1000 = 0.288 KWh
Per Month: 0.288*30 = 8.64 KWh
Per Year: 17.28*12 = 103.68 KWh
Total
103.68*4593 = 476202.24 KWh = 476.20 MWh
After
LED Tube Light
Watt: 9 W
Quantity: 955
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 9*16 = 144/1000 = 0.144 KWh
Per Month: 0.144*30 = 4.32 KWh
Per Year: 4.32*12 = 51.84 KWh
Total
51.84*955 = 49507.2 KWh = 49.51 MWh
Before
Lighting Energy Saver
Others Watt: 85 W
Quantity: 1127
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 85*16 = 1360/1000 = 1.36 KWh
Per Month: 1.36*30 = 40.8 KWh
Per Year: 17.28*12 = 489.6 KWh
Total
489.6*1127 = 551779.2 KWh = 551.78 MWh
After
Quantity: 313
Running Time: 16 Hrs.
Energy Consumption of Single Unit
Per Day: 40*16 = 640/1000 = 0.64 KWh
Per Month: 0.64*30 = 19.2 KWh
Per Year: 19.2*12 = 230.4 KWh
Total
230.4*313 = 72115.2 KWh = 72.12 MWh
LED
Savings Per Annum Item
Old Load
(MWh)
Load
Saving Load
(MWh)
(MWh)
Flood
Lighting Light
Tube
2769.41 663.55 1990.66
Remaining; 5423
Total
Total; 16353 Replaced
Replaced; 10930 Remaining
Motors Before
After
VFD
Rating of VFD: 200 KW
After
VFD
Rating of VFD: 200 KW
After
VFD
Rating of VFD: 250 KW
After
VFD
Rating of VFD: 75 KW
Running Frequency: 42 - 45 HZ
Savings; 943
Previous
Previous; 3576.26 Current
Current; 2633.23 Savings