HIGH VOLTAGE LOW VOLTAGE YELLOW ALERT YELLOW ALERT YELLOW ALERT YELLOW ALERT THERMAL CONDITION THERMAL CONDITION RANGE: 70 °C TO 150 °C RANGE: 50 °C TO 75 °C RECOMMENDED ACTIONS: RECOMMENDED ACTIONS: - Strict monitoring (once daily) - Strict monitoring (once daily) - Scheduled correction should arrange - Scheduled correction should arrange
RED ALERT RED ALERT
RED ALERT RED ALERT THERMAL CONDITION THERMAL CONDITION RANGE: ABOVE 150 °C RANGE: ABOVE 75 °C RECOMMENDED ACTIONS: RECOMMENDED ACTIONS: - Strict monitoring (once per shift) - Strict monitoring (once per shift) - Schedule immediate correction - Schedule immediate correction
NOTE: Thermal condition ranges & recommendations are based from recorded NRU-HV historical fault / abnormalities