4.SMMS-7 and MiNi SMMS-7 - Installation
4.SMMS-7 and MiNi SMMS-7 - Installation
Installation Highlights
Insulation work
Addition of refrigerant
Address setting
Test Operation
CORRECT
CORRECT
Air discharge
Air intake
Air intake
10mm or more
B
Through hole (15 x 20 long hole)
Model A B
SMMS-7 (8/10/12/14HP) 700 755
SMMS-7 (16/18/20HP) 920 755
SMMS-7 (22/24HP) 1310 755
NO GOOD
NO GOOD
Set height of stool by
500 mm or more
Gas piping
20mm or more
24 19.1 34.9
2 to 4 psig
Tapered portion
Indoor unit Pipe
Center
Brazing union
(half union) Flared portion
Flare nut
Work Procedure
Airtight test
Material
6.35 x 0.8 24 8 48 20
Soft 9.52 x 0.8 27 8 51 20
Hard
Half hard 12.70 x 0.8 34 10 54 20
15.88 x 1.0 37 10 57 20
19.05 x 1.0 N/A N/A 61 20
22.22 x 1.0 N/A N/A 64 20
Hard
28.6 x 1.0 N/A N/A 68 20
Half hard
34.9 x 1.1 N/A N/A 76 20
41.3 x 1.25 N/A N/A 83 20
Insulation guidelines
Condensation characteristics
Insulation guidelines
When using the piping cover When not using the piping cover
Insulation guidelines
PROFESSIONAL INSTALLATION
Drain slope
Down
Downward slope : At least 1/100 (a drop of 1cm per meter) slope !!
FCU
Drain support
Support bracket
interval !!
Any undulations
Slope upwards
NOTICE
Over another pipe
Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2,
U3, U4, U5, U6, U7, U8); Otherwise, the unit may break down.
Item Specification
Star connection
Select the power supply cabling of each outdoor unit from the following
specifications: Cable 5-core, in conformance with design H07 RN-F or 60245 IEC 66.
Don’t connect outdoor units by crossing Connect outdoor units via the
outside of them. incorporated terminal block (L1,L2,L3,N)
SMMS-e SMMS-7
HP
Model Name(MMY-) MCA(A) MOCP(A) Model Name(MMY-) MCA(A) MOCA(A)
8 MAP0806* 20.5 25 MAP0807* 20 25
10 MAP1006* 21.5 25 MAP1007* 22 25
12 MAP1206* 26.1 32 MAP1207* 24 32
14 MAP1406* 31.0 40 MAP1407* 26 32
16 MAP1606* 35.8 40 MAP1607* 29 32
18 MAP1806* 40.6 63 MAP1807* 35 40
20 MAP2006* 44.9 63 MAP2007* 42 50
22 MAP2206* 49.3 63 MAP2207* 48 63
24 AP2416* 52.2 63 MAP2407* 49 63
26 AP2616* 57.1 63 AP2617* 50 64
28 AP2816* 61.9 63 AP2817* 52 64
30 AP3016* 66.8 80 AP3017* 55 64
32 AP3216* 71.6 80 AP3217* 58 64
MCA : Minimum Circuit Amps = Maximum running current
MOCP : Maximum Overcurrent Protection(Amps)
SMMS-e SMMS-7
HP
Model Name(MMY-) MCA(A) MOCP(A) Model Name MCA(A) MOCA(A)
34 AP3416* 76.4 80 AP3417* 64 80
Power supply
terminal block
Communication
terminal block
Close-up view of
terminal block
Power supply
switch/circuit breaker or
power supply wiring/fuse
rating for indoor units
should be selected by the
accumulated total current
values of indoor units.
For power supply wiring, strictly conform to the Local Regulation in each country.
U1/U2
U1/U2 Control wiring between indoor and outdoor units Control wiring between indoor units
Control wiring
2-core with polarity wires are used for the Control wiring between indoor unit and
outdoor unit and Central controller wiring.
To prevent noise trouble, use 2-core shield wire.
The length of the communication line means the total length of the inter-unit wire length
between indoor and outdoor units added with the central control system wire length.
Communication line
Control wiring between indoor Wire size 1.25 mm2 (Up to 1000m)
unit and outdoor unit 2.00 mm2 (Up to 2000m)
Central control line Wire size 1.25 mm2 (Up to 1000m)
2.00 mm2 (Up to 2000m)
The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact each other and cannot be
stored in the same conduits. If doing so, it may cause troubles on the control system due to noise or other factor.
*For total wire length of remote controller please refer installation manual
Group control
U1/U2 U1/U2 U1/U2 U1/U2 U1/U2 U1/U2 U1/U2 U1/U2
A/B
Perform vacuuming for 2 or 3 hours, though the time differs depending on the
pipe length. Check that all the packed valves at the liquid side and gas side are
fully closed.
TABLE 3-1
IDU capacity rank 007 009 015 048
Capacity code (HP) 0.8 1.0 1.7 5.0
Corrective amount of refrigerant (kg) 0.2 0.4 0.6
TABLE 3-2 For DX coil interface
Capacity code (HP) 8 10 20 40
Corrective amount of refrigerant (kg) 1.4 1.8 3.6 7.2
*For more information please refer installation manual and Engineering data book*
●SMMS-e
Additional Additional refrigerant
Compensation
refrigerant charge amount by
= amount by +
charge amount indoor unit HP
outdoor unit HP
at site
Additional refrigerant
Real length of
+ X charge amount per X 1.2
liquid pipe
liquid pipe
●SMMS-7
Additional Additional refrigerant
Compensation
refrigerant charge amount by
= amount by +
charge amount indoor unit HP
outdoor unit HP
at site
Additional refrigerant
Real length of
+ X charge amount per
liquid pipe
liquid pipe
*For more information please refer installation manual and Engineering data book*
At first step after finish installation work, Auto Address set up is needed by push
SW15 about 2 or more second
If your many system connect with Central control, it’s needed more procedure for
manual Address setting which is explained in Control topic.
After Address setting finish, system are ready to make Test operation, 7-Segment will
be displayed U1- - - as below picture
If system are shown some Error, it’s needed to find some mistake and solve it first
then go to test operation by next presentation.