Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 52

High Pressure

Components
High Pressure CO22 Cylinders
 Cylinder Capacities:
35, 50, 75, 100 and 120 Lb.
 DOT 3AA1800
 DOT 3AA2300
 Red Enamel or Red Epoxy
CV98 Valve
 Maintenance Free
 No Disassembly
 Same Flow Path & Outlet
Threads Same As CV-90
 Fill & Actuation Port
Threads Are Different Size
to Prevent Use of Wrong
Devices
CV-98 Cut-A-Way View
 Mini Check
 Large Piston Surface
 Electric
 Pneumatic
 Manual Actuation
 Back-Pressure
CV98 Electric Actuator
 Electric Actuator for
CV-98 Valve
 Identified by Bottom of
Actuator
 Ease of Service /
Maintenance
 Stackable
 Swivel Nut Allows Easy
Installation & Removal
CV-98 Electric Actuator Parts
 Body
 Metron Actuator
 Cap
Metron Actuator
 Must Be Replaced After
Each Use
 Component Design
Allows Easy
Replacement
Electric Actuator - Interior
 Metron Protractor
Simply Sets in Place
 Connector Tucks in
Alongside of Protractor
 Be Careful to Not
Damage Wires
HF Electric Actuator
 Electric Actuator for
CV-98 Valve
 Used with Booster
Actuator
 Resettable
 Stackable
 Swivel Nut Allows Easy
Installation & Removal
Booster Actuator
 Used with HF Electric
Actuator
 Stackable
 Swivel Nut Allows Easy
Installation & Removal
Booster Actuator
 Resettable
Lever Release

 With Ring Pin and Chain


 Discard Ring Pin If Used
With Cable Pull
Lever Release
 P/N 423309
 Used on CV98 valve /
CV98 electric actuator
 Medium Diameter Pin
Lever Release
 P/N 70846
 Used on HF Electric
Actuator
 Small Diameter Pin
Connecting Link
 Connects Two Pilots For Simultaneous
Manual Actuation
Cable Pull Station
 Usually Located
Near Exits.
 Make Certain To
Allow a 7 Inch (17.5
cm) Clearance For
Cable To Be Pulled
Out.
Cable Boxes
 Junction Boxes for Wire Cables
CV98 Discharge Hose
 Provides Flexible Connection Between
Cylinder Valve & Manifold.
 Special Threads On Cylinder Valve End.
 Check valve included.
Pneumatic Time Delay
 UL, FM, USCG Approved
 10 Seconds UL/FM
 30 Seconds UL/FM/USCG
 60 Seconds UL/FM/USCG
HP Manifold System
Selector Valves
 1/2” to 2” Sizes
 UL, FM, ULC Listed
Selector Valves
 2 1/2” to 4” Sizes
 UL, FM, ULC Listed
Selector Valves

 Manual
Selector Valves

 Electric
Selector Valves
 Pneumatic
Selector Valves

 Manual old type


Selector Valves
Click to edit Master title style
• Click to edit Master text styles
 Pneumatic old type
• Second level
• Third level
• Fourth level
• Fifth level

28
28
Lever Release
 P/N 42484
 Used on old pneumatic
operated selector valves
Lever Release
 P/N 427207
 Used on all “new” selector valves
manual only or pneumatic and manual
 Red handle
Check Valves
 Used In Manifold For
Main/Reserve & Selector
Valve Systems.
Vent Plug
 Used In Manifold Main / Reserve
& Selector Valve Systems.

 Vents Low Pressure Gas.


Header Safety
 Safely Used In Closed
Sections of Pipe To
Relieve High Pressure
Cylinder
Cylinder Bracketing
Bracketing -- Single
Single Row
Row
 Various Sizes.
 Consists Of Channel,
Strap & Bolts.
Cylinder
Cylinder Bracketing
Bracketing -- Double
Double Row
Row
 Consists Of Backframe
Assembly & Cylinder Clamps.

 Can Be Configured In Single,


Double, or Back-to-Back Rows.
Cylinder Bracketing --
Cylinder Bracketing
Weigh
Weigh Rail
Rail Support
Support
Discharge
Discharge Pressure
Pressure Switch
Switch -- DPST
DPST

 Dual-pole, single throw switch


 For shutdown / interlock
connections
 Brings in alarm & shuts
down equipment
 Explosion-proof switch also
available
Pressure Trip
 Counterweight or spring-
loaded mechanical device
 Closes accessory devices
upon system actuation
Odorizer
 Wintergreen scent
 Scent discharged through piping network
 Warning to personnel that
CO2 has been discharged
in area
Pneumatic Siren
 90 dB at 10 feet
 16 lbs./min. flow rate
 1/4 inch FNPT
 U.L. Listed
Hose Reel
 Lengths: 25, 50, 75, and
100 Feet
 Diameter: 1/2 and 3/4 Inch
 Three Types of Discharge
Horns
Piping
Actuation Piping
 1/4” schedule 40 black iron, hot dipped
galvanized, chrome-plated, or stainless
steel pipe
 ASTM A120, A53, or A106
 Cast iron pipe not
allowed
Actuation Piping
 Maximum length of all ¼” actuation
piping cannot exceed 150 ft.
Actuation Piping
 Piping and fittings must be sealed with
pipe tape.
 Start at the second thread and wrap
two turns maximum.
 Do not allow tape to overlap the pipe
opening
Distribution Piping
 All pipe up to and including ¾” to be
schedule 40 (standard weight) black,
stainless or galvanized steel pipe.
 All pipe over ¾” to be schedule 80
(extra heavy) black, stainless or
galvanized steel pipe
 ASTM A53 or A106
 A120 shall not be
used
Distribution Piping
 Extra heavy galvanized malleable iron
or ductile iron fittings through 2”
 Galvanized forged steel fittings for all
larger sizes
Distribution Piping
 Ream, clean, and blow out all pipe
before installing.
 After assembly, blow out the entire pipe
system before installing discharge
nozzles.
Distribution Piping
 All dead end pipe lines to be provide
with a capped nipple, 2” long.
Hanger Applications
 Install pipe hangers in accordance with
good piping practice.
 Maximum spacing between hangers
must not exceed those listed below.

Page 7-5
Hanger Applications
 A hanger should be installed between
fittings when the fittings are more than
2 ft. apart.
Hanger Applications
 A hanger should be installed at a maximum
of 1 ft. from the nozzle.
Hanger Applications
 Hangers must be UL listed and rigidly
supported. Some typical hangers are
shown below.
 Consult all state and local codes for the type
of hangers that are acceptable.

You might also like