Mathematical Modeling of A Residential Air-Conditioning System
Mathematical Modeling of A Residential Air-Conditioning System
conditioning System.
Department of Chemical Engineering, BUET
1 3
Air side HT Co-efficient code Air side – Surface efficiency
Output : Output :
• Air Side (Heat transfer coefficient) • Surface efficiency air side.
Input: Input:
• Geometrical Parameters • Geometrical Parameters
• Air velocity • Air side heat-transfer coefficient.
• Air temperature • Heat exchanger material.
2 4
Refrigerant side HT Co-efficient Total power consumed by the fan.
code
Output :
Output : • Power input needed.
• Refrigerant (Heat transfer coefficient)
Input:
Input: • Friction factor of fins.
• Refrigerant flow rate • Friction factor of tubes.
• Evaporator pressure • Face velocity over the evaporator tubes.
• Geometrical Parameters
Evaporator
5
Overall Heat transferred.
Output :
• Total heat transferred.
Input:
• Refrigerant side heat transfer coefficient.
• Air-side heat transfer co-efficient.
• Face velocity over the evaporator tubes.
COMPRESSOR
Overall Power required.
Output :
• Total heat transferred.
Input:
• Refrigerant mass & flow rate.
• Pressure of Evaporator & Condenser.
• Isentropic expansion coefficient of refrigerant.
Evaporator
(Air Side)
"Evaporator Air Side" {All input data in mm}
Tair_evap= 33 [c]
Pair_evap=101.325
Vair_evap = 800 [m^3/hr]
rho_airevap = density(Air,T=Tair_evap,P=Pair_evap)
mair_evap = Vair_evap*rho_airevap*convert(1/hr,1/s)
Bair_e=28.5 [mm] "Vertical spacing between the tubes ina row"
Cair_e=24.2 [mm] "Spacing between the tubes in different rows"
tair_fe=.006*convert(in,mm) "Thickness of the fins"
d_oe=7.5 [mm] " Tube outer diameter"
Dair_e=1.7 [mm] "Center to center distance between the fins"
Hair_e=500 [mm] "Height of the Evaporator"
Wair_e=139 [mm] "Width of the evaporator"
Nair_e=2 "no of rows" "Number of rows in the direction of flow in the evaporator"
A_be = (pi*d_oe/1000)*(Wair_e/Dair_e)*(Hair_e/Bair_e)*((Dair_e-tair_fe)/1000)
"Bare Tube area"
A_fe = (Wair_e/Dair_e)*2*(Nair_e*(Cair_e/1000)-((Hair_e/Bair_e)*pi*(d_oe/1000)^2/4)) "Fin
area"
A_me = (Wair_e/Dair_e)*((Dair_e-tair_fe)/1000)*((Hair_e/1000)-(Hair_e/Bair_e)*(d_oe/1000))
"Minimum Flow area"
A_oe= A_be+A_fe "Total evaporator area"
Peri_e= A_oe/(Nair_e*Cair_e/1000) "Wetter Perimeter of the evaporator"
D_he= 4*A_me/Peri_e "Hydrolic diameter of the evaporator"
Afrontal_e= 0.500*0.139 [m^2] "Frontal area of the evaporator"
Test_evap= A_me/Afrontal_e "Minimum flow area to frontal area ratio"
Gemax_airevap=mair_evap/A_me "maximum mass velocity in the air side of the
evaporator“
mu_airevap=viscosity(Air,T=Tair_evap)
Re_airevap=(Gemax_airevap*D_he)/mu_airevap
Pr_airevap=prandtl(Air,T=Tair_evap)
K_airevap=conductivity(Air,T=Tair_evap)
h_airevap=.117*Re_airevap^.65*Pr_airevap^.66*(K_airevap/D_he)
Evaporator
(Refrigerant Side)
Ref$= 'R22'
{q_evap=(5250)
m_re=(Q_evap)/((En_refve*1000)-(En_refle*1000))}
d_ie= 7 *convert(mm,m)
Ai_re= pi*(d_ie^2)/4 [m^2]
m_re= 0.0285[kg/s]
G_re= m_re/Ai_re
Pref_e = 900[kpa]
X_ive = .1
X_Ile=1-x_ive
X_ove= .9
x_ole=1-x_ove
L_evap =40 [m]
T_evsat = Temperature(Ref$,P=Pref_e,X=0)
mu_refle= viscosity(Ref$,t=T_evsat,x=0)
k_refle=conductivity(Ref$, T=T_evsat, X=0)
En_refve= enthalpy(Ref$,P=Pref_e,X=1)
En_refle=enthalpy(Ref$,P=Pref_e,X=0)
Ifg_re=En_refve-En_refle
Re_refe=G_re*d_ie/mu_refle
c_conste= 0.0082 "Constant in the equation for calculating
evaporative heat transfer coefficient"
n_conste=0.4 "Constant in the equation for calculating
evaporative heat transfer coefficient"
A= ((x_ove-x_ive)*(ifg_re*1000)/(L_evap*9.8))
h_re =C_conste*(k_refle/d_ie)*((Re_refe^2*A))^n_conste
A_retotal= Pi*d_ie*L_evap
Evaporator
(Air side Surface Efficiency)
{Bair_e = 21
Cair_e = 18.16
tair_fe = .006*convert (in,mm)
d_oe= 7
h_airevap=87}
Lfin_evap = Bair_e/2
Mfin_evap = ((Bair_e/2)^2 + Cair_e^2)^.5/2
Beta_finevap = Lfin_evap/Mfin_evap
Shi_finevap = Mfin_evap/(d_oe/2)
R_by_rfinevap = 1.27*Shi_finevap*(Beta_finevap-0.3)^.5
Phi_finevap = (R_by_rfinevap -1 )*(1+ 0.35*ln(R_by_rfinevap))
m_finevap = ((2*h_airevap)/(kcopper_finevap*(tair_fe/1000)))^.5
Eta_finevap =
tanh(m_finevap*(d_oe/(2*1000))*Phi_finevap)/(m_finevap*(d_oe/(2*1000))*Phi_finevap)
Eta_surfaceevap = 1-(A_fe/A_oe)*(1-Eta_finevap)
Evaporator
(Power consumed by the fan)
W_fan_e = (V_ac*P_total_e*Afrontal_e)/(0.70)
Evaporator
(Total heat absorbed)
UA_evap=1/((1/(h_re*A_retotal))+(1/
(h_airevap*A_oe*Eta_surfaceevap)))
NTU_evap=UA_evap/(Cpair_e*mair_evap*1000)
epsilon_evap= 1- exp(-NTU_evap)
Qmax_evap=(Cpair_e*1000)*(Tair_evap-T_evsat)*mair_evap
Q_evap=epsilon_evap*Qmax_evap
Condenser
(Air side)
Test_1c= (d_ic*G_lavg)/mu_lc
Test_2c=((d_ic*G_vavg)/mu_lc)*(rho_lc/rho_vc)^0.5
c_pl=specheat(Ref$,p=p_c,x=0) "
specific heat of the liquid phase of the refrigerant "
deltat_c = Temperature(Ref$,P=P_c,x=0) - Outair_tc
"Temperature difference between the Refrigerant and tubewall"
Pr_l=prandtl(Ref$,P=P_c,x=0) "
Prandtl number of the refrigerant in liquid phase"
h_rc= 13.8*(Pr_l)^(1/3)
*(k_lc/d_ic)*((ifg_c*1000)/(c_pl*deltat_c))^(1/6)*Test_2c^0.2 "
heat transfer coefficient of the tube side of the condenser"
A_rctotal= pi*d_ic*L_cond
" total heat transfer area of the tube-side of the condenser"
Condenser
(Air-side Surface efficiency)
{Bair_c = 25
Cair_c = 20.8
tair_fc = .006*convert (in,mm)
d_oc= 5.5
h_aircond=87}
m_fincond = ((2*h_aircond)/(kcopper_fincond*(tair_fc/1000)))^.5
Eta_fincond = tanh(m_fincond*(d_oc/(2*1000))*Phi_fincond)/(m_fincond*(d_oc/(2*1000))*Phi_f
Eta_surfacecond = 1-(A_fc/A_oc)*(1-Eta_fincond)
Condenser
(Fan power consumed)
Re_lcond = ((Gemax_aircond*Cair_c*convert(mm,m))/(mu_aircond))
f_fin_c= ((Re_lcond)^(-0.5))
{A_fe = 6.6 [m^2]
A_me=.053 [m^2]}
v_mc= 0.78 [m^3/kg]
P_fin_c = f_fin_c*v_mc*(Gemax_aircond^2/2)*(A_fc/A_mc)
"Pressure drop in the tubes"
{Vair_cond= 800 [m^3/hr]}
V_acc=(Vair_cond*convert(1/hr,1/sec))/Afrontal_c
{mair_cond = V_dot_ac*1.146*convert(1/hr,1/s)}
"Total condenser"
Cpair_c=specheat(Air,T=Tair_cond)
Cpref_c=specheat(Ref$,P=P_c,x=1) "Considering the specheat
of the vapor phase of the refrigerant"
{Cpmin_c=Cpair_e}
UA_cond=1/((1/(h_rc*A_rctotal))+(1/
(h_aircond*A_oc*Eta_surfacecond)))
NTU_cond=UA_cond/(Cpair_c*1000*mair_cond)
epsilon_cond= 1- exp(-NTU_cond)
Qmax_cond=(Cpair_c*1000)*(T_cdsat-Tair_cond)*mair_cond
Q_cond=epsilon_cond*Qmax_cond
COMPRESSOR
(Power Rec
gamma= 1.106
Mass_R22=84
R=8.314/Mass_R22
W_C = R*(T_evsat+273)*((gamma)/(gamma-1))*((((P_c)/(Pref_e))^(((gamma-1)/
(gamma))))-1)
WREAL_C=m_re*(W_C*1000)
COP=Q_evap/(WREAL_C+W_FAN_E+w_fan_c)
W_total = WREAL_C+W_FAN_E+w_fan_c
If you keep the air flow constant & increase the heat transfer , then surely the outlet
temperature of air will increase. (According to energy conservation principles)
Dilemma:
If we want to have more heat flow we need more Delta t ( More pressure in the condenser)
But higher temperature of the Refrigerant decreases the heat transfer co eff of the condenser.
I should always try to have as high HT coeff possible. As it is a one time investment.
So I should keep all the process variables at such an optimum level that I achieve a good heat flow
but I Also have a good heat transfer co-efficient.
(Air velocity in the evaporator)
Locus Optimus
Effect of different materials
In the overall HT Co-efficient