Professional Documents
Culture Documents
Situate The Offer in Its Environment Position The Ranges in Relation To Customers' Expectations Get To Know The CB Ranges
Situate The Offer in Its Environment Position The Ranges in Relation To Customers' Expectations Get To Know The CB Ranges
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
Expert: R. Nikodem
Pedagogy: M. Allagnat
Duration: 27 mn Production: AMEG
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
1920 1949 1955 1972 1978 1986 1989 1996 2000 2004
Circuit
Separation
Opening breaker
of of open
closed
arc
maincontacts
contacts
Separation
Opening
Circuit of of open
breaker
arc
closed
maincontacts
contacts
kV
40.5
36
Circuit breakers very well-
24 suited to the protection and
SF1 SF2
17.5 switching of loads sensitive
to overvoltages
12
LF
7.2
Auto- Auto-
compression expansion
12.5 16 20 25 31.5 40 50 kA
17.5 kV vacuum
arc-enclosure with
external coil
24 kV vacuum
arc-enclosure with
internal coil
24
12.5 16 20 25 31.5 40 kA
SF6
Protection of inductive and capacitive loads sensitive to overvoltages
e.g. cast resin-type transformers, MV motors
Vacuum
Protection of frequently switched loads
e.g. ovens, frequently started motors (with surge arrester protection)
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
Aubenas site
Contactor
Rollarc LF
Izmir (Turkey)
SF1 SF2
4 versions
basic version (without relays)
fixed version
withdrawable version
withdrawable version for use in MC cassette
1 frame-size
12
7.2
Rollarc
Nominal voltage
(Un)
Short-circuit current
(Isc) 10 kA 8 kA
17.5
12
LF1 - LF2 - LF3 7.2
Nominal voltage
(Un)
Short-circuit current 25 to
(Isc) 25 to 50 kA 40 kA
LF is used mainly in power
Nominal current
plants and large sites (In)
630 to 3150 A
A single frame-size
17.5
12
LFP
Nominal voltage
(Un)
Short-circuit current 40 to 25 to
(Isc) 50 kA 31.5 kA
LFP is used mainly in
Nominal current
power plants (In)
5000 A
24
17.5
SF1 (frontal) Nominal voltage
(Un)
Short-circuit current
(Isc) 12.5 kA to 25 kA
SF1 frontal is used mainly in
buildings and small industries Nominal current
400 to 1250 A
(In)
24
17.5
SF1 (lateral) Nominal voltage
(Un)
Short-circuit current
(Isc) 12.5 to 25 kA
SF2 36
24
Nominal voltage
(Un)
Short-circuit current
(Isc) 25 to 40 kA 31.5 kA
LF
Rollarc LFP
Energy SF2
LF
Rollarc
SF2
LF
Rollarc
SF2
Infrastructures
and Industries
SF1
Buildings
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
17.5
12
7.2
Nominal voltage
Evolis 17.5 kV frontal (Un)
Short-circuit current
(Isc) 25 to 40 kA
Evolis is used in buildings as
well as in large sites and utility Nominal current
630 to 2500 A
substations (In)
24
Nominal voltage
Evolis 24 kV frontal (Un)
Short-circuit current 16 to
(Isc)
Evolis 24 kV is used in buildings 31.5 kA
as well as in large sites and Nominal current 630 to
utility substations (In) 2500 A
24
Short-circuit current 16 to
(Isc) 25 kA
Evolis 24 kV is designed for
buildings and small industries Nominal current 630 to
(In) 1250 A
Evolis 17
Energy
Evolis 17 Evolis 24
Evolis 17 Evolis 24
Infrastructures
and Industries
Evolis 24
Buildings
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
VIP relay
protection against phase overcurrents and earth faults
Current transformers
Mitop release
VIP relay
SF1 /
Evolis
Current transformers
Operating principle
24 24
SFset Evoset
SFset and Evoset are
12
designed for
Nominal voltage Nominal voltage
buildings and small (Un) (Un)
industries
Short-circuit current 12.5 to Short-circuit current 16 to
(Isc) 25 kA (Isc) 20 kA
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
2 main functions
monitoring of operation
recording of parameters
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
Panelbuilders or contractors
MCset SM6
End-users
Energy, Industry, Infrastructure, Buildings
SM6
MCset GenieEvo MCset F400 12 kV - 17.5 kV
24 kV - 36 kV
1-2-3 4
SMV
12 kV - 17.5 kV
24 kV
Retrofit reference
in Turkey
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
Cuttler
Hammer
Rollarc:
– Angola Oil, Girassol Mpg-Elf
– Germany Automobile, Ford
– Argentina Food industry, Mastellone
LF:
– United Kingdom P&O Ferries, North Sea Ferries
– Italy Sarlux power plant
– Malaysia Slim River hospital
SF:
– Algeria ONAFEX, Hilton Hotel
– Indonesia Bali airport
– France Stade de France, Paris
Evolis:
– Iran MAPNA, Power Plant Mgt Company
– Russia Borsk glass manufacturing
– Poland Gdanski port
F Target actors
?
B SF6 circuit breaker offer
Situate MV
circuit breakers
A Two breaking techniques
The Schneider Electric offer covers all types of networks and all market
segments, with circuit breakers sold loose or included in switchgear
assemblies