EPIC – III Function

.…….…
8/4/2007

POWER SERVICE
Signal sources measurement

Power line

Primary Line
voltage
Primary current

SCR
(Thyristor
ignition)

Secondary
current

ESP Secondary
voltage

- 08/12/21 - P 2
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
EPIC II spark control - Detection

mA Short 2-9

-kV

Sparks are detected from the


kV measurment samples , they
are continuosly analyzed for
slopes that indicates sparkover.
If found, a signal is given to the
Quenching function to perform
-kV proper action.
Spark sens. kV
A real spark shall on a
oscilloscope look like a spike on
the current (mA) and fast dip of
tension (kV)

- 08/12/21 - P 3
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
EPIC II spark control -
Quenching

mA

-kV

SELF

mA Short 2-9

-kV
SHORT 2-9

mA

SELF + -kV
SHORT 2-9

- 08/12/21 - P 4
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Spark level following

This example shows Spark rate limit = 6 sparks per minute


Average time between sparks will be 60/6 = 10s
as long as precipitator voltage is limited by sparkovers.

Slope Rise B=80 %


of step

Slope Rise A=20 % of step

Slope Time A= 80 %
Slope
Time B= 20 %

- 08/12/21 - P 5
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
EPIC II spark control
Level following

Step. % of rated current


mA

Slope
Original
EPIC

mA
Step. % of current

EPIC II

1
SPM

- 08/12/21 - P 6
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Arc detection and quenching

mA Quenching 1-99 pulses

-kV

Arc is defined as: -60kV Low voltage alarm


kV V < Arc detection level level (average)
continuously for 10 fired periods
Arc detection level (valley)
-5kV

- 08/12/21 - P 7
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Digital sampling of Primary
waveforms
Primary line voltage
IRMS= i12 + i22 - - - i642 [mA]
64
P= (u1• i1 + u2• i2 - - - u64• i 64) [kW]
64
Ps= (|u1• i1|+ |u2• i2|- - -|u64• i64|) [kVA]

64

Primary current IRMS = Primary Current (root mean square)


P = Active Power (from the mains)
PS = Apparent Power (from the mains)

EPIC-II does very accurate and sophisticated digital wave form sampling and calculations
at a speed of 32 times/ half period of T/R primary, secondary current and voltage, it is very
essential that the signals represent the actual field signal with good accuracy and that the
signals are free from distortion and transients.

- 08/12/21 - P 8
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Secondary Voltage measurement

_
Peak Average Valley
"No" load

Normal load

- 08/12/21 - P 9
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Limitations of ESP voltage and
current

-kV

Ignition angle limit


Volt peak limit
Spark over limit

Optimization Current Primary


limit limit Current
Average limit
pulse RMS

mA

- 08/12/21 - P 10
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Rapper control

Run time

00:00 02:00 04:00 06:00 08:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 00:00
(24:00)

Repetition time

Start time

- 08/12/21 - P 11
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
State diagram, rapper sequence

Feedback from contactor or equal


EPIC II "Runtime"

EPIC II rapper
motor output

Feedback

Motor running

EPIC II alarm
function sensing
the feedback

Alarm will be given Alarm will be


here if motor is given here if
running. (feedback motor is not
= ON) running.
(feedback not =
- 08/12/21 - P 12 ON)
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
EPIC III Master unit

ETHERNET

EPIC II
MU 1 MU 2

T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R T/R

Address 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

MU1, Address range Low 5, High 15 Opacity


Opacity
MU2, Address range Low 16, High 21 4-20 mA
4-20 mA

- 08/12/21 - P 13
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Master unit functions

• ESP ON All on
STANDBY T/Rs off, Heaters on
OFF All off

• MODE CHANGE

• SUM ALARM RESET

• OpOpt, Opacity optimization control

• Any EPIC II unit can be assigned Master

- 08/12/21 - P 14
EPIC2exfunction 14
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
PC-MTU display – IP config

- 08/12/21 - P 15
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Computer display- Main window

- 08/12/21 - P 16
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Computer display- Cascade
coupling of rapping Timer

- 08/12/21 - P 17
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Computer display- Operation window

- 08/12/21 - P 18
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Computer display- ESP Master window

- 08/12/21 - P 19
ALSTOM © 2007. We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.