5 - Asenware FM200 and Gas Suppression PPT-2169
5 - Asenware FM200 and Gas Suppression PPT-2169
• Asenware FM-200 Fire extinguishing system are designed for total flo
oding to protect high value assets
• Colorless and non-toxic gas, suitable for normally occupied area, whe
re there is any chance of presence of human present
• FM200 fire suppression is also known as HFC227ea( 七氟丙烷 ). FM2
00 is a waterless fire protection system, it is discharged into the risk w
ithin 10 seconds and suppresses the fire immediately.
FM-200 Benefits
Use less space, save cost
(Compare CO2 system,FM200 system need only small amount of agent to put o
ut fire, so use less cylinder)
• When the control panel operate the solenoid valve upon receiving signal from detectors,
solenoid will actuate the cartridge after certain delay time ( if given ) and gas will discharge
into the hazard area.
• * With Asenware Gas Release Control Panel : Normally, the panel remains in ‘Auto’ positi
on.Upon receiving the signal from detectors , panel immediately released discharge alar
m and turn off the HVAC or dampers if any. And then release the gas after predetermine
d delay period.
2. Remote Manual Operation
• When the operation is performed by Manual Release Station, an appropriate pull stati
on is operated after detecting fire in the specific hazard area.
• With Asenware Gas Release Control Panel : Asenware Gas Release panel additionally p
rovide manual operation from panel , one must put the key to ‘manual’ position.
• After pushing the manual release located on the panel, gas will be released as operati
on
described above.
3. Local Manual Operation
1.The control panel will operate upon activation of a ZONE1 and ZONE2 or press Manual
release station
2.control panel give signal to fire bell or storbe sounder (fire alarm) → delay period will
operate→ Selenoid valve will actuate the cartridge after certain delay time ( if given )
and then N2 gas release.
3.Pneumatic control valve (气动控制阀) is mounted on selector valve body to
operate when nitrogen pilot tank of specify hazard actuated→ N2 gas go through Gas
control pipe( 铜管 )to FM200 cylinder and then operate the FM200 cylinder→gas release
on High pressure soft tube( 高压软管 )
4.When the agent is discharged in the distribution piping, it pressurize the switch to
operate and give signal to control panel and control panel will give signal to warning
Signage ,its will flashing ,give information that ‘agent is released in the piping’→Finally
,Gas will be released to the room through the nozzle
FM-200 - Principle of operation
Cabinet type FM 200 system
1.The control panel will operate upon activation of a ZONE1 and ZONE2 or press Manual
release station
2.control panel give signal to fire bell or storbe sounder (fire alarm) → delay period will
operate→ Selenoid valve will actuate the cartridge after certain delay time ( if given )
and then release the FM200 gas
3.FM200 gas release on High pressure soft tube( 高压软管 ), When the agent is
discharged it pressurize the switch to operate and give signal to control panel and control
panel will give signal to warning Signage.it will flashing ,give information that ‘agent is
released in the piping’→Finally ,Gas will be released to the room through the nozzle
FM-200 - fire extinguisher control p
art
• Automatic gas extinguisher control system
• 1. AW-GEC2169 Automatic Gas Extinguisher Contr
ol Panel
• 2.Manual Release Station
• 3.Maintenance Switch
• 4. Gas Release Warning Signage
• 5. Conventional smoke detector, heat detector, bel
l, strobe sounder
AW-GEC2169 Automatic Gas Extinguisher Co
ntrol Panel
• AW-GEC2169 is upgrade from AW-GEC2159 with new design. The panel has 2 det
ection zones and new version has much more fashionable and easily operate butt
on from panel,also with safe and durable/visible metal cabinet with visible glass
window .
wring diagram
Gas Extinguishing Release Control Panel AW-GEC
2169
• Internal Terminal
ZONE1/ZONE2→connect Detector
EM VALVE →connect Selenoid valve
OPTICAL WARNING- →connect Gas Release
warning signage
SOUNDER OUTPUT → connect Bell or Strobe
Sounder
MODE SELECT→ connect Maintenance switch
MANUAL RELEASE→ connect Manual release
station
ABORT INPUT→connect PUSH/HOLD
RELEASED SWITCH→ connect pressure switch
Gas Extinguishing Release Control Panel AW-GEC
2169
• Battery Installation
The panel uses two lead acid gel 12V/2.3Ah batteries connected i
n series.
Connect the batteries with the supplied free lead and the Batterie
s to the power supply unit with the red (positive) and black (nega
tive) wires.
When the green battery LED is on steady it shows that the battery
condition and connections are normal.
Conventional Smoke Detector - Model no.:
AW-CSD381
• Wire connection point: No.6: Remote indicator(+) / Next detector IN (+) No.3:
Remote indicator(-). No.2: IN + ( zone input + ) No.5: IN - ( zone input - )
Conventional Heat Detector - Model no.: AW-CSD382
• Wire connection point: No.6: Remote indicator(+) / Next detector IN (+) No.3
: Remote indicator(-). No.2: IN + ( zone input + ) No.5: IN - ( zone input - )
Manual Release Station & Abort Switc
h
• Open the protection cover
• Press down the red button t
o trigger a manual release
• Reset by a key
• Open the protection cover
• Press the yellow button to
trigger an abort function
Fire Suppression System Manual Release Stat
ion
• Wire connection of Manual Release Station
• note:Resistance 6.8 KΩ and 470 Ω
470Ω
6.8 KΩ
Fire Suppression System Abort Switch
• Wire connection of PUSH/HOLD
• note:Resistance 6.8 KΩ and 470 Ω
6.8KΩ
Maintenance Switch
• This MAINTENANCE panel is
a key switch, which disconn
ects actuation circuits in the
system to prevent accidenta
l discharge during maintena
nce operations.
6.KΩ
Gas Release Warning Signage
10KΩ
10KΩ
_ +
Wire connection of Pressure switch
*Note:need to connect Resistance 6.8 KΩ and 470 Ω
6.8KΩ
470Ω
FM-200 Overview
Why choose Asenware
• 1. Our projects:
• Cambodia Power Substation FM200 System Project