Overcurrent Coordination Setting Guidelines Conductors
Overcurrent Coordination Setting Guidelines Conductors
Considerations
• The purpose of the phase overcurrent relay is to allow for full use of the feeder, and to protect the feeder
from overloads and faults.
• To accomplish this, the relay curve should be at or below the feeder ampacity and to the left of the damage
curve.
• NFPA 70: National Electrical Code (NEC) does allow MV circuit breaker trip settings up to 600% of the ampacity
of the conductors.
• However, settings in this range will not protect the conductors.
MV Switchgear Feeder Unit
Device Function Recommendations Comments