Cable Inputs in DG
Cable Inputs in DG
Cable Inputs in DG
– For the International Standards Method, the command will verify the suitability of the cable in
accordance with the selected standard.
– For the Cable Reinforcement Method, the command will verify the suitability of the cable in
accordance with the selected constraints and / or network consistency criteria. At least one of
Thermal Loading Limits, Consider Voltage Drop Per Terminals, Consider Voltage Drop Along
Feeder, Short Circuit Loading Limits, and Network Consistency must be selected.
Mode
Recommendation mode :
– For the International Standards Method, the command will create new cable types
• The cable derating factor will be set based on the installation method, specified on the cable
element’s Cable Analysis page.
– For the Cable Reinforcement Method, the command will recommend cable types for those
cables without Types yet defined, and those that cause violations of the specified constraints.
Constraints
• Thermal Loading Limits:
• Global - entered in the Maximum Thermal Loading field.
• Individual - Max Loading within the Load Flow tab of each cable.
• Voltage Drop Per Terminals :
• Global - entered in the Lower Limit of Terminal Voltage field..
• Individual - the voltage limit is specified in the Load Flow tab of each terminal.
• Voltage Drop Along Feeder : absolute voltage difference between the source terminal of the feeder and the final
terminal of the feeder.
• Global Constraints : entered in the Maximum Voltage Drop field.
• entered in the Maximum Voltage Drop field.
• Short Circuit Loading Limits : Mode is set to Verification
Model parameters
Define → Cable Layout