Transformer Protection: 2 Winding Auto Transformer Earthing Transformer Reactor

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 45

TRANSFORMER

PROTECTION
2 Winding
Auto transformer
Earthing transformer
Reactor
TRAINING DEPT

SJEC
Why transformer is needed?
• Take a task of transmitting a power of
1000W.
Power = Voltage x Current W
Required current at various voltages to transmit 1000W is given below
(I=P/V A)
If voltage = 10V current = 100A
voltage = 100V current = 10A
voltage = 1000V current = 1A
TRAINING DEPT

SJEC
What is advantage of less current flow?

• Conductors posses resistance. So current flowing through resistance


causes voltage drop (IxR), power loss (I^2xR). This power loss generates
heat which further increases resistance. So less current flow lesser losses
and higher effiency.
• The cross sectional area of the conductor has to be increased to have large
current flow.
• Large value of current causes skin effects.

At the same time increase in voltage also requires higher value of insulation
which increases the overall cost of the system.
Hence the transmission voltage is chosen based on techno-commercial values.

Also there is a limit on the generator voltage. Typically 6.6kV, 11kV, 22kV
TRAINING DEPT

SJEC
Need of Transformer
• In order to raise the voltage at the
beginning of transmission line (generating
stations) and to lower it to various levels in
sub-transmission, distribution & utilization
levels a transformer is required.
TRAINING DEPT

SJEC
Transformer Characteristics
• Input power is equal to output power. (Neglecting losses)
• The raising or lowering of voltage is accompanied with
corresponding lowering or raising of current.
• There is no change in frequency.
• Output waveform is an exact replica of Input waveform.
(Except during inrush and saturation)
TRAINING DEPT

SJEC
Basic Construction
• Basically a transformer consists of two
windings on a magnetic core. The winding
to which power is given is called Primary
Winding. The winding from which
transformed power is taken out is called
Secondary winding.
TRAINING DEPT

SJEC
Principle of Operation
• When a sinusoidal voltage is applied across a winding (1), a
sinusoidal current flows through it.
• This sinusoidal current flowing through winding (1) (Coil of many
turns) sets up a sinusoidal magnetic field.
(Basic principle: When a current flows through a conductor, a
magnetic field is setup)
• Nearly entire portion of this sinusoidal magnetic field flows through
the magnetic core.
(Magnetic core offers more easy path than air for flow of magnetic
field)
• This magnetic field links with the another winding(2) placed on the
core.
TRAINING DEPT

SJEC
Continued
• This magnetic field linking with the another coil being sinusoidal in
nature induces an emf in the another winding(2).

• So the basic principle for transformer operation is continuously


changing flux in magnetic core. An emf is induced only when there
is change of flux. Sinusoidal wave (current) continuously changes
and hence produces continuous changing flux.
• A Steady DC voltage/current (no change in value) cannot produce
changing flux and hence a transformer cannot work on steady DC.
TRAINING DEPT

SJEC
Formulae used in Transformer
problems
• Transformation Ratio :
( N1 / N2 ) = ( V1 / V2 ) = ( I2 / I1 )
where 1 indicates primary winding &
2 indicates secondary winging.

• Input power = Output power (losses neglected)


V1I1 cos ø = V2I2 cos ø
Transformer doesn’t have its own power factor (Neglecting no load
current). Its power factor is the same as that of the load. Hence
rating of the transformer is specified in VA (KVA, MVA etc)
[Apparent power] and not in watts W (kW, MW etc) [Real power].
As already stated transformer doesn’t introduce any change in
frequency or waveform.
TRAINING DEPT

SJEC
Voltage Regulation
• Broadly explained it is the ratio of voltage deviation to expected
voltage.
% Regulation = Expected voltage – Actual Voltage x 100
Expected voltage

So, we have to implement some mechanism to have constant


voltage at the secondary [customer] even though there is
fluctuations in the primary side [supplier].
This is done in transformers directly changing the turns ratio suitably
to meet the situation. Usually turns ratio is changed in the HV side
since HV winding has lesser current. [As this is a moving
mechanism and its is always advantageous to deal with smaller
current].
TRAINING DEPT

SJEC
Continued

This mechanism is called as TAP CHANGER. Tap changers are


classified into two types based on the load conditions of operation
a. ON LOAD tap changers
b. OFF LOAD tap changers

ON LOAD tap changers are the one capable of changing turns


ratio without any interruptions in service. [Basically it is motor
operated] eg Transformer used in transmission network.
OFF LOAD tap changers are mostly manually operated and
possible to operate only when the transformer is de-energized.
eg Transformers used in distribution network
TRAINING DEPT

SJEC
TAP CHANGERS

10
9
7 8
5 6
4
3
2
1

PRIMARY VOLTAGE
TRAINING DEPT

0
SJEC
As already stated in previous slides a
TAP changer is mostly placed in the
HV side of the transformer. The main
aim is to maintain the LV voltage at a
constant voltage (within certain limits).
This has to take care of both over
voltage and under voltage conditions.
All tap changers have a tap called
NOMINAL tap. This tap is designed for
the rated voltage of the transformer.
Transformer windings are provided with no.
tappings in HV side based on the required
voltage range. Usually this may be -20% to
+10%. These are nothing but connections
taken out from winding at different no. of
turns to suite the requirement.
TRAINING DEPT

SJEC
For eg. The requirement is to have a 1000 / 100 V transformer. The HV
winding is to be designed for -14% to +4% in steps of 2%.
(-14%, -12%, -10%, -8%, -6%, -4%, -2%, 0%, 2%, 4% Total 10 taps)
(860V, 880V, 900V, 920V, 940V, 960V, 980V, 1000V, 1020V, 1040V)
Let us assume the HV winding to be Primary and LV to be Secondary.
The secondary voltage must remain at 100V even when there is a
fluctuation in primary voltage from 860V to 1040 volts. Now the let us
assume there is 200 turns in LV winding. (Based on design calculations).
This gives 200turns/100V = 2 turns per volt.
Since the HV max voltage is 1040V it must have 1040V x 2 turns per volt =
2080 turns
The tapings are to placed at
860 x 2 = 1720 turns 880 x 2 = 1760 turns 900 x 2 = 1800 turns
920 x 2 = 1840 turns 940 x 2 = 1880 turns 960 x 2 = 1920 turns
980 x 2 = 1960 turns 1000 x 2 = 2000 turns 1020 x 2 = 2040 turns
1040 x 2 = 2080 turns
Tapings will be placed all these turns. 2000 turns is the nominal turns for the
HV winding and LV winding will have 200 turns with no tapings.
TRAINING DEPT

SJEC
Voltage Turns Tap no. Transformation ratio
860 V 1720 turns 1 8.6
880 V 1760 turns 2 8.8
900 V 1800 turns 3 9.0
920 V 1840 turns 4 9.2
940 V 1880 turns 5 9.4
960 V 1920 turns 6 9.6
980 V 1960 turns 7 9.8
1000V 2000 turns 8 10.0 (Nominal TAP)
1020V 2040 turns 9 10.2
1040V 2080 turns 10. 10.4
When the primary voltage is 1000V, the tap changer will connect tap 8
to the primary voltage and thereby secondary voltage is 100V.
Transformation ratio is 10.0.
Now when the primary is 960V the but we need to get 100V. So the
transformer must have a transformation ratio of 9.6. To get this, the tap
changer connects TAP 6 to the primary voltage and now the secondary
voltage is again 100V.
TRAINING DEPT

SJEC
AUTO-TRANSFORMERS
• Auto transformers have only one winding [for single
phase]. Same winding acts as HV and LV. The VARIAC
we used in our college electrical laboratory is an Auto-
transformer.
• The operation principle is the same as that of two
winding transformer described before is previous slides.
• The only difference between two winding transformer
and auto-transformer is usage of lesser copper wire due
to LV winding forming part of HV winding. Especially
when the transformation is nearing unity auto-
transformer gives great saving in copper.
TRAINING DEPT

SJEC
continued
• The disadvantage of auto-transformer is, it doesn’t provide electrical
isolation between HV & LV circuits which we get in two winding
transformers.
TRAINING DEPT

SJEC
TRANSFORMER LOADING
This refers to electrical loading and not to loading & unloading during
transportation and erecting process.
• Say, the Primary (HV/LV) winding is energised with the rated voltage. (Here
onwards rated voltage means voltage of correct magnitude, frequency & sinusoidal without harmonics
It induces a self induced emf in the primary winding
unless specified explicitly)
whose direction is opposite to the applied voltage. Numerically its value is
nearly equal to that of the applied voltage. (since the windings are highly inductive due to
magnetic core)
• An emf is induced in the secondary (LV/HV) winding (mutually induced
emf), which appears as voltage at the secondary winding terminals. Since
the transformer is not loaded, current through secondary winding is ZERO.
• But primary winding carries some current which is utilised for magnetizing
the core due to which emf is induced in the secondary winding. This
current in primary winding is nearly 90 o lagging since windings are highly
inductive circuits.
TRAINING DEPT

SJEC
continued
• If the resistance of the primary winding is neglected, there is no
power involved in magnetising the core of transformer.
Power = V x I x Cos ø since ø = 90o Cos ø = 0
= 0 watt.

So transformer on ZERO Load [Secondary open circuited] draws


ZERO power. (neglecting losses which is usually very very small.)

• Now when a load is connected to the secondary winding, a currents


start to flow in the secondary winding and creates a magnetic field.
TRAINING DEPT

SJEC
continued
• The direction of the current flowing in the secondary
winding is opposite to the current flowing in the primary
winding when checked at identical terminals of the two
windings. (The procedure for finding identical terminals of both the
windings is explained latter under heading “POLARITY TEST”.)
• The current being in opposite direction, the magnetic field is also in
opposite direction. The effect of this secondary winding magnetic
field is to reduce the net magnetic field in the core. (Since direction
is opposite, algebraically it has –ve sign. Just for understanding).
• When the net magnetic field in the core reduces, it results in
reduction of the self induced emf (Logically, opposing force for applied voltage) in
the primary winding.
• This increases difference between applied voltage and self induced
emf in the primary winding and thereby current increases in the
primary winding to restore the original magnetic flux in the core.
TRAINING DEPT

SJEC
continued
• When the secondary load is further increased the above process
repeats and increases the primary current in proportional to
transformation ratio.

Basically the winding of the transformer is classified as HV & LV by


the manufacturer, and it is the user who decides which is Primary
and secondary. The winding to which we give power (HV/LV) is
called Primary winding and the winding from which we take power
(LV/HV) is called Secondary winding.
TRAINING DEPT

SJEC
Identifying terminals & Vector
Groups
• First consider the case of single phase transformers.
Usually one of the primary winding terminal & one of the secondary
winding terminal will have some kind of identical marking indicating
them as identical terminals.
Note down the diagram below. It has 4 terminals, two for primary &
two for secondary. Primary winding is marked as 1U & 1V whereas
TRAINING DEPT

SJEC
Continued…..
Secondary terminals are marked 2u & 2v. A dot is placed at 1U & 2u. This
dot has some significance. It indicates the direction (polarity) of winding
(voltage) w.r.t other terminal ie when 1U is +ve wrt 1V then 2u is +ve wrt 2v.

This indicates that when 1V & 2v are made as reference for their respective
windings and the phase angle between primary (1U1V) & secondary
(2u2v) voltage measured will give 0 deg phase shift.

Now if 1V & 2u are made as reference for their respective windings and the
phase angle between primary (1U1V) & secondary (2v2u) voltage
measured will give 180 deg phase shift.

Therefore the above two condition may be considered as 12 o clock & 6 o


clock vector group. However this vector has no meaning since it is decided
only by external connections. A single phase transformer can be made as
12 o clock or 6 o clock without any difficulty.
TRAINING DEPT

SJEC
Continued…
This is not the case with 3 phase transformers.
Now let us examine the importance of this 12 o clock & 6 o clock
vector group in single phase transformers. The significance of
vector group lies when there is a need to connect transformers in
parallel. Refer the ckt below.
TRAINING DEPT

SJEC
Continued….
In the above ckt the identical terminals of two different transformers
are connected together. (via corresponding bus bar) This presents
no problem in parallel operation. Now consider below ckt.
TRAINING DEPT

SJEC
Continued….
In this case, transformer 2 is having 6 o clock vector group, whereas
transformer 1 is having 12 o clock vector group. When these two
transformers are connected parallel in above manner it is worse
than a dead short and there will be enormous short circuit current
limited only by winding resistance & bus bar resistance which is very
very less.
TRAINING DEPT

SJEC
VECTOR GROUP
VECTOR group of transformers and its significance
The waveform of secondary winding is a true replica of primary
winding waveform (provided there is continuous change in the
waveform and there is no saturation in core).
The Amplitude & RMS value of the waveform change based on the
transformation ratio. The frequency is not changed. But the two
waveforms may or may not be in phase with each other. There is a
phase angle difference between the two waveforms and this phase
angle remains constant until the vector group is undisturbed.

This phase angle difference plays significance when trying to


operate transformers in parallel, as these phase angle difference
results in local circulating currents as we saw with some examples
in previous slides.

While defining VECTOR groups the HV winding phasor is taken as


reference. Mostly 12 o clock is mentioned as 0 o clock.
TRAINING DEPT

SJEC
PHASE VOLTAGE / LINE VOLTAGE
.
This is the voltage phasor of 3
phase balanced system.
VR, VY, VB are three phase voltages.
VR-Y, VY-B, VB-R three LINE voltages.
Vectorial subtraction is obtained by
R-Y = R+(-Y) ie reverse the
vector to be subtracted and add it to
the vector from which it is to be
subtracted.
It is seen from the vector diagram
that
VR-Y leads VR by 30o, VY-
B leads VY by 30 and
o

VB-R leads VB by 30o.


TRAINING DEPT

Therefore VL=√3VPh and VL leads VPh by 30o (In a star connected winding)
This the relation between phase voltage and line voltage.
SJEC
LINE & PHASE VOLTAGE RELATIONSHIP IN 3 PHASE
CONNECTION

STAR CONNECTION
The line voltage leads phase voltage by 30
degrees in STAR connected winding. VL=√3VPh
The line current and phase current are in phase
and equal in magnitude. IL= IPh
DELTA CONNECTION
The line voltage and phase voltage are in phase
and equal in magnitude in DELTA connection
The line current lags phase current by 30
degrees in DELTA connected winding. IL= √3IPh
TRAINING DEPT

SJEC
VECTOR GROUPS IN STAR CONNECTED WINDINGS
For all purpose of theory and calculation a 3 phase transformer may
considered as a 3 single phase transformers connected as per
requirement.
Consider a 3 phase transformer with both primary and secondary
winding connected in STAR connection.
When we say STAR connection all similar ends (either starting or
ending ends and not a mixture) of a particular winding are
connected together.

CORRECT CONNECTION INCORRECT CONNECTION


TRAINING DEPT

SJEC
HV SIDE Yy0
.

HV SIDE PHASOR LV SIDE PHASOR


LV SIDE

Applying the same concept of single phase transformer vector group, when R phase
HV is +ve, R phase LV is also positive. The same logic applies for all other 2 phases.
This connection is a 12 o clock vector group (zero degree phase shift also 0 o clock).
This is more explained by phasor diagram shown above. It seen from the phasor
diagram there is no phase difference between respective vectors. Hence this is a 12
o clock connection.
TRAINING DEPT

Here point in both windings are formed by shorting finishing ends in both HV & LV
sides. Similar vector group may also be formed by shorting starting ends of both HV
& LV windings. SJEC
. HV SIDE Yy6

LV SIDE PHASOR
HV SIDE PHASOR
LV SIDE
Applying the same concept of single phase transformer vector group, when R phase HV is +ve,
R phase LV is -ve. The same logic applies for all other 2 phases. This connection is a 6 o clock
vector group (180 degree phase shift). This is more explained by phasor diagram shown above.
It seen from the phasor diagram there is a phase difference of 180 degrees between respective
vectors. Hence this is a 6 o clock connection.
Here the star point in HV winding is formed by shorting finishing ends and star point of LV
winding is formed by shorting starting ends. Hence we get the phase shift of 180 degrees in
secondary winding only.
Similar vector group may also be formed by shifting the star point in both HV & LV windings. For
TRAINING DEPT

simplicity only one is shown here.


SJEC
VECTOR GROUPS IN DELTA CONNECTED WINDINGS
For all purpose of theory and calculation a 3 phase transformer may
considered as a 3 single phase transformers connected as per
requirement.
Consider a 3 phase transformer with both primary and secondary
winding connected in DELTA connection.
When we say DELTA connection all dis-similar ends (starting end of
one winding is connected to finishing end of other winding and
similar ends are never connected together) of different ends are
connected together.

CORRECT CONNECTION INCORRECT CONNECTION


TRAINING DEPT

SJEC
HV SIDE
Dd0

HV SIDE PHASOR LV SIDE PHASOR

LV SIDE
Applying the same concept of single phase transformer vector group, when R phase HV is +ve,
R phase LV is also positive. The same logic applies for all other 2 phases. This connection is a
12 o clock vector group (zero degree phase shift. Also 0 o clock)
This is more explained by phasor diagram shown above. It seen from the phasor diagram there
is no phase difference between respective vectors. Hence this is a 12 o clock connection.
Here in HV side starting end of R is connected to finishing end of B, starting end of Y is
connected to finishing end of R and starting end of B is connected to finishing end of Y.
TRAINING DEPT

Similarly in LV side starting end of R is connected to finishing end of B, starting end of Y is


connected to finishing end of R and starting end of B is connected to finishing end of Y.
SJEC
HV SIDE
Dd6

HV SIDE PHASOR LV SIDE PHASOR

LV SIDE
Applying the same concept of single phase transformer vector group, when R phase HV is +ve, R phase LV
is also positive. The same logic applies for all other 2 phases. This connection is a 6 o clock vector group
(zero degree phase
shift. This is more explained by phasor diagram shown above. It seen from the phasor diagram there is a 180
degree phase difference between respective vectors. Hence this is a 6 o clock connection.
Here in HV side starting end of R is connected to finishing end of B, starting end of Y is connected to finishing
end of R and starting end of B is connected to finishing end of Y.
Similarly in LV side starting end of R is connected to finishing end of B, starting end of Y is connected to
TRAINING DEPT

finishing end of R and starting end of B is connected to finishing end of Y.


But the difference is made in taking out the external LV leads which is opposite to that of previous case. This
gives 180 degrees phase shift. SJEC
VECTOR GROUPS IN STRAR - DELTA CONNECTED
HV SIDE WINDINGS

Yd1

LV SIDE PHASOR

LV SIDE
HV SIDE PHASOR
This is an eg of 1 o clock connection. Just rotate both HV phasors
and LV phasor by 30 degree clockwise and view R phase line
voltages in both the cases. This forms the two hands of a clock forming
TRAINING DEPT

1 o clock. I hope the diagram itself is clear and needs no further


explanation
SJEC
Dy11 Continued…
HV SIDE

HV SIDE PHASOR
LV SIDE LV SIDE PHASOR

This is an eg of 11 o clock connection. Just view R phase line


voltages in both the cases. This forms the two hands of a clock forming
11 o clock. I hope the diagram itself is clear self explanatory and needs
TRAINING DEPT

no further explanation

SJEC
continued
Yd7
HV SIDE

LV SIDE PHASOR
HV SIDE PHASOR
LV SIDE

This is an eg of 7 o clock connection. Just rotate both HV phasors


and LV phasor by 30 degree clockwise and view R phase line
voltages in both the cases. This forms the two hands of a clock forming
TRAINING DEPT

7 o clock. I hope the diagram itself is clear and needs no further


explanation
SJEC
Dy5
HV SIDE

HV SIDE PHASOR LV SIDE PHASOR


LV SIDE

This is an eg of 5 o clock connection. Just view R phase line


voltages in both the cases. This forms the two hands of a clock forming
5 o clock. I hope the diagram itself is clear self explanatory and needs
TRAINING DEPT

no further explanation

SJEC
Differential Protection
Now imagine a long tube open at both ends.
How you will check for any defects in the
tube?
Pour water (1litre) into one end. If you get same 1 litre through other
end, there is no leak. There is no possibility of getting more than 1 litre.
If you get anything less than 1 litre there is leak somewhere in the tube.
TRAINING DEPT

SJEC
Continued……
This may be imagined as a transformer of unity (no step up no step
down) transformation ratio.

The same way, a transformer also transforms the power received to


sends it out. If there is any fault, there exists difference between input
power and output power.
For differential protection instead of measuring power, we measure
only current.
When we compare to quantities, first it is important to define a common
base. For this we have to define any one winding as reference and
convert all other winding currents to the reference winding based on
transformation ratio.
This alone is not sufficient. We have already seen that there exists
some difference in phase angle between different winding currents. So
we have to apply some phase angle correction correspondingly,
TRAINING DEPT

SJEC
Contined…
We will see more on differential protection with numerical eg next week
TRAINING DEPT

SJEC
QUESTIONS - 2
1.I need each of you to send minimum 5 transformer name plate details
in any form (photograph, scanned copies, hand drawn etc) but actual
transformer data complete in all respects (including mechanical weight,
dimensions etc).

Those who have not send their replies to QUESTIONS-1, kindly send it
immediately as I have to consolidate the results and send it to HQ.
If I didn’t receive before next week, I will mark NO RESPONSE and will
be submitted to HQ.
Answers to QUESTIONS-1 will be published along with QUESTIONS-3
next week.

Best wishes.
TRAINING DEPT

SJEC
.
QUESTIONS-1
TRAINING DEPT

SJEC
QUESTIONS
• Any doubts on previous slides feel free to
get it clarified. All further presentations
depends upon previous slides.

• Now we have nearly finished basics. Next


week we will enter into transformers
Protection.
• Please provide your comments on clarity
of information.
TRAINING DEPT

SJEC